TFP510
Page 8 of 10
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section.)
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
DS-1 Dry-Type Sprinklers
When ordering TYCO Series DS-1
Note: If sprinkler removal becomes
necessary, remove the sprinkler using
the same wrenching method noted
above. Sprinkler removal is easier when
a non-hardening sealant was used
and torque guidelines were followed.
After removal, inspect the sprinkler for
damage.
Step 4. After installing the ceiling or
wall and applying a ceiling finish, slide
on the outer piece of the escutcheon
until it comes in contact with the ceiling
or wall. Do not lift the ceiling panel out
of its normal position.
When using the Deep Escutcheon,
hold the outer piece in contact with the
mounting surface (ceiling or wall). Then
rotate the inner piece approximately 1/4
turn with respect to the outer piece,
to hold the Deep Escutcheon firmly
together.
Care and
Maintenance
The TYCO Series DS-1 Dry-Type Sprin-
klers, 5.6K Pendent, Upright, and Hori-
zontal Sidewall, Quick Response (3 mm
bulb) and Standard Coverage must be
maintained and serviced in accordance
with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover a
clearance hole, can delay the time to
sprinkler operation in a fire situation.
A Vent Hole is provided in the Bulb
Seat (Ref. Figures 1 and 2) to indicate
if the Dry-Type Sprinkler is remaining
dry. Evidence of leakage from the Vent
Hole indicates potential leakage past
the Inlet seal and the need to remove
the sprinkler to determine the cause of
leakage (e.g., an improper installation
or an ice plug). Close the fire protec-
tion system control valve and drain the
system before removing the sprinkler.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
Dry-Type Sprinklers, 5.6K Pendent,
Upright, and Horizontal Sidewall,
Quick Response (3 mm bulb) and Stan-
dard Coverage, specify the following
information:
• SIN:
Pendent – TY3935 or TY3235
Sidewall – TY3735 or TY3335
Upright – TY3135
• 5.6 K-factor
• Deector Style:
Upright, Pendent, or Horizontal
Sidewall
•
Quick Response, Standard Cover-
age, Dry-Type Sprinkler
• Order Length:
Dry-Type Sprinklers are furnished
based upon Order Length as
measured per Figures 3 through
10. After taking the measurement,
round it to the nearest 1/4 inch
increment.
• Inlet Connections:
3/4 Inch NPT, 1 Inch NPT, or ISO
7-R 1
• Temperature Rating
• Sprinkler Finish
•
Escutcheon Style and Finish, as
applicable
• Part Number (P/N) from Table D
The Upright Sprinkler without an
Escutcheon (TY3135) is available in
1 Inch NPT only.
Part Numbers are for 3/4 inch and
1 inch NPT standard order sprin-
klers. Orders for all other sprinkler
assemblies must be accompanied
by a complete description. Refer to
the Price List for a complete listing
of Part Numbers.
Sprinkler Wrench
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
Sprinkler Boot
Specify: Model DSB-2 Dry Sprinkler
Boot, P/N 63-000-0-002
This Part Number includes one (1)
Boot, two (2) Strap Ties, and 1/3 oz.
of Adhesive (a sufficient quantity for
installing one boot).