Tyco TY-FRB Series User manual

Page 1 of 4 AUGUST 2022 TFP666
Worldwide
Contacts
www.tyco-fire.com
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycore/tfp666
Series TY-FRB – 5.6 and 8.0 K-factor
Conventional (Old Style) Sprinklers
Quick Response
General
Description
The TYCO Series TY-FRB, 5.6 and
8.0 K-factor, Conventional Sprinklers
described in this technical data sheet
are Quick Response, Standard Cover-
age, decorative 3 mm glass bulb type
spray sprinklers. These sprinklers are
intended to be installed either pendent
or upright and, in either position,
produce a spherical water discharge
pattern with approximately 50% of
the discharge directed upwards and
approximately 50% of the discharge
directed downwards.
Conventional sprinklers are generally
used with Ordinary and Extra High
Hazard Class Systems, as dened by
the automatic sprinkler system instal-
lation rules of the country and author-
ity having jurisdiction. The NATIONAL
FIRE PROTECTION ASSOCIATION
(NFPA) permits the use of “Old Style
Sprinklers” where special construction
features require a unique water distri-
bution, for the protection of fur vaults,
or to replace similar sprinklers that had
been installed prior to 1955.
Corrosion-resistant coatings, where
applicable, are utilized to extend the life
of copper alloy sprinklers beyond that
which would otherwise be obtained
when exposed to corrosive atmo-
spheres. Although corrosion-resistant
coated sprinklers have passed the
standard corrosion tests of the appli-
cable Approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently,
it is recommended that the end user
be consulted with respect to the suit-
ability of these coatings for any given
corrosive environment. The effects of
ambient temperature, concentration of
chemicals, and gas/chemical velocity
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
NOTICE
The TYCO Series TY-FRB Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applica-
ble standards of the NFPA, in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identication
Numbers (SINs)
TY3631 . . . . . . . . . . 5.6K, 1/2 in. NPT
TY4631 . . . . . . . . . . 8.0K, 3/4 in. NPT

TFP666
Page 2 of 4
Technical
Data
Approvals
UL and C-UL Listed
LPCB Approved
VdS Approved
NYC Approved
EAC Approved
(See Table A for complete approval
information.)
Sprinklers with Polyester Finish are UL
and C-UL Listed as Corrosion-Resistant
Sprinklers.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=5.6 gpm/psi½(80,6 Lpm/bar½)
K=8.0 gpm/psi½(115,2 Lpm /bar½)
Temperature Ratings
See Table A
Finishes
Sprinkler: See Table A
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . . Brass/Copper
Sealing Assembly ..Beryllium Nickel w/TEFLON
Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deector . . . . . . . . . . . . . . . . . . . . . . . . . Copper
Operation
The glass bulb contains a uid which
expands when exposed to heat. When
the rated temperature is reached, the
uid expands sufciently to shatter the
glass bulb, allowing the sprinkler to
activate and water to ow.
Design
Criteria
The TYCO Series TY-FRB Conventional
Sprinklers are intended for re protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable Listing or
Approval agency such as UL Listing is
based on NFPA 13 requirements. The
Series TY-FRB Conventional Sprinklers
are only for non-recessed applications.
* **
*
****
*
*
SHOWN
PENDENT
SHOWN
PENDENT
CROSS SECTION
SHOWN UPRIGHT
CROSS SECTION
SHOWN UPRIGHT
7/16" (11,1 mm)
NOMINAL
MAKE-IN
ESCUTCHEON
PLATE SEATING
SURFACE
ESCUTCHEON
PLATE SEATING
SURFACE
Pipe thread connections per
ISO 7-1 can be provided on
special request.
Temperature rating is
indicated on Deector
or adjacent to orice
seat on Frame.
WRENCH
FLATS
WRENCH
FLATS
Sealing
Assembly
Compression
Screw
1/2"
NPT
2-3/16"
(55,6 mm)
1-1/2"
(38,1 mm)
1-1/2"
(38,1 mm)
2
4
5
6
1
33
1
2
5
4
6
1
2
Bulb
Button
Frame
-
-4-
3-
5-
Deector6 -
Components:
3/4"
NPT
1/2" (12,7 mm)
NOMINAL
MAKE-IN
2-1/4"
(57,2 mm)
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4" NPT MODELS)
FIGURE 1
SERIES TY-FRB 5.6 K-FACTOR (TY3631) AND 8.0 K-FACTOR (TY4631)
QUICK RESPONSE CONVENTIONAL SPRINKLERS
FIGURE 2
W-T YPE 6
SPRINKLER WRENCH

TFP666
Page 3 of 4
Installation
The Series TY-FRB Sprinklers must
be installed in accordance with this
section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm) for the 135°F (57°C) to
3/32 in. (2,4 mm) for the 286°F (141°C)
temperature ratings.
A leak-tight 1/2 in. NPT sprinkler joint
should be obtained with a torque of
7 to 14 lb-ft (9,5 to 19,0 N∙m). A leak-
tight 3/4 in. NPT sprinkler joint should
be obtained with a torque of 10 to
20 lb-ft (13,4 to 26,8 N∙m). Higher levels
of torque may distort the sprinkler inlet
and cause leakage or impairment of the
sprinkler.
Step 1. With pipe thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
tting.
Step 2. Tighten the sprinkler into the
sprinkler tting using only the W-Type
6 Sprinkler Wrench (See. Figure 2).
With reference to Figure 1, the W-Type
6 Sprinkler Wrench is to be applied to
the Wrench Flats.
Care and
Maintenance
The TYCO Series TY-FRB Sprinklers
must be maintained and serviced in
accordance with this section.
Before closing a re protection system
main control valve for maintenance
work on the re protection system that
it controls, permission to shut down the
affected re protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notied.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or other-
wise altered after leaving the factory.
Modied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. Refer to the Instal-
lation section for additional information.
Frequent visual inspections are rec-
ommended to be initially performed
for corrosion resistant coated sprin-
klers, after the installation has been
completed, to verify the integrity of the
corrosion resistant coating. Thereafter,
annual inspections per NFPA 25 should
sufce; however, instead of inspecting
from the oor level, a random sampling
of close-up visual inspections should
be made, so as to better determine the
exact sprinkler condition and the long
term integrity of the corrosion-resistant
coating, as it may be affected by the
corrosive conditions present.
The owner is responsible for the inspec-
tion, testing, and maintenance of their
re protection system and devices in
compliance with this document, as well
as with the applicable standards of the
NATIONAL FIRE PROTECTION ASSO-
CIATION (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualied Inspec-
tion Service in accordance with local
requirements and/or national codes.
Type Temperature
Rating Bulb
Liquid Color
Sprinkler Finish
Natural
Brass Chrome
Plated Polyester* Lead
Coated
5.6K
CONVENTIONAL
(TY3631)
135°F (57°C) Orange
1, 2, 4, 5, 7 1, 2, 4, 7
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286°F (141°C) Blue
8.0K
CONVENTIONAL
(TY4631)
135°F (57°C) Orange
1, 2, 3, 4, 5, 7 1, 2, 4, 7
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286°F (141°C) Blue
Notes:
1. UL Listed
2. C-UL Listed
3. LPCB Approved (LPCB Ref. No. 094a/06 & 007k/04)
4. Approved by the City of New York under MEA 354-01-E
5. VdS Approved (For details, contact Johnson Controls, Enschede, Netherlands, Tel. +31-53-428-4444 / Fax +31-53-428-3377.)
6. Where polyester-coated and lead-coated sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-
Resistant Sprinklers
* Frame and deector only
7. EAC Approved
TABLE A
LABORATORY LISTINGS AND APPROVALS

EDIT DATA SHEET NUMBER
Page 4 of EDIT PAGE COUNT
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a trademark of The Chemours Company FC, LLC
1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-re.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with
NPT Thread Connections
Specify: (specify) SIN, Series TY-FRB
Conventional Sprinkler Quick
Response, (specify) SIN, K=(specify),
(specify) temperature rating, with
(specify) nish, P/N (specify from Table
B)
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
P/N 57 - XXX - X - XXX
SIN
373 5.6K CONVENTIONAL (1/2 in. NPT) TY3631
393 8.0K CONVENTIONAL (3/4 in. NPT) T Y4 631
SPRINKLER
FINISH
1NATURAL
BRASS
3PURE WHITE (RAL9010)*
POLYESTER
4SIGNAL WHITE (RAL9003)
POLYESTER
5JET BLACK (RAL9005)**
POLYESTER
9CHROME
PL ATED
TEMPERATURE
RATING
135 135°F (57°C)
155 155°F (68°C)
175 175°F (79°C)
200 200°F (93°C)
286 286°F (141°C)
Notes:
* Eastern Hemisphere sales only
** Available only for temperature ratings of 155°F (68°C) or 200°F (93°C)
TABLE B
SERIES TY-FRB CONVENTIONAL SPRINKLERS
PART NUMBER SELECTION

TFP666
Change History Appendix
Worldwide
Contacts
www.tyco-fire.com
1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
ISSUE DATE NOTES
08-22
Page 1, updated QR code and URL; Page 4, changed corporate address and telephone number to 1467
Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220, formerly 1400 Pennbrook Parkway,
Lansdale, PA 19446 | Telephone +1-215-362-0700.
04-22
Page 1, added QR code and URL to allow convenient access to electronic version from printed doc-
ument; Page 2, Approvals sub-section, added EAC Approved; Page 3, Table A, added EAC Approved
for all nishes and temperature ratings.
03-20 Removed LPCB certication from TY4631 5.6 K sprinkler.
08-18
Updated Tyco® branding and document format; Added Johnson Controls copyright; Added disclaimer
stating specications and information subject to change without notice; Added reference to Regulatory
and Health Warning Technical Data Sheet TFP2300.
01-17 Corrected Table B caption to Series TY-FRB, formerly shown as Series TY-B.
10 -14 Corrected K-factors and Temperature Ratings in Table B Part Number Selection.
06-14 Corrected SIN numbers in Table A Laboratory Listings and Approvals and Table B Part Number Selection.
05-14 Claried Polyester nish; Updated and standardized RAL color nishes.
07-04 Added reference to Installer Warning data sheet TFP700; Added LPCB Reference Numbers; Added
White (RAL9010) nish for Eastern Hemisphere sales.
01-03 Added new Tyco Fire & Building Products masthead.
09-02 New Technical Data Sheet TFP666 describes Series TY-FRB Conventional Sprinklers.
Other manuals for TY-FRB Series
17
This manual suits for next models
2
Table of contents
Other Tyco Irrigation System manuals

Tyco
Tyco RFII Series User manual

Tyco
Tyco ESFR-17 User manual

Tyco
Tyco Rapidresponse LFII Series User manual

Tyco
Tyco DS-1 Series User manual

Tyco
Tyco TY-B Series User manual

Tyco
Tyco G5 Sprinkler Guard User manual

Tyco
Tyco G1 User manual

Tyco
Tyco ESFR-22 User manual

Tyco
Tyco DV-5 User manual

Tyco
Tyco TY3201 User manual

Tyco
Tyco RFII Series User manual

Tyco
Tyco RFII Series User manual

Tyco
Tyco ESFR-22 User manual

Tyco
Tyco RFII-MRI Series User manual

Tyco
Tyco RSV-1 User manual

Tyco
Tyco TY-B Series User manual

Tyco
Tyco DS-1 Series User manual

Tyco
Tyco TY-FRB Series User manual

Tyco
Tyco ELOC User manual

Tyco
Tyco ESFR-14 User manual