manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco
  6. •
  7. Irrigation System
  8. •
  9. Tyco TFP PH5 Owner's manual

Tyco TFP PH5 Owner's manual

General
Description
The Model TFP PH5, 5.6 K-factor, In-
stitutional Horizontal Sidewall Sprin-
klers are standard response - standard
coverage, spray sprinklers designed
for use in areas such as correctional,
detention, and mental health care fa-
cilities.
The unique features of the Model TFP
PH5 provide a tamper resistant sprin-
kler design that helps eliminate the
opportunity for individuals to injure
themselves or others with components
of a fire sprinkler. At the same time, the
Model TFP PH5 optimizes an aes-
thetically appealing flush design that
conceals most of the operating parts.
WARNING
The Model TFP PH5 Institutional Hori-
zontal Sidewall Sprinklers described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the integrity of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or manufac-
turer should be contacted relative to
any questions.
Sprinkler
Identification
Number
SIN TY3390
Technical
Data
Approvals
UL and C-UL Listed for light and ordi-
nary hazard occupancies.(Refer to the
Design Criteria section.)
NYC under MEA 351-01-E.
Maximum Working Pressure
175 psi (12,1 bar)
Inlet Thread Connection
1/2 inch NPT
Discharge Coefficient
K=5.6GPM/psi
1/2
(80,6 LPM/bar1/2)
Temperature Ratings
135°F/57°C
Finishes
Sprinkler: Chrome Plated
Escutcheon: Chrome Plated
Physical Characteristics
Body.............. Brass
Deflector............Bronze
DeflectorHood ........Bronze
DeflectorPost.........Bronze
Deflector Post Pin . . . . . . Bronze
DeflectorCore ........Bronze
Compression Screw . . . . . Bronze
Lever . . . . . . . . . . . . . Bronze
ReleaseSpring ........Bronze
SealingAssembly...........
. . . . . . Beryllium Nickel w/ Teflon*
FusibleElement............
. Solder, Copper, and Stainless Steel
Dust Cover . . Chrome Plated Steel
Operation
In the standby condition, the design of
theModelTFPPH5issuchthata
suspended load of 80 lbs. (36 kg) or
more applied to the linkage mecha-
nism will release the sprinkler. Also,
when properly installed, the escutch-
eon is held fast to the wall to deter its
removal. The shape of the escutcheon
cannot be grasped easily, which fur-
ther deters tampering.
A fusible solder operating element se-
cures the linkage mechanism of the
Model TFP PH5. When the rated tem-
perature is reached, the solder melts
releasing the linkage mechanism that
holds the sprinkler closed. This allows
the deflector to extend outward and
water to flow.
Model TFP PH5 — 5.6 K-factor
Institutional Horizontal Sidewall Sprinklers
Standard Response, Standard Coverage
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Page 1 of 4 TFP654
FEBRUARY, 2002
Customer Service/Sales:
Tel: (215) 362-0700 / (800) 523-6512
Fax: (215) 362-5385
TFP654 (6-4.6)
OBSOLETE
Design
Criteria
The 5.6 K-factor, Model TFP PH5 (SIN
TY3390) Institutional Horizontal Side-
wall Sprinklers are intended for use in
fire protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on NFPA 13 require-
ments). The Model TFP PH5 (SIN
TY3390) must be installed with a de-
flector to ceiling distance of 4 to 12
inches (100 to 300 mm). To meet this
requirement, the centerline of the
sprinkler waterway must be located 4-
1/2 to 12-1/2 inches (114,3 to 317,5
mm) below the ceiling (Ref. Figure 2).
Only the Institutional Escutcheons
shown in Figure 3 can be utilized with
the Model TFP PH5.
NOTES
The Sprinkler Body must not extend
beyond the Institutional Escutcheon
(Ref. Figure 5). Otherwise the tamper
resistant design of the Model TFP PH5
will be compromised. Consequently,
Model 1752 Spacers, which are as-
sociated with other TFP institu-
tional sprinklers, cannot to be util-
ized.
Integrity of the tamper resistant design
of the Institutional Escutcheon is de-
pendent on the piping installation de-
sign. When installed properly, the In-
stitutional Escutcheon is held fast to
the mounting surface by the tightening
of the sprinkler assembly into the
sprinkler fitting. In order to accomplish
a proper installation, the sprinkler fit-
ting must be properly located with re-
spect to distance from the face of the
sprinkler fitting to the face of the
mounting surface (Ref. Figure 3); the
sprinkler fitting being rigidly secured
and held immobile; and, the centerline
of the sprinkler fitting being perpen-
dicular to the mounting surface to as-
sure that the escutcheon sits squarely
against the mounting surface around
the entire perimeter of the Institutional
Escutcheon. Figure 2 illustrates a typi-
cal installation that can be utilized to
help adjust the location of the sprinkler
fitting; to help assure immobility of the
sprinkler fitting; and, to help maintain
perpendicularity of the sprinkler fitting
to the mounting surface.
Installation
The 5.6 K-factor, Model TFP PH5
Sprinklers must be installed in accord-
ance with the following instructions:
NOTES
Refer to the Design Criteria section for
important information regarding the
piping installation design and its effect
on maintaining the integrity of the tam-
per resistant design of the Institutional
Escutcheons.
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft.lbs. (28,5 Nm) of torque
is to be used to install these sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
Page2of4 TFP654
FIGURE 1
MODEL TFP PH5 INSTITUTIONAL
HORIZONTAL SIDEWALL SPRINKLER
Components:
1 - Body
2 - Deflector Hood
3 - Deflector
4 - Deflector Post
(2 req’d)
5- DeflectorPostPin
(2 req’d)
6 - Deflector Core
7 - Compression Screw
8 - Lever
9- ReleaseSpring
10 -Sealing Assembly
11 - Fusible Element
12 - Dust Cover
NPT
1/2"
CENTERLINE
WATERWAY
OF SPRINKLER
1/2"
(12.7 mm)
ASSEMBLY
DEFLECTOR
IN OPERATED
POSITION
WRENCHING
NOTCH (2)
SPRINKLER
LINKAGE
MECHANISM
WITH DEFLECTOR
INSTALL
SPRINKLER
HOOD ORIENTED AT
TOP AS SHOWN
SPRINKLER
FITTING
FACE OF
NOMINAL MAKE-IN
7/16" (11.1 mm)
INSTALLED
SIDE VIEW
SIDE VIEW
OPERATED
12
8
145
10
11
9
2
376
FRONT VIEW
INSTALLED
2.81"
(71.4 mm)
(80.8 mm)
3.18"
VIEW
CROSS-SECTION
* Registered Trademark of DuPont
OBSOLETE
age or impairment of the sprinkler.
Do not attempt to compensate for im-
proper location of the sprinkler fitting
by under- or over-tightening the sprin-
kler. Readjust the position of the sprin-
kler fitting to suit, or increase or de-
crease the number of Model 1752
Spacers, as applicable.
After the installation is complete, make
certain that the Institutional Escutch-
eon is held fast to the mounting sur-
face and that it sits squarely against
the ceiling around its entire perimeter.
Step 1. The TFP PH5 Sprinklers must
be installed horizontally with the cen-
terline of their waterway perpendicular
to the back wall surface, and the De-
flector must be located with the top
towards the ceiling (Ref. Figure 1).
Step 2. With the Institutional Escutch-
eon in place and with pipe thread
sealant applied to the pipe threads,
hand tighten the sprinkler into the
sprinkler fitting.
Step 3. Wrench tighten the Sprinkler
using only the Model 1509-3 Sprin-
kler Wrench (Ref. Fig. 5). The wrench-
ing teeth of the Sprinkler Wrench are
to be applied to the sprinkler wrench-
ing notch areas (Ref. Fig. 1).
Step 4. After the installation is com-
plete, make certain that the Institu-
tional Escutcheon is held fast to the
mounting surface and that it sits
squarely against the wall around its
entire perimeter.
NOTE
The Sprinkler Body must not extend
beyond the Institutional Escutcheon
(Ref. Fig. 4). Otherwise the tamper
resistant design of the Model TFP PH5
will be compromised.
Care and
Maintenance
The 5.6 K-factor, Model TFP PH5
Sprinklers must be maintained and
serviced in accordance with the follow-
ing instructions:
NOTES
Service inspections should be made
on a regular basis to detect possible
damage or alterations to the sprinkler
and escutcheon. Inspections should
include making certain that the Institu-
tional Escutcheon is held fast to the
mounting surface. Damaged or altered
sprinklers are to be replaced immedi-
ately to avoid personal injury and to
prevent use for causing personal in-
jury, as well as to maintain the sprin-
kler system in an operative condition.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection systems must
be obtained from the proper authori-
ties and all personnel who may be
affected by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
shipped or stored where their tempera-
tures will exceed 100°F/38°C and they
must never be painted, plated, coated,
or otherwise altered after leaving the
factory. Modified or over-heated sprin-
klers must be replaced.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
TFP654 Page 3 of 4
FIGURE 3
INSTITUTIONAL ESCUTCHEON OPTIONS
FOR USE WITH THE MODEL TFP PH5
NOTE: Model 1752 Spacers are not to be used to obtain horizontal adjustment for the
Model TFP PH5 with Style B2 or C Escutcheons.
CLEARANCE FOR
DETERMINED BY
DIAMETER
REDUCING
COUPLING
CLEARANCE FOR
DETERMINED BY
MOUNTING SURFACE
FITTING FLUSH WITH
FACE OF SPRINKLER
DIAMETER
REDUCING
COUPLING
(71.4 mm)
4-1/4" DIA.
(108.0 mm)
2.81"
(65.1 mm)
2-9/16"
1-3/16"
(30.2 mm)
5" DIA.
(127.0 mm)
(37.6 mm)
(33.8 mm)
1.33" 1.48"
STYLE B2
STYLE C
OBSOLETE
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or compo-
nents manufactured by companies not
affiliated by ownership with Tyco Fire
Products or for products and compo-
nents which have been subject to mis-
use, improper installation, corrosion,
or which have not been installed, main-
tained, modified or repaired in accord-
ance with applicable Standards of the
National Fire Protection Association,
and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products’ sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES,ANDINNOEVENT
SHALL TYCO FIRE PRODUCTS’ LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
Ordering
Procedure
Contact your local distributor for avail-
ability.
Sprinkler Assemblies:
Specify: 5.6 K-factor, Chrome Plated,
135°F/57°C, Model TFP PH5
(TY3390) Institutional Horizontal Side-
wall Sprinkler, P/N 51-106-9-135.
Separately Ordered Escutcheons:
Specify: Style (B2 or C), Chrome
Plated, Institutional Escutcheons.
Style B2 . . . . . . . . . . . . . . . . . . P/N 56-001-7-512
Style C . . . . . . . . . . . . . . . . . . . P/N 56-001-7-513
Separately Ordered Wrenches:
Specify: Model 1509-3 Sprinkler
Wrench, P/N 56-001-5-093.
Separately Ordered Parts For
Installation In Concrete Walls:
Specify: Model 1781 Centering Grom-
met for installation in concrete,
P/N 56-000-1-781.
Specify: Model 1780 Retaining Flange
with Set Screws for installation in con-
crete, P/N 56-000-1-780.
FIGURE 4
PROPER POSITIONING OF
ESCUTCHEON
FIGURE 3
TYPICAL INSTALLATION WHEN USING 1780 RETAINING FLANGE
AND MODEL 1781 CENTERING GROMMET
Page4of4 TFP654
FIGURE 5
MODEL 1509-3
SPRINKLER WRENCH
1
/
2" DRIVE
ACCEPTS
TEETH
WREN
C
HIN
G
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
OBSOLETE

Other Tyco Irrigation System manuals

Tyco G5 Sprinkler Guard User manual

Tyco

Tyco G5 Sprinkler Guard User manual

Tyco DS-1 Series User manual

Tyco

Tyco DS-1 Series User manual

Tyco CC2 User manual

Tyco

Tyco CC2 User manual

Tyco LFII Series User manual

Tyco

Tyco LFII Series User manual

Tyco BB User manual

Tyco

Tyco BB User manual

Tyco ESFR-17 User manual

Tyco

Tyco ESFR-17 User manual

Tyco Gem PSN 56-701-9-010 User manual

Tyco

Tyco Gem PSN 56-701-9-010 User manual

Tyco TY-L Series User manual

Tyco

Tyco TY-L Series User manual

Tyco Ultra K17 User manual

Tyco

Tyco Ultra K17 User manual

Tyco ESFR-22 User manual

Tyco

Tyco ESFR-22 User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco ESFR-17 User manual

Tyco

Tyco ESFR-17 User manual

Tyco ELO-231B Series User manual

Tyco

Tyco ELO-231B Series User manual

Tyco 3002B User manual

Tyco

Tyco 3002B User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco RFII Series User manual

Tyco

Tyco RFII Series User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco LFII Series User manual

Tyco

Tyco LFII Series User manual

Tyco TY-FRL-5.6 Series User manual

Tyco

Tyco TY-FRL-5.6 Series User manual

Tyco RAPID RESPONSE Series User manual

Tyco

Tyco RAPID RESPONSE Series User manual

Tyco LFII Series Instruction Manual

Tyco

Tyco LFII Series Instruction Manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco CC3 User manual

Tyco

Tyco CC3 User manual

Tyco FASTFLEX YN25 User manual

Tyco

Tyco FASTFLEX YN25 User manual

Popular Irrigation System manuals by other brands

Autopot 36Pot system Set-up guidelines

Autopot

Autopot 36Pot system Set-up guidelines

Eden 94122-EDAMZ quick start guide

Eden

Eden 94122-EDAMZ quick start guide

Eden 94094EDAMZ manual

Eden

Eden 94094EDAMZ manual

Reliable DH80 Dry manual

Reliable

Reliable DH80 Dry manual

Reliable J168 instructions

Reliable

Reliable J168 instructions

Viking Micromatic VK100 Technical data

Viking

Viking Micromatic VK100 Technical data

Elgo READY 2 DRIP installation guide

Elgo

Elgo READY 2 DRIP installation guide

Hunter SRC Plus 600i owner's manual

Hunter

Hunter SRC Plus 600i owner's manual

hillvert HT-COSTIGAN-3600 user manual

hillvert

hillvert HT-COSTIGAN-3600 user manual

Autopot Easy2grow 40 Set-up guidelines

Autopot

Autopot Easy2grow 40 Set-up guidelines

Cellfast LUX IDEAL 52-160 user manual

Cellfast

Cellfast LUX IDEAL 52-160 user manual

Tyco Fire Product Gem A instruction manual

Tyco Fire Product

Tyco Fire Product Gem A instruction manual

Reliable G6-80 K8.0 quick start guide

Reliable

Reliable G6-80 K8.0 quick start guide

Viking VK1001 SR Upright Sprinkler K5.6 Technical data sheet

Viking

Viking VK1001 SR Upright Sprinkler K5.6 Technical data sheet

Munters Green Field DC user manual

Munters

Munters Green Field DC user manual

Netafim nmc-pro installation manual

Netafim

Netafim nmc-pro installation manual

Toro TMC-424 Series brochure

Toro

Toro TMC-424 Series brochure

viRaTec Miyo SMART GARDEN technical information

viRaTec

viRaTec Miyo SMART GARDEN technical information

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.