manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco
  6. •
  7. Irrigation System
  8. •
  9. Tyco ESFR-22 User manual

Tyco ESFR-22 User manual

Model ESFR-22
22.4 K-factor Pendent Sprinklers
Early Suppression, Fast Response
Page 1 of 4 MARCH 2020 TFP321
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
Finish
Natural Brass
Physical Characteristics
Frame � � � � � � � � � � � � � � � � � � � � � � � � � � � � �Brass
Deflector � � � � � � � � � � � � � � � � � � � � � � � � � �Bronze
Compression Screw � � � � � � � � � � Stainless Steel
Hook � � � � � � � � � � � � � � � � � � � � � � � � � � � � MONEL
Strut� � � � � � � � � � � � � � � � � � � � � � � � � � � � � MONEL
Link Assembly� � � � � � � � � � � � � � � � Solder, Nickel
Button � � � � � � � � � � � � � � � � � � � � � � � � � � � � �Brass
Sealing Assembly ��Beryllium Nickel w/TEFLON
Additional Technical Data
See Table A for additional technical
data�
Operation
The fusible link assembly is com-
prised of two link halves that are joined
together by a thin layer of solder� When
the rated temperature is reached, the
solder melts and the two link halves
separate, activating the sprinkler and
flowing water�
Applications for TYCO ESFR Sprin-
klers are expanding beyond currently
recognized installation standards�
For information on research fire tests
(for example, with flammable liquids
and aerosols) that may be accept-
able to an authority having jurisdiction,
contact Johnson Controls Technical
Services�
NOTICE
The Model ESFR-22 Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association (NFPA), in addition
to the standards of any authorities
having jurisdiction (for example, FM
Global). Failure to do so may impair the
performance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
In all cases, the appropriate NFPA or
FM installation standard, or other appli-
cable standard, must be referenced
to ensure applicability and to obtain
complete installation guidelines. The
general guidelines in this technical data
sheet are not intended to provide com-
plete installation criteria.
Sprinkler
Identification
Number
See Table A for sprinkler identification
number�
General
Description
TYCO Model ESFR-22 Pendent Sprin-
klers are Early Suppression, Fast
Response Sprinklers having a nominal
K-factor of 22�4, see Figure 1� They are
suppression-mode sprinklers that are
especially advantageous as a means of
eliminating the use of in-rack sprinklers
when protecting high-piled storage�
The Model ESFR-22 Sprinklers are pri-
marily used for ceiling-only sprinkler
protection of (but not limited to) the
following storage applications:
• most encapsulated or non-encap-
sulated common materials including
cartoned, unexpanded plastics
• uncartoned (exposed) expanded
plastics in accordance with NFPA 13
and FM Global standards
• some storage arrangements of rub-
ber tires, roll paper, flammable liq-
uids, and aerosols
For more specific criteria, see Table
A as well as the applicable design
standard�
The Model ESFR-22 can protect a
storage arrangement of 40 ft (12,2 m)
with a ceiling height of 45 ft (13,7 m)
without requiring in-rack sprinklers�
In addition, it can be installed with a
maximum deflector-to-ceiling distance
of 18 in� (460 mm)�
TFP321
Page 2 of 4
Design
Criteria
The following general guidelines pro-
vided for the TYCO Model ESFR-22
Pendent Sprinklers can be used for a
quick reference�
The National Fire Protection Associa-
tion (NFPA) and FM Global (FM Approv-
als) provide installation standards that
must be used to properly design an
automatic sprinkler system utilizing
Early Suppression, Fast Response
(ESFR) Sprinklers� The guidelines pro-
vided by NFPA and FM Approvals may
differ� Consequently, the appropri-
ate standard must be used for a given
installation�
In all cases, the appropriate NFPA
or FM Approvals installation stan-
dard must be referenced to ensure
applicability and to obtain complete
installation guidelines� The following
general guidelines are not intended to
provide complete installation criteria�
See Table B for additional information�
In addition to this technical data sheet,
the following Technical Data Sheets
describe other TYCO ESFR Sprinklers:
• TFP312
Model ESFR-25 (TY9226)
K=25�2 Pendent Sprinkler
• TFP315
Model ESFR-17 (TY7226)
K=16.8 Pendent Sprinkler
• TFP316
Model ESFR-17 (TY7126)
K=16.8 Upright Sprinkler
• TFP317
Model ESFR-17 (TY7223)
K=16.8 Pendent Sprinkler
• TFP318
Model ESFR-1 (TY6226)
K=14.0 Pendent Sprinkler
• TFP319
Model ESFR-14 (TY6236)
K=14.0 Pendent Sprinkler
• TFP320
Model ESFR-17 (TY7229)
K=16.8 Pendent Sprinkler
Roof Construction
Unobstructed or obstructed construc-
tion, such as smooth ceiling, bar joists,
beam and girder, etc� Where the depths
of the solid structural members, (for
example, beams and stem) exceed
12 in� (302 mm), install ESFR Sprinklers
in each channel formed by the struc-
tural members�
TABLE A
MODEL ESFR-22 PENDENT SPRINKLER
TECHNICAL DATA
Item Description
Sprinkler Identication Number (SIN) TY8223
K-factor, gpm/psi½(Lpm/bar½)22�4 gpm/psi½(320 Lpm/bar½)
Thread Size 1 in� NPT or ISO 7-R 1
Sprinkler Orientation Pendent
Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
Components:
WRENCH
FLATS
3-13/16"
(96,8 mm)
9/16"
(14,3 mm)
NOMINAL
MAKE-IN
1-13/16"
(46,0 mm)
THERMAL
SENSING
ELEMENT
TEMPERATURE
RATING
-Hook4
-
7
8-
5
6
-
-Link Assembly
Sealing
Button
Assembly
Strut
-
2
3-
1-
Compression
Deector
Frame
Screw
1" NPT
2" (50,8 mm)
2
3
6
4
5
8
7
1
FIGURE 1
MODEL ESFR-22 (TY8223) EARLY SUPPRESSION, FAST RESPONSE
PENDENT SPRINKLER 22.4 K-FACTOR
TFP321
Page 3 of 4
Ceiling Slope
Maximum 2 in� rise for 12 in� run (16�7%)
Maximum Coverage Area
100 ft2(9,3 m2)
In some cases, the installation stan-
dards permit a greater coverage area�
Minimum Coverage Area
64 ft2(5,8 m2) per NFPA 13 / FM Global
2-0
Maximum Spacing
• 12 ft (3,7 m) for building heights up
to 30 ft (9,1 m)
• 10 ft (3,1 m) for building heights
greater than 30 ft (9,1 m); in some
cases, installation standards permit
a greater spacing
TABLE B
MODEL ESFR-22 PENDENT SPRINKLERS
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
Minimum Spacing
8 ft (2,4 m)
Minimum Clearance to Commodity
36 in� (914 mm)
Deflector-to-Ceiling Distance
NFPA – 6 to 18 in� (152 to 457 mm)
Centerline of Thermal Sensing
Element-to-Ceiling Distance
FM Global – Refer to FM Global 2-0 for
Storage Sprinklers
Storage Type NFPA FM Global
Sprinkler Type ESFR Storage
Response Type FR QR
System Type Wet Wet
Temperature Rating ºF (ºC)116 5°F ( 74°C )
212°F (100°C)
165° F ( 74°C )
212°F (100°C)
Open Frame (i.e., no solid shelves) Single, Double, Multiple-
Row, or Portable Rack Storage of Class I-IV and Group A or
B Plastics
Refer to NFPA 13 Refer to FM 2-0 and 8-9
Solid Pile or Palletized Storage of Class I-IV and Group A or
B Plastics Refer to NFPA 13 Refer to FM 2-0 and 8-9
Idle Pallet Storage Refer to NFPA 13 Refer to FM 2-0, 8-9, and 8-24
Rubber Tire Storage Refer to NFPA 13 Refer to FM 2-0 and 8-3
Roll Paper Storage
(Refer to the Standard) Refer to NFPA 13 Refer to FM 8-21
Flammable/Ignitable Liquid Storage
(Refer to the Standard) Refer to NFPA 30 Refer to FM 7-29
Aerosol Storage
(Refer to the Standard) Refer to NFPA 30B Refer to FM 7-31
Automotive Components in Portable Racks
(Control mode only; refer to the Standard) N/A N/A
N/A – Not Applicable
TFP321
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
MONEL and INCONEL are registered trademarks of Special Metals Corporation;
TEFLON is a registered trademark of DuPont
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Installation
TYCO Model ESFR-22 Pendent Sprin-
klers must be installed in accordance
with this section�
General Instructions
Damage to the fusible Link Assem-
bly during installation can be avoided
by handling the sprinkler by the frame
arms only (that is, do not apply pres-
sure to the fusible Link Assembly),
and by using the appropriate sprinkler
wrench� Failure to do so can lead to an
unstable link assembly and premature
activation of the sprinkler� Damaged
sprinklers must be replaced�
A leak-tight 1 in� NPT sprinkler joint
should be obtained by applying a min-
imum-to-maximum torque of 20 to
30 lb-ft (26,8 to 40,2 N∙m)� Higher
levels of torque can distort the sprin-
kler inlet with consequent leakage or
impairment of the sprinkler�
Note: Install the Model ESFR-22 Pendent
Sprinkler in the pendent position (see
Figure 2).
Step 1. With pipe-thread sealant
applied, hand-tighten the sprinkler into
the sprinkler fitting� Do not apply pres-
sure to the Link Assembly, and handle
the Model ESFR-22 Pendent Sprinkler
only by the Frame arms�
Step 2. Use only the W-Type 1 Sprin-
kler Wrench (see Figure 2) to install
the Model ESFR-22 Pendent Sprinkler�
Fully engage (seat) the wrench recess
on the sprinkler wrench flats (see
Figure 1) and wrench-tighten�
Step 3. After installation, inspect the
Link Assembly of each Model ESFR-22
Pendent Sprinkler for damage� In par-
ticular, verify that the Link Assembly
and Hook are positioned as illustrated
in Figures 1 and 2, and that the Link
Assembly is not bent, creased, or
forced out of normal position in any
way� Replace damaged sprinklers�
Care and
Maintenance
TYCO Model ESFR-22 Pendent Sprin-
klers must be maintained and serviced
in accordance with this section�
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this action�
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced�
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory�
Modified sprinklers must be replaced�
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush�
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation� Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced�
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associ-
ation such as, NFPA 25, in addition to
the standards of any authorities having
jurisdiction� Contact the installing con-
tractor or product manufacturer with
any questions�
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes�
Limited
Warranty
For warranty terms and conditions, visit
www�tyco-fire�com�
Ordering
Procedure
Contact your local distributor for avail-
ability� When placing an order, indicate
the full product name and Part Number
(P/N)�
Sprinkler Assemblies with
1 in. NPT Thread Connection
Specify: Model ESFR-22 (TY8223),
K=22�4, Early Suppression, Fast
Response Pendent Sprinkler with
1 in� NPT thread connection, (specify)
temperature rating, Natural Brass, P/N
(specify):
165° F ( 74°C ) ������������������58-464-1-165
212°F (100°C) �����������������58 - 464-1-212
Special Order
Sprinkler Assemblies with
ISO 7-1 Thread Connections
Specify: Model ESFR-22 (TY8223),
K=22�4, Early Suppression, Fast
Response Pendent Sprinkler with
ISO 7-1 thread connection, (specify)
temperature rating, Natural Brass,
P/N (specify):
165° F ( 74°C ) ������������������58-465-1-165
212°F (100°C) �����������������58- 465-1-212
Sprinkler Wrench
Specify: W-Type 1 Sprinkler Wrench,
P/N 56-872-1-025
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
WRENCH
RECESS
FIGURE 2
W-TYPE 1
SPRINKLER WRENCH

Other Tyco Irrigation System manuals

Tyco 16.8 K-factor User manual

Tyco

Tyco 16.8 K-factor User manual

Tyco ESFR-1 User manual

Tyco

Tyco ESFR-1 User manual

Tyco TFP PH2 Instruction Manual

Tyco

Tyco TFP PH2 Instruction Manual

Tyco RAPID RESPONSE Series User manual

Tyco

Tyco RAPID RESPONSE Series User manual

Tyco TY-L Series User manual

Tyco

Tyco TY-L Series User manual

Tyco ESFR-17 User manual

Tyco

Tyco ESFR-17 User manual

Tyco DS-2 Series User manual

Tyco

Tyco DS-2 Series User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco ELO-231B Series User manual

Tyco

Tyco ELO-231B Series User manual

Tyco Grinnell F692 DESIGNER User manual

Tyco

Tyco Grinnell F692 DESIGNER User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco RSV-1 User manual

Tyco

Tyco RSV-1 User manual

Tyco BB User manual

Tyco

Tyco BB User manual

Tyco ESFR-25 Operating and maintenance instructions

Tyco

Tyco ESFR-25 Operating and maintenance instructions

Tyco rapid response LFII Series User manual

Tyco

Tyco rapid response LFII Series User manual

Tyco ELOC User manual

Tyco

Tyco ELOC User manual

Tyco Rapidresponse LFII Series User manual

Tyco

Tyco Rapidresponse LFII Series User manual

Tyco LFII Series User manual

Tyco

Tyco LFII Series User manual

Tyco ESFR-25 User manual

Tyco

Tyco ESFR-25 User manual

Tyco ILLUSION TY5521 User manual

Tyco

Tyco ILLUSION TY5521 User manual

Tyco HV User manual

Tyco

Tyco HV User manual

Tyco ESFR-25 User manual

Tyco

Tyco ESFR-25 User manual

Tyco DS-1 Series User manual

Tyco

Tyco DS-1 Series User manual

Tyco TY-L Series User manual

Tyco

Tyco TY-L Series User manual

Popular Irrigation System manuals by other brands

DIG ECO1 MVA instruction manual

DIG

DIG ECO1 MVA instruction manual

HYDRO-RAIN HRX-075 quick start guide

HYDRO-RAIN

HYDRO-RAIN HRX-075 quick start guide

ANC Technology GG-001B user manual

ANC Technology

ANC Technology GG-001B user manual

Reliable N252 EC quick start guide

Reliable

Reliable N252 EC quick start guide

Reliable XL Series manual

Reliable

Reliable XL Series manual

Johnson Controls tyco ULTRA K17 manual

Johnson Controls

Johnson Controls tyco ULTRA K17 manual

Hunter INSTITUTIONAL SERIES I-90 manual

Hunter

Hunter INSTITUTIONAL SERIES I-90 manual

Tyco Fire Product CENTRAL GB-LO 17/32 instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL GB-LO 17/32 instruction manual

Eden 94154EDAMZ quick start guide

Eden

Eden 94154EDAMZ quick start guide

Johnson Controls tyco TY3334 manual

Johnson Controls

Johnson Controls tyco TY3334 manual

Autopot 60Pot System Set-up guidelines

Autopot

Autopot 60Pot System Set-up guidelines

Rain Bird 32HE Installation & operating guide

Rain Bird

Rain Bird 32HE Installation & operating guide

Viking SIN VK510 Technical data

Viking

Viking SIN VK510 Technical data

Johnson Controls tyco TY-FRL Series manual

Johnson Controls

Johnson Controls tyco TY-FRL Series manual

Reliable F1FR56 quick start guide

Reliable

Reliable F1FR56 quick start guide

Tyco Fire Product Star Stealth S240 instruction manual

Tyco Fire Product

Tyco Fire Product Star Stealth S240 instruction manual

RainPoint Smart+ HCS021 user manual

RainPoint

RainPoint Smart+ HCS021 user manual

Sime EASY SYSTEM 1-2 I Design, installation and servicing instructions

Sime

Sime EASY SYSTEM 1-2 I Design, installation and servicing instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.