Tyco G2 User manual

General
Description
The Model G2 Sprinkler Guard (Ref.
Figure 1) is designed for use with
Series ELO-231, ELO-231B, or
ELO231FRB Sprinklers that may be
located in areas that make them sus-
ceptible to mechanical or physical
damage.
The WS-2 Shield (Ref. Figure 2) is de-
signed to shield pendent sprinklers
from water spray of higher elevation
sprinklers (e.g., rack storage sprinkler
installations). When the WS-2 Shield
is used with the Series ELO-231,
ELO231B, or ELO-231FRB Pendent
Sprinklers, the assemblies become
Pendent Intermediate Level Sprin-
klers intended for use in fire sprinkler
systems designed in accordance with
the standard installation rules recog-
nized by the applicable Listing agen-
cy (i.e., UL Listing is based on NFPA
requirements).
The Model WSG-2 Sprinkler Guard
with Shield (Ref. Figure 3), in addition
to providing protection from mechani-
cal or physical damage, shields the
upright sprinkler from water spray of
higher elevation sprinklers (e.g., rack
storage sprinkler installations). When
the WSG-2 is used with the Series
ELO-231, ELO-231B, or ELO-231FRB
Upright Sprinklers, the assemblies
become Upright Intermediate Level
Sprinklers intended for use in fire
sprinkler systems designed in accor-
dance with the standard installation
rules recognized by the applicable
Listing agency (i.e., UL Listing is based
on NFPA requirements).
The G2, WS-2, and WSG-2 are a re-
designation for the Central G2, WS-2,
and WSG-2.
NOTICE
The Model G2 Sprinkler Guard, WS-2
Shield, and WSG-2 Sprinkler Guard
with Shield described herein must be
installed and maintained in compli-
ance with this document, and with the
applicable standards of the National
Fire Protection Association, in addi-
tion to the standards of any authori-
ties having jurisdiction. Failure to do
so may impair the integrity of these
devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or manufac-
turer should be contacted relative to
any questions.
Technical
Data
Approvals
UL and C-UL Listed. FM Approved.
(Refer to Table A)
Finishes
Red Painted and Zinc Coated
Physical Characteristics
Welded assembly fabricated from
carbon steel
Design Criteria
In accordance with the requirements
of the NFPA, sprinkler guards shall be
listed. Guards are only listed for use
with specified sprinklers; therefore,
the G2 and WSG-2 must only be used
with the Series ELO-231, ELO-231B,
and ELO-231FRB Sprinklers shown in
Table A.
G2
WS-2
WSG-2
Model G2 Sprinkler Guard, Model WS-2 Shield, and
Model WSG-2 Sprinkler Guard with Shield
Series ELO-231, ELO-231B, and ELO-231FRB Sprinklers
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Page 1 of 4 MAY, 2009 TFP782
Installation
The Models G2, WS-2, and WSG-2 are
to be installed as follows:
G2 Sprinkler Guard (Upright and
pendent Sprinklers) and WSG-2
Sprinkler Guard with Shield (Upright
Sprinklers)
Step 1. The G2 and WSG-2 is to be
mounted on the sprinkler after the
sprinkler has been installed in accor-
dance with its applicable technical
data sheet.
Step 2. With the Clips loose, first
spread the two halves of the Sprin-
kler Guard just enough to pass by the
sprinkler deflector from the side. Then,
once again spread the two halves of
the Sprinkler Guard just enough to
pass over the sprinkler wrench flats
onto the “Thread Relief” portion of
the sprinkler. (Refer to Figures 1 and
3.)
Step 3. With the Sprinkler Guard posi-
tioned on the “Thread Relief” portion
of the sprinkler, engage the Clips and
then slide the Clips until they seat in
the “1/2 inch NPT Sprinkler Guard
Clip Detents” or “3/4 inch NPT
Sprinkler Guard Clip Detents”, as
applicable, to complete the installa-
tion as shown in Figures 1 and 3.
Make sure that this action results in a
tight fit between the Clip and the Rib
Detents, If not, bend the clip slightly
and repeat the process until a tight fit
is obtained.
Note: The Clips must seat securely to
the appropriate Rib Detents in order to
be considered fully seated and in order
to complete the installation.
Note: The G2 and WSG-2 may be located
in any position relative to the sprinkler
frame arms.
WS-2 Shield (Pendent Sprinklers with
or without G2 Sprinkler Guard)
Step 1. The WS-2 Shield is to be in-
stalled onto the sprinkler before the
sprinkler is installed in accordance
with its applicable technical data
sheet.
Step 2. Thread the WS-2 Shield onto
the sprinkler threads with the stamped
marking toward the sprinkler deflec-
tor and just to the end of the pipe
threads.
Step 3. Install the sprinkler in accor-
dance with its applicable data sheet.
Step 4. To complete the installation
of the WS-2, rotate the WS-2 Shield
clockwise (looking up) until it seats
against the sprinkler fitting.
As applicable, the G2 Sprinkler Guard
can now be installed.
SPRINKLER
(76,2 mm)
WITH SPRINKLER
THREAD RELIEF
BASE RING
CLIP
DETENT)
AT 1/2" NPT
(ENGAGED
SPRINKLER
GUARD CLIP
ENGAGE
3"
3/4" NPT
DETENT
SPRINKLER
GUARD CLIP
3-1/4" (82,6 mm) DIA.
RING
BASE
BAR
SHOWN
SERIES
1/2" NPT
ELO-231
3-5/8"
(92,1 mm)
SPRINKLERS
PENDENT
UPRIGHT OR
USE WITH
SPRINKLER
SERIES
TFP
SIN
CSC
SIN
SPRINKLER
TYPE
SPRINKLER
K-FACTOR
MOUNTING
LOCATION
APPROVALS
G2
GUARD
WS-2
SHIELD
WSG-2
WITH
SHIELD
GUARD
ELO-231
T Y5111 C5111 Upright 11.2 (3/4” NPT) Thread Relief 1,2 N/A 1
T Y5111 C5111 Pendent 11.2 (3/4” NPT) Thread Relief 1,2 1N/A
T Y5811 C5 811 Upright 11.2 (1/2” NPT) Thread Relief 1,2 N/A 1
ELO-231B
TY5151 C5151 Upright 11.2 (3/4” NPT) Thread Relief 1,2 N/A 1
TY5251 C5251 Pendent 11.2 (3/4” NPT) Thread Relief 1,2 1N/A
TY5851 C5851 Upright 11.2 (1/2” NPT) Thread Relief 1,2 N/A 1
ELO-231FRB TY5131 C5131 Upright 11.2 (3/4” NPT) Thread Relief 1,2 N/A 1,2
TY5231 C5231 Pendent 11.2 (3/4” NPT) Thread Relief 1,2 1,2 N/A
APPROVALS & NOTES:
1. Listed by Underwriters Laboratories Inc. and Underwriters Laboratories Inc. for use in Canada.
2. Approved by Factory Mutual Research Corporation.
N/A Not Applicable for noted sprinkler.
TABLE A — LABORATORY LISTINGS AND APPROVALS
FIGURE 1
MODEL G2 SPRINKLER GUARD — DIMENSIONS
Page 2 of 4 TFP782
SPRINKLER
ELO-231FRB
ASSEMBLED
DETENT)
(79,4 mm)
3-1/8"
1/2" NPT
DETENT
SPRINKLER
GUARD CLIP
GUARD CLIP
SPRINKLER
(ENGAGED
AT 3/4" NPT
CLIP
3-1/4" (82,6 mm) DIA.
BAR
BASE
RING
3/4" NPT
SHOWN
5" (127,0 mm) DIA.
SERIES
SHIELD
FACTORY
(93,7 mm)
3-11/16"
ONLY
UPRIGHT
SPRINKLERS
USE WITH
WITH SPRINKLER
THREAD RELIEF
BASE RING
ENGAGE
FIGURE 3
MODEL WSG2 SPRINKLER GUARD WITH SHIELD — DIMENSIONS
Care and
Maintenance
The Models G2, WS-2, and WSG-2 do
not require any regularly scheduled
maintenance; however, proper instal-
lation of the Sprinkler Guards and/
or Shields should be verified during
the annual visual inspection of the
sprinklers.
The owner is responsible for the in-
spection, testing, and maintenance
of their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service.
2-5/16"
(58,7 mm)
INSTALLED
MODEL WS-2
SHIELD
3/4" NPT
FIELD SERIES
SPRINKLER
3/4" NPT
SHOWN
ELO-231B
5" (127,0 mm) DIA.
(71,4 mm)
2-13/16"
ONLY
PENDENT
SPRINKLERS
USE WITH
GUARD
MAY BE USED
WITH MODEL G2
IN CONJUNCTION
FIGURE 2
MODEL WS-2 SHIELD — DIMENSIONS
TFP782 Page 3 of 4
Page 4 of 4 TFP782
© 2009 TYCO FIRE SUPPRESSION & BUILDING PRODUCTS
, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Limited
Warranty
Products manufactured by Tyco Fire
Suppression & Building Products
(TFSBP) are warranted solely to the
original Buyer for ten (10) years against
defects in material and workmanship
when paid for and properly installed
and maintained under normal use and
service. This warranty will expire ten
(10) years from date of shipment by
TFSBP. No warranty is given for prod-
ucts or components manufactured by
companies not affiliated by ownership
with TFSBP or for products and com-
ponents which have been subject to
misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by TFSBP to be defective
shall be either repaired or replaced, at
TFSBP’s sole option. TFSBP neither
assumes, nor authorizes any person
to assume for it, any other obligation
in connection with the sale of products
or parts of products. TFSBP shall not
be responsible for sprinkler system
design errors or inaccurate or incom-
plete information supplied by Buyer or
Buyer’s representatives.
In no event shall TFSBP be liable, in
contract, tort, strict liability or under
any other legal theory, for inciden-
tal, indirect, special or consequential
damages, including but not limited to
labor charges, regardless of whether
TFSBP was informed about the pos-
sibility of such damages, and in no
event shall TFSBP’s liability exceed an
amount equal to the sales price.
The foregoing warranty is made in
lieu of any and all other warranties,
express or implied, including warran-
ties of merchantability and fitness for
a particular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
Contact your local distributor for
availability.
G2 Sprinkler Guard:
Specify: Model G2 Sprinkler Guard
having a (specify) finish, P/N (specify).
Red Painted ..............P/N 56-000-1-087
Zinc Coated . . . . . . . . . . . . . . P/N 56-000-1-086
WS-2 Shield:
Specify: Model WS-2 Shield for
(specify 3/4 or 1/2) inch NPT sprinkler
threads and having a (specify) finish,
P/N (specify).
3/4” NPT
Red Painted ..............P/N 56-000-1-083
3/4” NPT
Zinc Coated . . . . . . . . . . . . . . P/N 56-000-1-082
1/2” NPT
Red Painted ..............P/N 56-000-1-081
1/2” NPT
Zinc Coated . . . . . . . . . . . . . . P/N 56-000-1-080
WSG-2 Guard with Shield:
Specify: Model WSG-2 Sprinkler
Guard with Shield having a (specify)
finish, P/N (specify).
Red Painted ..............P/N 56-000-1-098
Zinc Coated1 .............P/N 56-000-1-097

Other manuals for G2

1

This manual suits for next models

5

Other Tyco Irrigation System manuals

Tyco CC1 User manual

Tyco

Tyco CC1 User manual

Tyco EC-5 Series User manual

Tyco

Tyco EC-5 Series User manual

Tyco TY-FRB Series Operator's manual

Tyco

Tyco TY-FRB Series Operator's manual

Tyco ESFR-17 User manual

Tyco

Tyco ESFR-17 User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco DS-1 TY3255 Operating and maintenance instructions

Tyco

Tyco DS-1 TY3255 Operating and maintenance instructions

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco RapidResponse SIN TY4334 Instruction Manual

Tyco

Tyco RapidResponse SIN TY4334 Instruction Manual

Tyco LFII Series User manual

Tyco

Tyco LFII Series User manual

Tyco ESFR-25 User manual

Tyco

Tyco ESFR-25 User manual

Tyco ESFR-1 User manual

Tyco

Tyco ESFR-1 User manual

Tyco ELOC User manual

Tyco

Tyco ELOC User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco RAVEN Institutional TY3281 User manual

Tyco

Tyco RAVEN Institutional TY3281 User manual

Tyco AquaMist ULF AM27 User manual

Tyco

Tyco AquaMist ULF AM27 User manual

Tyco TY3201 User manual

Tyco

Tyco TY3201 User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco EC-8 Series User manual

Tyco

Tyco EC-8 Series User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco Rapidresponse LFII Series User manual

Tyco

Tyco Rapidresponse LFII Series User manual

Tyco TY-FRFS User manual

Tyco

Tyco TY-FRFS User manual

Tyco ESFR-34 User manual

Tyco

Tyco ESFR-34 User manual

Tyco BB User manual

Tyco

Tyco BB User manual

Tyco TY-FRL Series User manual

Tyco

Tyco TY-FRL Series User manual

Popular Irrigation System manuals by other brands

Tyco Fire Product CENTRAL BV4-QREC instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV4-QREC instruction manual

Rain Bird 552 Series Operation & maintenance manual

Rain Bird

Rain Bird 552 Series Operation & maintenance manual

Uponor MLC-S Mounting instructions

Uponor

Uponor MLC-S Mounting instructions

Tyco Fire Product CENTRAL BV instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV instruction manual

Autopot easy2grow 48 Set-up guidelines

Autopot

Autopot easy2grow 48 Set-up guidelines

Task Force Tips Masterstream Series INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

Task Force Tips

Task Force Tips Masterstream Series INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

Duramaxx Sprizzz manual

Duramaxx

Duramaxx Sprizzz manual

Kompernass KH4083-10 operating instructions

Kompernass

Kompernass KH4083-10 operating instructions

DIG 400A Series instruction manual

DIG

DIG 400A Series instruction manual

Ebinger LEADER 50 Instruction booklet

Ebinger

Ebinger LEADER 50 Instruction booklet

Eden 96122EDAMZ quick start guide

Eden

Eden 96122EDAMZ quick start guide

Kärcher WU 60/2 sun instructions

Kärcher

Kärcher WU 60/2 sun instructions

Reliable F1 Res 30 LL Bulletin

Reliable

Reliable F1 Res 30 LL Bulletin

Reliable F3QR56 manual

Reliable

Reliable F3QR56 manual

Galcon 9001D Operation and installation instructions

Galcon

Galcon 9001D Operation and installation instructions

Toro FLX35-6 Series Installation and service instructions

Toro

Toro FLX35-6 Series Installation and service instructions

Johnson Controls DS-2 Series manual

Johnson Controls

Johnson Controls DS-2 Series manual

CENTRAL ELO-231 manual

CENTRAL

CENTRAL ELO-231 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.