as shown in Figure 2. This air gap is
necessary for proper operation of the
sprinkler. If the ceiling is to be repaint-
ed after the installation of the Sprinkler,
care must be exercised to ensure that
the new paint does NOT seal off any of
the air gap.
Factory painted Cover Plates MUST
NOT be repainted. They should be re-
placed, if necessary, by factory painted
units. Non-factory applied paint may
adversely delay or prevent sprinkler
operation in the event of a fire.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Before closing a fire protection sys-
tem main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied or over heated sprinklers must be
replaced.
Care must be exercised to avoid dam-
age to the sprinklers -before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
If a sprinkler must be removed, do not
reinstall it or a replacement without
reinstalling the Cover Plate Assembly.
If a Cover Plate Assembly becomes
dislodged during service, replace it
immediately.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and devic-
es in compliance with this document,
as well as with the applicable stan-
dards of the National Fire Protection
Association (e.g., NFPA 25), in addition
to the standards of any other authori-
ties having jurisdiction. The installing
contractor or sprinkler manufacturer
should be contacted relative to any
questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualified Inspection Service in accor-
dance with local requirements and/or
national code.
Limited
Warranty
Products manufactured by Tyco Fire
& Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years from
date of shipment by TFBP. No warran-
ty is given for products or components
manufactured by companies not af-
filiated by ownership with TFBP or for
products and components which have
been subject to misuse, improper in-
stallation, corrosion, or which have not
been installed, maintained, modified or
repaired in accordance with applicable
Standards of the National Fire Protec-
tion Association, and/or the standards
of any other Authorities Having Juris-
diction. Materials found by TFBP to be
defective shall be either repaired or re-
placed, at TFBP’s sole option. TFBP
neither assumes, nor authorizes any
person to assume for it, any other ob-
ligation in connection with the sale of
products or parts of products. TFBP
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP’s liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, ex-
press or implied, including warranties
of merchantability and fitness for a
particular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Contact your local
distributor for availability.
Sprinkler Assembly
Specify: (SIN), (specify temperature
rating) Series RFII Concealed Pendent
Sprinkler, P/N (specify).
155°F/68°C 200°F/93°C
TY3551 51-790-1-155 51-790-1-200
TY3531 51-792-1-155 51-792-1-200
Separately Ordered Cover Plate:
Specify: (specify temperature rating)
Series RFII Concealed Cover Plate
with (specify finish), P/N (specify).
139°F/59°C(a) 165°F/74°C(b)
Brass . . . . . . . . . . 56-792-1-135 56-792-1-165
Chrome . . . . . . . . 56-792-9-135 56-792-9-165
Signal White (c)
(RAL 9003). . . . 56-792-4-135 56-792-4-165
Grey White (d)
(RAL 9002). . . . 56-792-0-135 56-792-0-165
Pure White (e)
(RAL 9010). . . . 56-792-3-135 56-792-3-165
Custom . . . . . . . . 56-792-X-135 56-792-X-165
(a) For use with 155°F/68°C sprinklers.
(b) For use with 200°F/93°C sprinklers.
(c) Previously known as Bright White.
(d) Previously known as Standard White.
(e) Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: RFII Sprinkler Wrench,
P/N 56-000-1-075.
Air and Dust Seal:
Specify: Air and Dust Seal,
P/N 56-908-1-001.
FIGURe 5
OPTIONAL AIR AND DUST SeAL FOR SeRIeS RFII (TY3551)
CUP
SUPPORT
ROOM
SEAL
PLATE
RETAINER
SPRINKLER
CLEAN
PLATE
COVER
RETAINER
LIP OF
FACE OF
CEILING
BEVEL AS
ORIENT
SEAL
ASSEMBLY
COVER SHOWN