General
Description
The Series TY-FRL, 5.6 K-factor, Hori-
zontal Sidewall Sprinklers are quick
response - standard coverage, solder
type spray sprinklers designed for use
in light and ordinary hazard, commer-
cial occupancies such as banks, ho-
tels, shopping malls, offices, etc. They
are designed for installation along a
wall or the side of a beam and just
beneath a smooth ceiling. Horizontal
sidewall sprinklers are commonly used
instead of pendent or upright sprin-
klers due to aesthetics or building con-
struction considerations, where piping
across the ceiling is not desirable.
WARNINGS
The Series TY-FRL Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failuretodosomay
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY3321 - HSW 5.6K, 1/2"NPT
TY3321 is a redesignation for S1878
and G8946.
Technical
Data
Approvals
UL and C-UL Listed.
FM and NYC Approved.
(Refer to Table A for complete approval
information.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=5.6GPM/psi
1/2 (80,6 LPM/bar1/2)
Temperature Ratings
RefertoTableA
Finishes
Sprinkler: Refer to Table A
Physical Characteristics
Frame .............Bronze
Strut.............. Monel
Deflector............Bronze
Hook.............. Monel
Link Assembly . . . . . . . . Nickel
EjectionSpring ........Inconel
Button .............Bronze
Seal ..............Teflon†
† DuPont Registered Trademark
Operation
The fusible link (heat collector) assem-
bly is comprised of two halves that are
joined together by a thin layer of solder.
When the rated temperature is
reached, the solder melts and the two
link halves separate, allowing the
sprinkler to operate.
Design
Criteria
The 5.6 K-Factor, Series TY-FRL Hori-
zontal Sidewall Sprinklers are in-
tended for fire protection systems de-
signed in accordance with the
standard installation rules recognized
by the applicable Listing or Approval
agency (e.g., UL Listing is based on
NFPA 13 requirements); however, the
minimum distance between sprinklers
to prevent cold soldering is 8 feet (2,4
m). The Series TY-FRL Horizontal
Sidewall Sprinkler must be installed
with a deflector to ceiling distance of 4
to 6 inches (100 to 150 mm). To meet
this requirement the centerline of the
sprinkler waterway must be located 4-
5/16 to 6-5/16 inches (110 to 160 mm)
below the ceiling. Installation of the
Series TY-FRL Horizontal Sidewall
Sprinklers in recessed escutcheons
will void all manufacturer’s warranties,
as well as possibly void the sprinkler’s
Approvals and/or Listings.
Page 1 of 4 TFP140
JULY, 2004
Series TY-FRL — 5.6 K-factor
Horizontal Sidewall Sprinklers
Quick Response, Standard Coverage
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Installation
The Series TY-FRL Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. Higher levels of
torque may distort the sprinkler inlet
and cause leakage or impairment of
the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRL Horizontal Side-
wall Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. The Series TY-FRL Horizontal
Sidewall Sprinklers must be installed
with their centerline of waterway paral-
lel to the ceiling and perpendicular to
the back wall surface. The word “TOP”
on the deflector must face upwards
toward the ceiling.
Step 2. After installing an escutcheon
(as applicable) over the sprinkler pipe
threads and with pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
9 Sprinkler Wrench (Ref. Figure 2).
With reference to Figure 1, the W-Type
9 Sprinkler Wrench is to be applied to
the wrench area.
Page2of4 TFP140
FIGURE 1
QUICK RESPONSE
SERIES TY-FRL (TY3321) HORIZONTAL SIDEWALL SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
1-Frame
2-Strut
3 - Deflector
4-Hook
5-LinkAssembly
6 - Ejection Spring
7-Button
8-Seal
*Temperature rating is indicated on deflector.
**Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
W-TYPE 9 SPRINKLER
WRENCH
WRENCH
RECESS
WATERWAY
OF SPRINKLER
CENTERLINE
SURFACE
PLATE SEATING
WALL
TOP
*
(
15,9 mm
)
5/8"
NOMINAL
5/16" (7,9 mm)
DEFLECTOR
BOSS
(41,3 mm)
DEFLECTOR
1-5/8"
3.5°
2-11/16"
(
68,3 mm
)
7/16" (11,1 mm)
NOMINAL MAKE-IN
(50,8 mm)
2"
WRENCH
AREA
6
34527
WRENCH
FLANGES
NPT
81
**
1/2"
Care and
Maintenance
The Series TY-FRL Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied or over-heated sprinklers must be
replaced.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
code.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products’ sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES,ANDINNOEVENT
SHALL TYCO FIRE PRODUCTS’ LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
TFP140 Page 3 of 4
TYPE TEMP.
RATING
FRAME
COLOR
CODE
NATURAL
BRASS
CHROME
PLATED
SPRINKLER FINISH
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) for Light or Ordinary Hazard Occupancies as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) for Light or Ordinary Hazard Occupancies as Quick Response
Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) for Light Hazard Occupancies as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 112-04-E.
TABLE A
LABORATORY LISTINGS AND APPROVALS
5.6
1/2"
NPT
HORIZONTAL
SIDEWALL
(TY3321)
165°F/74°C Unpainted
212°F/100°C White
1, 2, 3, 4
K
Ordering
Procedure
When placing an order, indicate the full
product name. Refer to the Price List
for complete listing of Part Numbers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, 5.6 K-factor, (specify tem-
perature rating), Series TY-FRL Hori-
zontal Sidewall Sprinkler with (specify
type of finish), P/N (specify from Table
B).
Sprinkler Wrench:
Specify: W-Type 9 Sprinkler Wrench,
P/N 56-000-1-849.
Page4of4 TFP140
P/N 58 — XXX — X — XXX
165°F/74°C165
TEMPERATURE
RATING
1
SPRINKLER
TABLE B
PART NUMBER SELECTION
SERIES TY-FRL HORIZONTAL SIDEWALL SPRINKLERS
212°F/100°C212NATURAL BRASS
9
MODEL/SIN
CHROME PLATED
946 5.6K HSW (1/2"NPT) TY3321
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446

This manual suits for next models

1

Other Tyco Irrigation System manuals

Tyco LFII Series User manual

Tyco

Tyco LFII Series User manual

Tyco ESFR-22 User manual

Tyco

Tyco ESFR-22 User manual

Tyco RFII-C Series User manual

Tyco

Tyco RFII-C Series User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco TY7158 User manual

Tyco

Tyco TY7158 User manual

Tyco TFP PH2 Instruction Manual

Tyco

Tyco TFP PH2 Instruction Manual

Tyco DS-1 TY3255 Operating and maintenance instructions

Tyco

Tyco DS-1 TY3255 Operating and maintenance instructions

Tyco ESFR-22 User manual

Tyco

Tyco ESFR-22 User manual

Tyco EC-5 Series User manual

Tyco

Tyco EC-5 Series User manual

Tyco DV-5 User manual

Tyco

Tyco DV-5 User manual

Tyco Rapidresponse LFII Series Operating and maintenance instructions

Tyco

Tyco Rapidresponse LFII Series Operating and maintenance instructions

Tyco ESFR-17 User manual

Tyco

Tyco ESFR-17 User manual

Tyco ESFR-25 User manual

Tyco

Tyco ESFR-25 User manual

Tyco TFP485 User manual

Tyco

Tyco TFP485 User manual

Tyco AM11 User manual

Tyco

Tyco AM11 User manual

Tyco ESFR-25 User manual

Tyco

Tyco ESFR-25 User manual

Tyco EC-5 Series User manual

Tyco

Tyco EC-5 Series User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco Rapidresponse LFII Series User manual

Tyco

Tyco Rapidresponse LFII Series User manual

Tyco K17-231 User manual

Tyco

Tyco K17-231 User manual

Tyco Rapidresponse LFII Series User manual

Tyco

Tyco Rapidresponse LFII Series User manual

Tyco DS-3 Series Operating and maintenance instructions

Tyco

Tyco DS-3 Series Operating and maintenance instructions

Tyco 16.8 K-factor User manual

Tyco

Tyco 16.8 K-factor User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Popular Irrigation System manuals by other brands

Metabo Dry-running Sensor Hydrostop operating instructions

Metabo

Metabo Dry-running Sensor Hydrostop operating instructions

Reliable G5-80 manual

Reliable

Reliable G5-80 manual

Reliable KFR56 Series quick start guide

Reliable

Reliable KFR56 Series quick start guide

Komet Trigon 105 Technical manual

Komet

Komet Trigon 105 Technical manual

Sime SMART quick start guide

Sime

Sime SMART quick start guide

Reliable F1-28 Series quick start guide

Reliable

Reliable F1-28 Series quick start guide

Toro 570Z PRX Series Specifications

Toro

Toro 570Z PRX Series Specifications

Nelson Traveling Sprinkler Assembly and operating instructions

Nelson

Nelson Traveling Sprinkler Assembly and operating instructions

Viking MICROFAST VK311 Technical data

Viking

Viking MICROFAST VK311 Technical data

Viking VK800 Technical data

Viking

Viking VK800 Technical data

Hunter Institutional I-20 manual

Hunter

Hunter Institutional I-20 manual

GÜDE MP 120/5A/GJ manual

GÜDE

GÜDE MP 120/5A/GJ manual

Toro 53707 installation guide

Toro

Toro 53707 installation guide

Viking VK638-D Technical data

Viking

Viking VK638-D Technical data

claber POP-UP 90 user manual

claber

claber POP-UP 90 user manual

Johnson Controls Tyco EC-8 Series manual

Johnson Controls

Johnson Controls Tyco EC-8 Series manual

Motorola IRRInet-M DC owner's manual

Motorola

Motorola IRRInet-M DC owner's manual

Task Force Tips FM Series INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

Task Force Tips

Task Force Tips FM Series INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.