Replace sprinklers that:
•were damaged by dropping, striking,
wrench twisting, wrench slippage, or
the like.
•were modied or over-heated.
•are leaking or exhibiting visible signs
of corrosion.
Frequent visual inspections are recom-
mended to be initially performed for
sprinklers installed in potentially cor-
rosive atmospheres to verify the integ-
rity of the materials of construction as
they may be affected by the corrosive
conditions present for a given installa-
tion. Thereafter, annual inspections per
NFPA 25 are required.
Owners are responsible for the inspec-
tion, testing, and maintenance of their
re protection system and devices in
compliance with this document, as well
as with the applicable standards of the
National Fire Protection Association
(for example, NFPA 25), in addition to
the standards of any other Authorities
Having Jurisdiction. Contact the install-
ing contractor or sprinkler manufacturer
regarding any questions.
Sprinklers are recommended to be in-
spected, tested, and maintained by a
qualied Inspection Service in accor-
dance with local requirements and/or
national codes.
Disclaimer for
RAVEN
Institutional
Sprinklers
Tyco Fire Protection Products speci-
cally disclaims any liability for damages
or injury (including death) arising out of
or caused by manipulation, disman-
tling, or misuse of RAVEN Institutional
Sprinklers or the use or attempted use
of the RAVEN Institutional Sprinklers or
any component thereof as an instru-
ment unrelated to its intended function
as a re protection device.
Limited
Warranty
Products manufactured by Tyco Fire
Protection Products (TFPP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in ma-
terial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years from
date of shipment by TFPP. No warran-
ty is given for products or components
manufactured by companies not af-
liated by ownership with TFPP or for
products and components which have
been subject to misuse, improper in-
stallation, corrosion, or which have not
been installed, maintained, modied
or repaired in accordance with appli-
cable Standards of the National Fire
Protection Association, and/or the stan-
dards of any other Authorities Having
Jurisdiction. Materials found by TFPP to
be defective shall be either repaired or
replaced, at TFPP’s sole option. TFPP
neither assumes, nor authorizes any
person to assume for it, any other ob-
ligation in connection with the sale of
products or parts of products. TFPP
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.
In no event shall TFPP be liable, in con-
tract, tort, strict liability or under any
other legal theory, for incidental, indi-
rect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFPP
was informed about the possibility of
such damages, and in no event shall
TFPP’s liability exceed an amount equal
to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, express
or implied, including warranties of mer-
chantability and tness for a particular
purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on fail-
ure of or defect in products, materials
or components, whether the claim is
made in contract, tort, strict liability or
any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product description and Part
Number (P/N).
Sprinkler Assemblies
Specify: RAVEN (standard or extend-
ed coverage), 165°F (74°C), Institutional
(pendent or horizontal sidewall)
Sprinkler with (nish) and P/N (below).
Standard Coverage Pendent (TY3281)
Chrome .................. P/N 50-314-9-165
White Color ............... P/N 50-314-4-165
Standard Coverage HSW (TY3381)
Chrome .................. P/N 50-316-9-165
White Color ............... P/N 50-316-4-165
Extended Coverage Pendent (TY3282)
Chrome .................. P/N 50 -315 -9-165
White Color ............... P/N 50-315-4-165
Extended Coverage HSW (TY3382)
Chrome ...................P/N 50-317-9 -165
White Color ................P/N 50-317-4-165
Separately Ordered
Escutcheons Style F
(3” Diameter)
Chrome .................. P/N 56-314-9-010
White Color ............... P/N 56-314-4-010
Separately Ordered
Escutcheons Style G
(4” Diameter)
Chrome .................. P/N 56-312-9-010
White Color ............... P/N 56-312-4-010
Separately Ordered
Sprinkler Wrench
Specify W-Type 25 Installation Wrench,
P/N 56-314-1-001.
Separately Ordered
Adjustment Spacer Ring
Specify Adjustment Spacer Ring for
use with RAVEN Institutional Sprinklers,
P/N 56-000-1-755.
Separately Ordered
Parts for Installation in Concrete
Specify Model 1781 Centering
Grommet for installation in concrete,
P/N 56-000-1-781.
Specify Model 1780 Retaining Flange
with Set Screws for installation in con-
crete, P/N 56-000-1-780.
Copyright © 2009, 2012 Tyco Fire Protection Products. All rights reserved.
TEFLON is trademark of The DuPont Corporation.
TFP651
Page 10 of 10