Tyco RFII Series User manual

Series RFII — 5.6 K-factor
“Royal Flush II” Pendent Concealed Sprinklers
Quick & Standard Response, Standard Coverage
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Page 1 of 4 MAY, 2008 TFP181
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
General
Description
The Tyco®Series RFII Quick Response
(3 mm bulb) & Standard Response (5
mm bulb), 5.6 K-Factor, “Royal Flush
II” Concealed Pendent Sprinklers are
decorative sprinklers featuring a flat
cover plate designed to conceal the
sprinkler. It is the best choice for archi-
tecturally sensitive areas such as ho-
tel lobbies, office buildings, churches,
and restaurants.
Each unit includes a Cover Plate As-
sembly that conceals the sprinkler op-
erating components above the ceiling.
The separable two-piece design of the
Cover Plate and Support Cup Assem-
blies allows installation of the sprin-
klers and pressure testing of the fire
protection system prior to installation
of a suspended ceiling or application
of the finish coating to a fixed ceiling.
They also permit removal of suspend-
ed ceiling panels for access to building
service equipment without having to
first shut down the fire protection sys-
tem and remove sprinklers.
Also, the separable two-piece design
of the Sprinkler provides for 1/2 inch
(12,7 mm) of vertical adjustment, to
provide a measure of flexibility with re-
gard to which the length of fixed pipe
drops to the sprinklers must be cut.
The Series RFII Sprinklers are shipped
with a Disposable Protective Cap. The
Protective Cap is temporarily removed
for installation, and then it can be re-
placed to help protect the sprinkler
while the ceiling is being installed or
finished. The tip of the Protective Cap
can also be used to mark the center
of the ceiling hole into plaster board,
ceiling tiles, etc. by gently pushing the
ceiling product against the Protec-
tive Cap. When the ceiling installation
is complete the Protective Cap is re-
moved and the Cover Plate Assembly
installed.
As an option, the Series RFII Standard
Response (5 mm bulb) “Royal Flush II”
Concealed Pendent Sprinklers may be
fitted with a silicone Air and Dust Seal
(Ref. Fig. 5). The Air and Dust Seal is
intended for sensitive areas where it
is desirable to stop air and dust travel
through the cover plate from the area
above the ceiling.
NOTIce
The Series RFII Concealed Pendent
Sprinklers described herein must be
installed and maintained in compliance
with this document and with the appli-
cable standards of the National Fire
Protection Association, in addition to
the standards of any authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Number
TY3551 (5 mm bulb)
TY3531 (3 mm bulb)
Technical
Data
Approvals:
UL and C-UL Listed. FM Approved
NYC under MEA 353-01-E. LPCB
(Ref. No. 094a/09 for TY3551 &
094a/10 for TY3531)
The approvals apply only to the ser-
vice conditions indicated in the De-
sign Criteria section.
Approvals for Air & Dust Seal:
(Part # 10908100)
UL and C-UL Listed for use with the
RFII (TY3551); Standard Response
Concealed Sprinkler.
Maximum Working Pressure:
Maximum 250 psi (17,3 bar) by UL,
C-UL, and NYC. Maximum 175 psi
(12,1 bar) by FM and LPCB.
Temperature Rating:
155°F/68°C - Sprinkler
139°F/59°C - Plate
200°F/93°C - Sprinkler
165°F/74°C - Plate
Discharge Coefficient:
K= 5.6 GPM/psi1/2 (80,6 LPM/bar1/2)
Adjustment:
1/2 inch (12,7 mm)
Finishes:
Refer to Ordering Procedure section.
Page 2 of 4 TFP181
Physical Characteristics:
Frame................... Bronze
Support Cup. . . Chrome Plated Steel
Guide Pins . . . . . . . . . Stainless Steel
Deflector................. Bronze
Compression Screw. . . . . . . . . Brass
Blub ......................Glass
Cap. . . . . . . . . . . . . Bronze or Copper
Sealing Assembly. . . . . . . . . . . . . . . .
. . . . . . . . .Beryllium Nickel w/ Teflon†
Cover Plate . . . . . . . . . . . . . . . . Brass
Retainer .................. Brass
Ejection Spring. . . . . . Stainless Steel
†DuPont Registered Trademark
Patents:
U.S.A. Patent No. 4,014,388
Operation
When exposed to heat from a fire, the
Cover Plate, normally soldered to the
Retainer at three points, falls away
to expose the Sprinkler Assembly.
At this point the Deflector supported
by the Guide Pins drops down to its
operational position.
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
FIGURe 1
MODeL RFII cONceALeD SPRINKLeR
ASSeMBLY
glass Bulb, activating the sprinkler and
allowing water to flow.
Design
Criteria
The RFII (TY3551), 5 mm Bulb Type,
Concealed Pendent Sprinklers are UL
and C-UL Listed as standard response
-standard spray sprinklers for use in
accordance with the current NFPA
standard. They are FM Approved as
standard response -standard spray
sprinklers for use in accordance with
the current FM Loss Prevention Data
Sheets.
The RFII (TY3531) 3 mm Bulb Type,
Concealed Pendent Sprinklers are UL
and C-UL Listed as quick response
standard spray sprinklers for use in
accordance with the current NFPA
standard. They are FM Approved as
standard response -standard spray
sprinklers for use in accordance with
the current FM Loss Prevention Data
Sheets.
The Series RFII Concealed Pendent
Sprinklers are only listed and approved
with the Series RFII Concealed Cover
Plates having a factory applied finish.
The Series RFII must not be used in
applications where the air pressure
above the ceiling is greater than
that below. Down drafts through the
Support Cup could delay sprinkler
operation in a fire situation.
Installation
The Tyco®Series RFII must be in-
stalled in accordance with the follow-
ing instructions:
NOTIce
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bub-
ble should be present. The diameter
of the air bubble is approximately 1/16
inch (1,6 mm) for the 155°F/68°C and
3/32 inch (2,4 mm) for the 200°F/93°C
temperature ratings.
A 1/2 inch NPT sprinkler joint should
be obtained with a minimum to max-
imum torque of 7 to 14 ft.lbs. (9,5 to
19,0 Nm). Higher levels of torque may
distort the sprinkler inlet with conse-
quent leakage or impairment of the
sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in the Sprinkler
Assembly by under-or over-tightening
the Sprinkler/Support Cup Assembly.
Readjust the position of the sprinkler
fitting to suit.
Step 1. The sprinkler must only be in-
stalled in the pendent position and
with the centerline of the sprinkler per-
pendicular to the mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant ap
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 4. Wrench tighten the sprinkler
using only the RFII Sprinkler Wrench
(Ref. Figure 3). The RFII Sprinkler
Wrench is to be applied to the Sprin-
kler as shown in Figure 3.
Step 5. Replace the Protective Cap
(Ref. Figure 4) by pushing it upwards
until it bottoms out against the Sup-
port Cup. The Protective Cap helps
prevent damage to the Deflector and
Arms during ceiling installation and/or
during application of the finish coating
of the ceiling. It may also be used to
locate the center of the clearance hole
by gently pushing the ceiling material
up against the center point of the Pro-
tective Cap.
NOTIce
As long as the Protective Cap remains
in place, the system is considered to
be “Out of Service”.
SPRINKLER/SUPPORT CUP
ASSEMBLY
COVER PLATE/RETAINER
ASSEMBLY
GUIDE
DEFLECTOR
(DROPPED
POSITION)
PINS (2)
SCREW
COMPRESSION
DEFLECTOR
ROLL FORMED
THREADS
CUP WITH
SUPPORT
FRAME
1/2" NPT
CAP
BULB
SEALING
ASSEMBLY
RETAINER
WITH THREAD
DIMPLES
SPRING
EJECTION
TABS (3)
SOLDER COVER
PLATE
THREAD INTO
UNTIL MOUNTING
SUPPORT CUP
SURFACE IS
FLUSH WITH
CEILING
TFP181 Page 3 of 4
Step 6. After the ceiling has been
completed with the 2-1/2 inch (63,5
mm) diameter clearance hole and in
preparation for installing the Cover
Plate Assembly, remove and discard
the Protective Cap, and verify that the
Deflector moves up and down freely. If
the Sprinkler has been damaged and
the Deflector does not move up and
down freely, replace the entire Sprin-
kler assembly. Do not attempt to mod-
ify or repair a damaged sprinkler.
Step 7. When installing an Air and
Dust Seal, refer to Figure 5, otherwise
proceed to Step 8. To attach the Air
and Dust Seal, verify the angle of the
outside edge of the seal is oriented ac-
cording to Figure 5. Start the edge of
the Retainer in the grooved slot of the
Air and Dust Seal and continue around
the retainer until the entire Air and Dust
Seal is engaged.
Step 8. Screw on the Cover Plate/Re-
tainer Assembly until the Retainer Fig-
ure 2 (or Air and Dust Seal -Figure 5)
contacts with the ceiling. Do not con-
tinue to screw on the Cover Plate/Re-
tainer Assembly such that it lifts a ceil-
ing panel out of its normal position. If
the Cover Plate/Retainer Assembly
cannot be engaged with the Support
Cup or the Cover Plate/Retainer As-
sembly cannot be engaged sufficiently
to contact the ceiling, the Sprinkler Fit-
ting must be repositioned.
Care and
Maintenance
The Tyco®Series RFII must be
maintained and serviced in accordance
with the following instructions:
NOTIce
Absence of the Cover Plate Assembly
may delay sprinkler operation in a fire
situation.
When properly installed, there is a nom-
inal 3/32 inch (2,4 mm) air gap between
the lip of the Cover Plate and the ceiling,
FIGURe 4
DISPOSABLe PROTecTIve cAP
CLEARANCE
HOLE
COVER PLATE
PROFILE DEPTH
DIMENSION B
1/2" (12,7 mm)
THREADED
ADJUSTMENT
D
SPRINKLER
FACE OF
FITTING
RETAINER
ASSEMBLY
MANUFACTURER
3/32" (2,4 mm)
PRESET GAP
FACE OF CEILING,
RETAINING RING
MOUNTING
SURFACE
SUPPORT CUP
SPRINKLER
ASSEMBLY
DIAMETER
CLEARANCE HOLE
DEFLECTOR
IN DROPPED
POSITION
(4,8 to 17,5 mm)
3/16" to 11/16"
REFERENCE
COVER PLATE
COVER PLATE
DIAMETER
DIMENSION A
DIMENSION C
A: 3-1/4 inches (82,6 mm) C: 2-3/8 to 2-5/8 inches (60,3 to 66,7 mm)
B: 3/16 inches (4,8 mm) D: 1-3/4 to 2-1/4 inches (44,5 to 57,2 mm)
FRAME
ARM
SUPPORT
CUP
7/8" (23 mm)
SQUARE
1/2" SOCKET
ACCEPTS
DRIVE
ARROWS WITH
ALIGN
FRAME ARMS
FIGURe 2
SeRIeS cONceALeD SPRINKLeR INSTALLATION DIMeNSIONS
FIGURe 3
RFII SPRINKLeR wReNch
Page 4 of 4 TFP181
© 2008 TYCO FIRE & BUILDING PRODUCTS
, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
as shown in Figure 2. This air gap is
necessary for proper operation of the
sprinkler. If the ceiling is to be repaint-
ed after the installation of the Sprinkler,
care must be exercised to ensure that
the new paint does NOT seal off any of
the air gap.
Factory painted Cover Plates MUST
NOT be repainted. They should be re-
placed, if necessary, by factory painted
units. Non-factory applied paint may
adversely delay or prevent sprinkler
operation in the event of a fire.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Before closing a fire protection sys-
tem main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied or over heated sprinklers must be
replaced.
Care must be exercised to avoid dam-
age to the sprinklers -before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
If a sprinkler must be removed, do not
reinstall it or a replacement without
reinstalling the Cover Plate Assembly.
If a Cover Plate Assembly becomes
dislodged during service, replace it
immediately.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and devic-
es in compliance with this document,
as well as with the applicable stan-
dards of the National Fire Protection
Association (e.g., NFPA 25), in addition
to the standards of any other authori-
ties having jurisdiction. The installing
contractor or sprinkler manufacturer
should be contacted relative to any
questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualified Inspection Service in accor-
dance with local requirements and/or
national code.
Limited
Warranty
Products manufactured by Tyco Fire
& Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years from
date of shipment by TFBP. No warran-
ty is given for products or components
manufactured by companies not af-
filiated by ownership with TFBP or for
products and components which have
been subject to misuse, improper in-
stallation, corrosion, or which have not
been installed, maintained, modified or
repaired in accordance with applicable
Standards of the National Fire Protec-
tion Association, and/or the standards
of any other Authorities Having Juris-
diction. Materials found by TFBP to be
defective shall be either repaired or re-
placed, at TFBP’s sole option. TFBP
neither assumes, nor authorizes any
person to assume for it, any other ob-
ligation in connection with the sale of
products or parts of products. TFBP
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP’s liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, ex-
press or implied, including warranties
of merchantability and fitness for a
particular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Contact your local
distributor for availability.
Sprinkler Assembly
Specify: (SIN), (specify temperature
rating) Series RFII Concealed Pendent
Sprinkler, P/N (specify).
155°F/68°C 200°F/93°C
TY3551 51-790-1-155 51-790-1-200
TY3531 51-792-1-155 51-792-1-200
Separately Ordered Cover Plate:
Specify: (specify temperature rating)
Series RFII Concealed Cover Plate
with (specify finish), P/N (specify).
139°F/59°C(a) 165°F/74°C(b)
Brass . . . . . . . . . . 56-792-1-135 56-792-1-165
Chrome . . . . . . . . 56-792-9-135 56-792-9-165
Signal White (c)
(RAL 9003). . . . 56-792-4-135 56-792-4-165
Grey White (d)
(RAL 9002). . . . 56-792-0-135 56-792-0-165
Pure White (e)
(RAL 9010). . . . 56-792-3-135 56-792-3-165
Custom . . . . . . . . 56-792-X-135 56-792-X-165
(a) For use with 155°F/68°C sprinklers.
(b) For use with 200°F/93°C sprinklers.
(c) Previously known as Bright White.
(d) Previously known as Standard White.
(e) Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: RFII Sprinkler Wrench,
P/N 56-000-1-075.
Air and Dust Seal:
Specify: Air and Dust Seal,
P/N 56-908-1-001.
FIGURe 5
OPTIONAL AIR AND DUST SeAL FOR SeRIeS RFII (TY3551)
CUP
SUPPORT
ROOM
SEAL
PLATE
RETAINER
SPRINKLER
CLEAN
PLATE
COVER
RETAINER
LIP OF
FACE OF
CEILING
BEVEL AS
ORIENT
SEAL
ASSEMBLY
COVER SHOWN

This manual suits for next models

2

Other Tyco Irrigation System manuals

Tyco TY7158 User manual

Tyco

Tyco TY7158 User manual

Tyco ESFR-25 User manual

Tyco

Tyco ESFR-25 User manual

Tyco LFII Series User manual

Tyco

Tyco LFII Series User manual

Tyco CC1 User manual

Tyco

Tyco CC1 User manual

Tyco RFIII User manual

Tyco

Tyco RFIII User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco Rapidresponse LFII Series User manual

Tyco

Tyco Rapidresponse LFII Series User manual

Tyco RFII Series User manual

Tyco

Tyco RFII Series User manual

Tyco EC-5 Series User manual

Tyco

Tyco EC-5 Series User manual

Tyco LFII Series User manual

Tyco

Tyco LFII Series User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco SW-20 User manual

Tyco

Tyco SW-20 User manual

Tyco FASTFLEX YN25 User manual

Tyco

Tyco FASTFLEX YN25 User manual

Tyco Power Pro Series User manual

Tyco

Tyco Power Pro Series User manual

Tyco TFP PH2 Instruction Manual

Tyco

Tyco TFP PH2 Instruction Manual

Tyco SW-20 User manual

Tyco

Tyco SW-20 User manual

Tyco ESFR-1 Operating and maintenance instructions

Tyco

Tyco ESFR-1 Operating and maintenance instructions

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco TY-FRB Series Instruction Manual

Tyco

Tyco TY-FRB Series Instruction Manual

Tyco DS-1 Series User manual

Tyco

Tyco DS-1 Series User manual

Tyco ESFR-17 User manual

Tyco

Tyco ESFR-17 User manual

Tyco ELOC User manual

Tyco

Tyco ELOC User manual

Tyco TY-L Series User manual

Tyco

Tyco TY-L Series User manual

Tyco TY1136 User manual

Tyco

Tyco TY1136 User manual

Popular Irrigation System manuals by other brands

Reliable F1FR56 Bulletin

Reliable

Reliable F1FR56 Bulletin

EIJKELKAMP 09.06 operating instructions

EIJKELKAMP

EIJKELKAMP 09.06 operating instructions

Kärcher HKF 50 E manual

Kärcher

Kärcher HKF 50 E manual

Hunter Institutional Series quick start guide

Hunter

Hunter Institutional Series quick start guide

Sime GEMINI Installation, use and maintenance

Sime

Sime GEMINI Installation, use and maintenance

IrriGreen Irrigreen2 Guide

IrriGreen

IrriGreen Irrigreen2 Guide

Tyco Fire Product TY-B Series instruction manual

Tyco Fire Product

Tyco Fire Product TY-B Series instruction manual

claber AQUAUNO MIST user manual

claber

claber AQUAUNO MIST user manual

W&H OsseoSet 200 Instructions for use

W&H

W&H OsseoSet 200 Instructions for use

Viking MicrofastHP VK316 Technical data

Viking

Viking MicrofastHP VK316 Technical data

Chapin 4701 Assembly / operation instructions / parts

Chapin

Chapin 4701 Assembly / operation instructions / parts

Toro OSMAC E-SERIES Specifications

Toro

Toro OSMAC E-SERIES Specifications

Reliable F1FR80 Series manual

Reliable

Reliable F1FR80 Series manual

Hunter Institutional I-40 quick start guide

Hunter

Hunter Institutional I-40 quick start guide

ATIKA VT 36 manual

ATIKA

ATIKA VT 36 manual

Lux Tools A-EWSU-C Original instructions

Lux Tools

Lux Tools A-EWSU-C Original instructions

Tyco Fire Product STAR SIN S3400 SR manual

Tyco Fire Product

Tyco Fire Product STAR SIN S3400 SR manual

Tyco Fire Product Star Celeste S140 instruction manual

Tyco Fire Product

Tyco Fire Product Star Celeste S140 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.