TFP401
Page 2 of 4
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and flow water.
Design
Criteria
The TYCO RAPID RESPONSE Series
LFII Residential Pendent and Recessed
Pendent Sprinklers (TY3934) are to
be installed in accordance with this
section.
Residential Sprinkler Design Guide
When conditions exist that are outside
the scope of the provided criteria, refer
to the Residential Sprinkler Design
Guide TFP490 for the manufactur-
er’s recommendations that may be
acceptable to the local authority having
jurisdiction.
Ceiling Types
Smooth flat horizontal, or beamed, or
sloped, in accordance with the 2013
Edition of NFPA 13D, 13R, or 13 as
applicable.
Hydraulic Design
(NFPA 13D and 13R)
For systems designed to NFPA 13D or
NFPA 13R, the minimum required sprin-
kler flow rates are given in Table A as a
function of temperature rating and the
maximum allowable coverage areas.
The sprinkler flow rate is the minimum
required discharge from each of the
total number of “design sprinklers” as
specified in NFPA 13D or NFPA 13R.
The number of “design sprinklers”
specified in NFPA 13D and 13R for wet
pipe systems is to be applied when
designing dry pipe systems.
Hydraulic Design
(NFPA 13)
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is to be the greater of the following:
• The ow rates given in Table A as a
function of temperature rating and
the maximum allowable coverage
area.
•
A minimum discharge of 0.1 gpm/ft
2
over the “design area” comprised
of the four most hydraulically
demanding sprinklers for actual
coverage areas protected by the
four sprinklers.
Obstruction to Water Distribution
Sprinklers are to be located in accor-
dance with the obstruction rules of
NFPA 13D, 13R, and 13 as applicable
for residential sprinklers as well as with
the obstruction criteria described within
the Technical Data Sheet TFP490.
Operational Sensitivity
Sprinklers are to be installed with a
deflector-to-ceiling distance of 1 to 4
inches below smooth ceilings.
For "Beamed Ceiling" conditions as
allowed by NFPA, the maximum deflec-
tor distance below the bottom of a
beam is 1-3/4 inches. See NFPA Stan-
dards for allowed beam configurations.
Sprinkler Spacing
The minimum spacing between sprin-
klers is 8 feet (2,4 m). The maximum
spacing between sprinklers cannot
exceed the length of the coverage area
(Table A) being hydraulically calculated
(e.g., maximum 12 feet for a 12 ft. x 12
ft. coverage area, or 20 feet for a 20 ft.
x 20 ft. coverage area).
Installation
The TYCO RAPID RESPONSE Series
LFII Residential Pendent and Recessed
Pendent Sprinklers (TY3934) must
be installed in accordance with this
section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm).
A leak-tight 1/2 inch NPT sprinkler joint
should be obtained by applying a min-
imum-to-maximum torque of 7 to 14
ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in an Escutch-
eon Plate by under- or over- tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Series LFII Residential Pendent
Sprinkler Installation
The Series LFII Residential Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step 1. Install pendent sprinklers in the
pendent position with the deector par-
allel to the ceiling.
Step 2. With pipe thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
tting.
Step 3. Tighten the sprinkler into the
sprinkler tting using only the W-Type
6 Sprinkler Wrench (Figure 3). With ref-
erence to Figure 1, apply the W-Type 6
Sprinkler Wrench to the wrench ats.
*
*
*
*
CROSS SECTION PENDENT RECESSED PENDENT
1-3/8"
(34,9 mm)
2"
(50,8 mm)
WRENCH
FLATS
RECESSED
ESCUTCHEON
NOMINAL MAKE-IN
SEATING SURFACE
NPT
DEFLECTOR
2-7/8" (73,0 mm) DIA.
4
3
1
2
5
6
-Compression
Screw
Deector
-
Temperature
rating is indicated
on Deector
-
Frame
Button
Sealing
Assembly
-
-
Bulb
-
FIGURE 1
RAPID RESPONSE SERIES LFII RESIDENTIAL
PENDENT AND RECESSED PENDENT SPRINKLERS (TY3934)