manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco
  6. •
  7. Security Sensor
  8. •
  9. Tyco 614 Series Manual

Tyco 614 Series Manual

Tyco 614 Series
Collective Smoke and CO
Fire Detectors
I N F O R M A T I O N S H E E T
DESCRIPTION
The Tyco 614 series of low profile fire detectors consists of:
• 614CH combined Carbon Monoxide (CO) and Heat detector
Using both CO and Heat sensors in combination enables an increase in
the sensitivity of the CO sensor when a rapid increase in temperature is
present (heat enhancement), making the 614CH suitable for detecting
both slow smouldering and fast flaming fires. The heat sensor also acts
as an independant rate-of-rise and fixed temperature detector Class A1R,
conforming to AS 7240.5-2004. The 614CH is well suited to applications
where heat detection alone is insufficient but smoke detectors are
vulnerable to nuisance alarms.
• 614P Photoelectric (Scattered Light) smoke detector
The 614P is listed as conforming to AS 7240.7:2004 and is well suited
to detecting visible smoke produced by smouldering fires including
overheated electrical cabling.
• 614I Ionisation smoke detector
The 614I Ionisation smoke detector is listed as conforming to
AS 7240.7:2004. It reacts to visible and invisible fire aerosols enabling
early detection of flaming fires.
The 614T Type A, B, C and D Heat detectors supplement the Tyco 614
series for heat only applications - refer separate information sheet. The 614
series detectors are compatible with Vigilant F3200, MX4428 and Simplex
4100U c.i.e. They may be used as service replacements for the Minerva 614
series detectors both on these and the obsolete F08 and F4000 panels.
INSTALLATION
The base should be fixed so that the park plunger faces toward the door
or trafficable area, to suit the 614T, should it be used. This ensures the
detector LED will be visible from the direction of entry, in accordance with
AS 1670.1-2004. However, the 614P/I/CH LED is visible through 360°
and can be oriented differently to suit the application. For effective detection
of fast flaming fires in sleeping areas, 614CH detectors should be spaced as
per heat detector requirements. Refer to the 5B base information sheet for
more details. The Tyco 614 detectors mount onto the base with a clockwise
rotational motion. Rotating the detector anticlockwise past an indent to the
park position disconnects the detector from the circuit whilst still retaining
it in the base. Depressing the plunger at the side of the base allows the
detector to be rotated back into its operating position.
TESTING
The 614CH is tested using the X330 in-situ tester with CO detector test
gas, part no. 517.001.262. The heat sensor can be tested in-situ using
the X461 test unit, in sleeping areas and where detection is engineered to
depend on the heat sensor. The 614P and 614I smoke detectors can be
tested in-situ using the X330 Test Tool with X500 Test Smoke.
MAINTENANCE
The Tyco 614 series detectors should be maintained in accordance with the
relevant section of AS 1851 (Australia) or NZS 4512:2003 (New Zealand).
Additionally, although the 614CH has an expected life in excess of 10
years, in order for the 614CH to provide the intended level of fire detection,
the detector should be checked for calibration 5 years after installation (or
5 years after re-installation following service) or within 7 years of the date
of manufacture. Wormald Detector Clean & Calibration Wollongong are
equipped and competent to check the calibration of 614CH detectors.
Environmental conditions of temperature and humidity outside the specified
range for more than momentary excursions may detrimentally affect the
service life or operation of the 614CH.
LOCKING DEVICE
A detector locking device is moulded into the 5B base.
This must be detached and inserted into the locking
aperture if required, prior to the selected detector being
installed. The detector may then be removed only by
inserting an unlocking tool (a Ø3 x 22mm long rod) into
the hole on the detector cover to depress the locking
device.
19 February 2008
Tyco614Inf0802 Issue 6 Tyco Safety Products - Australasia Page 1 of 2
SPECIFICATIONS
614CH 614I 614P
10 to 33Vdc 12 to 33Vdc 10 to 33Vdc
Quiescent Current
70µA 60µA 60µA
Alarm State Current1
5mA to 85mA
Alarm State Voltage 2
4V to 7.6V
Ext. Powered Load 3
50mA at 28Vdc (max.)
Ambient Temp
(min)
4
0°C -20°C -20°C
Ambient Temp
(max)
+50°C +70°C +70°C
Rel. Humidity
(min)
5
15% 10% 10%
Rel. Humidity
(max)
5
90% 95% 95%
Alarm Indicator Colour
Red
Remote Indicator
Tyco E500 Mk2 series
Dimensions (mm)
54 x 127 (H x dia)
Sensitivity
38ppm, A1R 0.32 MIC X 4%Obs/m
CSIRO ActivFire Listed
afp1718 afp1716 afp1715
Part Numbers
516.600.304 516.600.305 516.600.301
5B Base
517.050.017
In-situ Smoke Tester
517.001.255
In-situ Heat Tester
X461
Test Gas
517.001.262 X500 X500
Specifications are typical unless stated otherwise.
1. Must be externally limited. Minimum current for required LED visibility is 5mA.
Maximum current 85mA at 55°C. 2. Minimum voltage with remote indicator
shorted @ 5mA. Max @ 85mA without remote indicator connected. 3. Remote
indicator output can control external load from +24V, eg. sounder. 4. Storage
temp for 614CH -20°C to +55°C without exposure to icing or condensation.
5. Humidity must be non-condensing.
www.tycosafetyproducts-anz.com
Tyco Safety Products, a division of Tyco Australia Pty Limited
A.B.N. 80 008 399 004, reserve the right to alter specifications without
notice, in line with Tyco’s policy of continuing product improvement.
19 February 2008
Tyco614Inf0802 Issue 6 Tyco Safety Products - Australasia Page 2 of 2
WIRING
A maximum of two 1.5mm2 cables can
be connected at any one terminal. All
wiring terminates at the base as follows:
R: – Remote*
L: – In and Out
L1: + In & Remote
L2: + Out
* When a common remote indicator is
used for two or more detectors, join the ‘R’
terminal to the next base ‘R’ terminal. The
remote indicator will then activate when
any of the connected detectors signals an
alarm.
SEALING DETECTOR BASE HOLES
Where differential air pressure may exist between a ceiling cavity and the room below, it is advisable to seal cable access holes
to the back of a fire detector in the room, thus stopping ceiling cavity air from flowing past or through the detector that could
otherwise affect reliable fire detection. Such air flows may cause more rapid dust or moisture build-up in the detector or “shield”
the detector from smoke or hot gas in the room during a fire.
AVOIDING NUISANCE ALARMS
The incidence of nuisance alarms can be greatly reduced if the following precautions are taken:
a. Do not install smoke detectors in environments contaminated by airborne particles (eg. dust, saw-dust), where cigarette
smoke is prevalent, or in areas with condensing humidity (eg. bathrooms). Use appropriate heat or carbon monoxide detectors
in these areas.
b. Do not install detectors where high air velocity is expected. Air flow will increase the amount of dust that accumulates in a
detector and will increase the risk of nuisance alarms.
CARBON MONOXIDE FIRE DETECTION
CO is a toxic gas produced by carbon-based fires. Being colourless, odourless and tasteless, CO is almost impossible for
a person to detect. Exposure to raised levels of CO can cause disorientation and collapse during physical exertion, whilst
exposure to high levels of CO can lead to permanent brain damage and death. Slow-developing and smouldering fires produce
significant quantities of CO before detectable levels of smoke are released. In these situations CO detectors actuate far earlier
than Photoelectric or Ionisation smoke detectors. Where the 614CH is used in sole occupancy units, it must be installed on
heat detector spacing.
DETECTOR SELECTION GUIDE
In the table below, detectors in BOLD are recommended as the most suitable for detecting the given type of fire in the
particular environment. Non-bold detectors are suitable but may not give optimum performance for that application.
Environment
Fire type
Very clean
(computer
room)
Clean
(office,
hotel)
Moderately
clean
(warehouse)
Moderately
dirty/smoky
(loading area)
Dirty/
smoky
(car park)
Dirty/smoky
Hot
(kitchen)
Overheating (electrical/
electronic equipment)
614P
614I
614P
614I
614CH
614P
614I
614P
Smouldering
(wood, paper)
614CH
614P
614CH
614P
614P
614CH
614P
614CH
Flaming
(wood, paper, flammable liquids)
614CH
614I
614P
614CH
614I
614P
614I
614CH
614P
614I
614CH
614T**
Flaming with high heat
(late stage flaming)
614P
614I
614CH
614P
614I
614CH
614T**
614I
614T**
614CH
614I
614T**
614T** 614T**
614I = Ionisation Smoke Detector 614P = Photoelectric Smoke Detector 614CH = combined Carbon Monoxide (CO) and Class A1R Heat Detector
614T = 614T Heat Detector. These detectors can be used separately, or combined, to provide fire detection for most applications.
** Refer to 614T Information sheet
TYCO E500Mk2
REMOTE INDICATOR
TYCO 5B
UNIVERSAL
BASE
-
+
TYCO
COLLECTIVE
c.i.e.
ALARM
ZONE
CIRCUIT
-
+
ELD
R
L
M
L1
L2
R
L
M
L1
L2
R
LL1
L2
R
LL1
L2
Common Remote Indicator Link - see Note
PARK PLUNGER

This manual suits for next models

3

Other Tyco Security Sensor manuals

Tyco Visonic SMD-429 PG2 Series User manual

Tyco

Tyco Visonic SMD-429 PG2 Series User manual

Tyco SD-304C PG2 User manual

Tyco

Tyco SD-304C PG2 User manual

Tyco Visonic TOWER-30AM PG2 User manual

Tyco

Tyco Visonic TOWER-30AM PG2 User manual

Tyco WS4933 Series User manual

Tyco

Tyco WS4933 Series User manual

Tyco BLAZEMASTER CPVC User manual

Tyco

Tyco BLAZEMASTER CPVC User manual

Tyco Visonic PowerG NEXT CAM PG2 User manual

Tyco

Tyco Visonic PowerG NEXT CAM PG2 User manual

Tyco DSC PowerSeries PC1616 Manual

Tyco

Tyco DSC PowerSeries PC1616 Manual

Tyco Visonic TOWER-30AMPG2 User manual

Tyco

Tyco Visonic TOWER-30AMPG2 User manual

Tyco MX Technology 801Ex Series Manual

Tyco

Tyco MX Technology 801Ex Series Manual

Tyco TOWER-20AM User manual

Tyco

Tyco TOWER-20AM User manual

Tyco DSC WS8904P User manual

Tyco

Tyco DSC WS8904P User manual

Tyco PowerG PG9936H User manual

Tyco

Tyco PowerG PG9936H User manual

Tyco FC410DIM User manual

Tyco

Tyco FC410DIM User manual

Tyco MX-862 User manual

Tyco

Tyco MX-862 User manual

Tyco Visonic SD-304C PG2 User manual

Tyco

Tyco Visonic SD-304C PG2 User manual

Tyco FV300 SERIES User manual

Tyco

Tyco FV300 SERIES User manual

Tyco Visonic TOWER-20 PG2 User manual

Tyco

Tyco Visonic TOWER-20 PG2 User manual

Tyco WS4933 Series User manual

Tyco

Tyco WS4933 Series User manual

Popular Security Sensor manuals by other brands

Honeywell 2MLF-RD4A user guide

Honeywell

Honeywell 2MLF-RD4A user guide

Fire Sentry SS4-AS Installation guide and operating manual

Fire Sentry

Fire Sentry SS4-AS Installation guide and operating manual

System Sensor FAAST 9400X Installation and maintenance instructions

System Sensor

System Sensor FAAST 9400X Installation and maintenance instructions

urmet domus Grothe McGuard professional 120 Installation and Operating Instrucitons

urmet domus

urmet domus Grothe McGuard professional 120 Installation and Operating Instrucitons

Reed Instruments R5120 instruction manual

Reed Instruments

Reed Instruments R5120 instruction manual

Alcatel ASM 180 TD user manual

Alcatel

Alcatel ASM 180 TD user manual

Heiman HM-621THS user manual

Heiman

Heiman HM-621THS user manual

Ekinex EK-SM2-TP manual

Ekinex

Ekinex EK-SM2-TP manual

Olafus BDB55G-3 quick start guide

Olafus

Olafus BDB55G-3 quick start guide

Besam SR221-2 quick start guide

Besam

Besam SR221-2 quick start guide

Macurco CD-6MC User instructions

Macurco

Macurco CD-6MC User instructions

Optigene Genie HT user manual

Optigene

Optigene Genie HT user manual

SilverSaver 1000 quick start guide

SilverSaver

SilverSaver 1000 quick start guide

HELVAR digidim 314 installation guide

HELVAR

HELVAR digidim 314 installation guide

Lince 4059GR868ZENITH Installation, operation and maintenance manual

Lince

Lince 4059GR868ZENITH Installation, operation and maintenance manual

Allen-Bradley SensaGuard 440N-Z21SS2H-AS installation instructions

Allen-Bradley

Allen-Bradley SensaGuard 440N-Z21SS2H-AS installation instructions

WERMA Signaltechnik Ex-LED Signal Tower 741 Instructions for use

WERMA Signaltechnik

WERMA Signaltechnik Ex-LED Signal Tower 741 Instructions for use

ActSafe TCX Assault user manual

ActSafe

ActSafe TCX Assault user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.