  9. Unitronics Vision V130-T2 User manual

Unitronics Vision V130-T2 User manual

This manual suits for next models

24

Other Unitronics Controllers manuals

Unitronics Vision700 User manual

Unitronics

Unitronics Vision700 User manual

Unitronics Vision V120 User manual

Unitronics

Unitronics Vision V120 User manual

Unitronics UniStream Built-in Series User manual

Unitronics

Unitronics UniStream Built-in Series User manual

Unitronics Vision OPLC V130-33-TA24 User manual

Unitronics

Unitronics Vision OPLC V130-33-TA24 User manual

Unitronics UniStream USC-B10-RA28 User manual

Unitronics

Unitronics UniStream USC-B10-RA28 User manual

Unitronics Vision OPLC V130 User manual

Unitronics

Unitronics Vision OPLC V130 User manual

Unitronics Vision V350-35-TU24 User manual

Unitronics

Unitronics Vision V350-35-TU24 User manual

Unitronics Vision V130-J-TA24 User manual

Unitronics

Unitronics Vision V130-J-TA24 User manual

Unitronics Vision OPLC V1040-T20B User manual

Unitronics

Unitronics Vision OPLC V1040-T20B User manual

Unitronics VisionV120-22-UN2 User manual

Unitronics

Unitronics VisionV120-22-UN2 User manual

Unitronics Vision OPLC V1040-T20B User manual

Unitronics

Unitronics Vision OPLC V1040-T20B User manual

Unitronics MJ20-MEM1 User manual

Unitronics

Unitronics MJ20-MEM1 User manual

Unitronics Vision OPLC V560-T25B User manual

Unitronics

Unitronics Vision OPLC V560-T25B User manual

Unitronics Vision OPLC V130-J-B1 User manual

Unitronics

Unitronics Vision OPLC V130-J-B1 User manual

Unitronics UniStream US5-B5-B1 User manual

Unitronics

Unitronics UniStream US5-B5-B1 User manual

Unitronics Vision V130-TR6 User manual

Unitronics

Unitronics Vision V130-TR6 User manual

Unitronics V230 User manual

Unitronics

Unitronics V230 User manual

Unitronics Uni-COM UAC-CB-01RS2 User manual

Unitronics

Unitronics Uni-COM UAC-CB-01RS2 User manual

Unitronics Jazz JZ20-UA24 User manual

Unitronics

Unitronics Jazz JZ20-UA24 User manual

Unitronics Vision120 User manual

Unitronics

Unitronics Vision120 User manual

Unitronics UniStream USC-B5-R38 User manual

Unitronics

Unitronics UniStream USC-B5-R38 User manual

Unitronics V130-33-TR6 User manual

Unitronics

Unitronics V130-33-TR6 User manual

Unitronics Vision V130-33-R34 User manual

Unitronics

Unitronics Vision V130-33-R34 User manual

Unitronics Jazz OPLC JZ20-R10 User manual

Unitronics

Unitronics Jazz OPLC JZ20-R10 User manual

Popular Controllers manuals by other brands

Sunricher SR-ZV9003T3-RGBW-US Installation

Sunricher

Sunricher SR-ZV9003T3-RGBW-US Installation

Ksenia intro Installation and configuration manual

Ksenia

Ksenia intro Installation and configuration manual

Inovance CAN200 Series manual

Inovance

Inovance CAN200 Series manual

Gauzy LC6 FLEX Controller Installation and operation guide

Gauzy

Gauzy LC6 FLEX Controller Installation and operation guide

Viking SLP-1 Technical practice

Viking

Viking SLP-1 Technical practice

CKD KBX-30E-U Series instruction manual

CKD

CKD KBX-30E-U Series instruction manual

Sharp Energy Sun Flux User manual & installation guide

Sharp Energy

Sharp Energy Sun Flux User manual & installation guide

Yamaha RCX40 user manual

Yamaha

Yamaha RCX40 user manual

AB Quality PowerFlex 400 Frames D-H Service bulletin

AB Quality

AB Quality PowerFlex 400 Frames D-H Service bulletin

Yamaha MJC8 owner's manual

Yamaha

Yamaha MJC8 owner's manual

AL-KO ATC operating instructions

AL-KO

AL-KO ATC operating instructions

Savant SmartControl 2 Deployment guide

Savant

Savant SmartControl 2 Deployment guide

GameSir T3S user manual

GameSir

GameSir T3S user manual

Kostal inveor operating manual

Kostal

Kostal inveor operating manual

Emerson Yarway 20-55 Operating and safety instructions

Emerson

Emerson Yarway 20-55 Operating and safety instructions

CoCo ACM-LV24 Quick installation guide

CoCo

CoCo ACM-LV24 Quick installation guide

Brooks SLA5810/20 Installation and operation manual

Brooks

Brooks SLA5810/20 Installation and operation manual

SIGMA TEK SR 011 Technical manual

SIGMA TEK

SIGMA TEK SR 011 Technical manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Unitronics
1
Vision™PLC+HMI
User Guide
V130-33-T2/V130-J-T2
V350-35-T2/V350-J-T2
V430-J-T2
▪12 Digital Inputs, including 2 Analog,
3 HSC/Shaft-encoder inputs
▪12 Transistor Outputs
General Description
The products listed above are micro-PLC+HMIs, rugged programmable logic controllers that comprise
built-in operating panels.
Detailed Installation Guides containing the I/O wiring diagrams for these models, technical specifications,
and additional documentation are located in the Technical Library in the Unitronics website:
https://unitronicsplc.com/support-technical-library/
Item
V130-T2
V130J-T2
V350-T2
V350J-T2
V430J-T2
On-board I/O
Model Dependent
Screen
2.4"
3.5" Color Touch
4.3" Color Touch
Keypad
Yes
None
Function Keys
None
Yes
Com Port, Built-in
RS232/485
Yes
Yes
Yes*
Yes*
Yes*
USB device,
mini-B
None
None
Yes*
Yes*
Yes*
Com Ports, separate
order, user-installed
The user may install a CANbus port (V100-17-CAN), and one of the following:
•RS232/RS485 port (V100-17-RS4/V100-17-RS4X)
•Ethernet (V100-17-ET2)
•Profibus Slave (V100-17-PB1)
* V430J/V350/V350J comprises both RS232/485 and USB ports; note that only one channel may be used at a time.
Standard Kit Contents
Item
V130-T2
V130J-T2
V350-T2
V350J-T2
V430J-T2
Controller
Yes
Terminal Blocks
Yes
Battery (installed)
Yes
Slides
(2 sets of key labels)
None
Yes
None
Mounting Brackets
Yes (2 parts)
Yes (4 parts)
Rubber Seal
Yes
Vision™PLC+HMI Installation Guide
2
Unitronics
Alert Symbols and General Restrictions
When any of the following symbols appear, read the associated information carefully.
Symbol
Meaning
Description
Danger
The identified danger causes physical and property damage.
Warning
The identified danger could cause physical and property damage.
Caution
Caution
Use caution.
▪Before using this product, the user must read and understand this document.
▪All examples and diagrams are intended to aid understanding, and do not guarantee operation.
Unitronics accepts no responsibility for actual use of this product based on these examples.
▪Please dispose of this product according to local and national standards and regulations.
▪Only qualified service personnel should open this device or carry out repairs.
▪Failure to comply with appropriate safety guidelines can cause severe injury or property
damage.
▪Do not attempt to use this device with parameters that exceed permissible levels.
▪To avoid damaging the system, do not connect/disconnect the device when power is on.
Environmental Considerations
▪Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration, in
accordance with the standards given in the product’s technical specification sheet.
▪Do not place in water or let water leak onto the unit.
▪Do not allow debris to fall inside the unit during installation.
▪Ventilation: 10mm space required between controller’s top/bottom edges & enclosure walls.
▪Install at maximum distance from high-voltage cables and power equipment.
Mounting
Note that figures are for illustrative purposes only.
Dimensions: V130/V350/V130J/V350J
Vision™PLC+HMI
Unitronics
3
* Note that for models V130/V350, the bezel width is up to 8.4 mm (0.33”).
Dimensions: V430J
Model
Cut-out
View area
V130V130J
92x92 mm (3.622”x3.622”)
58x30.5mm (2.28"x1.2")
V350/V350J
92x92 mm (3.622”x3.622”)
72x54.5mm (2.95"x2.14")
V430J
122.5x91.5 mm (4.82”x3.6”)
96.4x55.2mm (3.79"x2.17")
Panel Mounting
Before you begin, note that the mounting panel cannot be more than 5 mm thick.
1. Make a panel cut-out of the appropriate size:
2. Slide the controller into the cut-out, ensuring that the rubber seal is in place.
3. Push the mounting brackets into their slots on the sides of the panel as shown in the figure below.
4. Tighten the bracket’s screws against the panel. Hold the bracket securely against the unit while
tightening the screw.
5. When properly mounted, the controller is squarely situated in the panel cut-out as shown in the
accompanying figures.
V130/V350/V130J/V350J
Vision™PLC+HMI Installation Guide
4
Unitronics
V430J
DIN-rail Mounting (V130/V350/V130J/V350J)
1. Snap the controller onto the DIN rail as
shown in the figure to the right.
2. When properly mounted, the controller is
squarely situated on the DIN-rail as
shown in the figure to the right.
UL Compliance
The following section is relevant to Unitronics’ products that are listed with the UL.
The following models: V130-33-R34, V130-J-R34, V130-T4-ZK1, V350-35-RA22, V350-J-RA22,
V350-35-R34, V350-J-R34, V430-J-R34
are UL listed for Hazardous Locations.
The following models: V130-33-B1,V130-J-B1,V130-33-TA24,V130-J-TA24,V130-33-T38,V130-J-T38
V130-33-TR20,V130-J-TR20,V130-33-TR34,V130-J-TR34,V130-33-RA22,V130-J-RA22,
V130-33-TRA22,V130-J-TRA22,V130-33-T2,V130-J-T2,V130-33-TR6,V130-J-TR6,V130-33-R34,
V350-35-B1, V130-T4-ZK1, V350-J-B1,V350-35-TA24,V350-J-TA24,V350-35-T38,V350-J-T38,
V350-35-TR20,V350-J-TR20,V350-35-TR34,V350-J-TR34,V350-35-TRA22,V350-J-TRA22,
V350-35-T2,V350-J-T2,V350-35-TR6,V350-J-TR6,V350-S-TA24,V350-JS-TA24,V350-35-RA22,
Vision™PLC+HMI
Unitronics
5
V350-J-RA22,V350-35-R34, V430-J-B1,V430-J-TA24,V430-J-T38, V430-J-R34,V430-J-RH2,
V430-J-TR34,V430-J-RA22,V430-J-TRA22,V430-J-T2,V430-J-RH6
are UL listed for Ordinary Location.
For models from series V130, V130-J, V430, that include “T4” or “J4” in the Model name, Suitable for
mounting on the flat surface of Type 4X enclosure.
For examples: V130-T4-R34, V130-J4-R34, V430-J4-T2
UL Ordinary Location
In order to meet the UL ordinary location standard, panel-mount this device on the flat surface
of Type 1 or 4 X enclosures
UL Ratings, Programmable Controllers for Use in Hazardous Locations,
Class I, Division 2, Groups A, B, C and D
These Release Notes relate to all Unitronics products that bear the UL symbols used to mark products
that have been approved for use in hazardous locations, Class I, Division 2, Groups A, B, C and D.
Caution
▪This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, or Non-
hazardous locations only.
▪Input and output wiring must be in accordance with Class I, Division 2 wiring methods and in
accordance with the authority having jurisdiction.
▪WARNING—Explosion Hazard—substitution of components may impair suitability for Class I,
Division 2.
▪WARNING –EXPLOSION HAZARD –Do not connect or disconnect equipment unless power
has been switched off or the area is known to be non-hazardous.
▪WARNING –Exposure to some chemicals may degrade the sealing properties of material
used in Relays.
▪This equipment must be installed using wiring methods as required for Class I, Division 2 as
per the NEC and/or CEC.
Panel-Mounting
For programmable controllers that can be mounted also on panel, in order to meet the UL Haz Loc
standard, panel-mount this device on the flat surface of Type 1 or Type 4X enclosures.
Relay Output Resistance Ratings
The products listed below contain relay outputs:
Programmable controllers, Models: V430-J-R34, V130-33-R34,V130-J-R34 and V350-35-R34,
V350-J-R34
▪When these specific products are used in hazardous locations, they are rated at 3A res.
▪Except for models V430-J-R34, V130-33-R34, V130-J-R34, V130-T4-ZK1 and V350-35-R34,
V350-J-R34,when these specific products are used in non-hazardous environmental conditions,
they are rated at 5A res, as given in the product’s specifications.
Communication and Removable Memory Storage
When products comprise either USB communication port, SD card slot, or both, neither
the SD card slot nor the USB port are intended to be permanently connected, while the USB port is
intended for programming only.
Removing / Replacing the battery
When a product has been installed with a battery, do not remove or replace the battery unless the
power has been switched off, or the area is known to be non-hazardous.
Vision™PLC+HMI Installation Guide
6
Unitronics
Please note that it is recommended to back up all data retained in RAM, in order to avoid losing data
when changing the battery while the power is switched off. Date and time information will also need to
be reset after the procedure.
UL des zones ordinaires:
Pour respecter la norme UL des zones ordinaires, monter l'appareil sur une surface plane de type de
protection 1 ou 4X
Certification UL des automates programmables, pour une utilisation en
environnement à risques, Class I, Division 2, Groups A, B, C et D.
Cette note fait référence à tous les produits Unitronics portant le symbole UL - produits qui ont été
certifiés pour une utilisation dans des endroits dangereux, Classe I, Division 2, Groupes A, B, C et D.
Attention
▪Cet équipement est adapté pour une utilisation en Classe I, Division 2, Groupes A, B, C et
D, ou dans Non-dangereux endroits seulement.
▪Le câblage des entrées/sorties doit être en accord avec les méthodes
de câblage selon la Classe I, Division 2 et en accord avec l’autorité compétente.
▪AVERTISSEMENT: Risque d’Explosion – Le remplacement de certains composants rend
caduque la certification du produit selon la Classe I, Division 2.
▪AVERTISSEMENT - DANGER D'EXPLOSION - Ne connecter pas ou ne débranche pas
l'équipement sans avoir préalablement coupé l'alimentation électrique ou la zone est
reconnue pour être non dangereuse.
▪AVERTISSEMENT - L'exposition à certains produits chimiques peut dégrader les propriétés
des matériaux utilisés pour l'étanchéité dans les relais.
▪Cet équipement doit être installé utilisant des méthodes de câblage suivant la norme Class I,
Division 2 NEC et /ou CEC.
Montage de l'écran:
Pour les automates programmables qui peuvent aussi être monté sur l'écran,
pour pouvoir être au standard UL, l'écran doit être monté dans un coffret avec une surface plane de
type 1 ou de type 4X.
Certification de la résistance des sorties relais
Les produits énumérés ci-dessous contiennent des sorties relais:
▪Automates programmables, modèles : V430-J-R34, V130-33-R34,V130-J-R34 and
V350-35-R34,V350-J-R34
▪Lorsque ces produits spécifiques sont utilisés dans des endroits dangereux, ils supportent
un courant de 3A charge résistive.
▪Excepté les modèles: V430-J-R34, V130-33-R34,V130-J-R34, V130-T4-ZK1 et V350-35-R34,
V350-J-R34 lorsque ces produits spécifiques sont utilisés dans un environnement non dangereux, ils
sont évalués à 5A res, comme indiqué dans les specifications du produit Plages de températures
Communication et de stockage amovible de mémoire (carte mémoire)
Produits comprend un port USB de communication, soit un port carte SD ou les deux, ni le port SD, ni
le port USB ne sont censés être utilisés en permanence, tandis que l'USB est destiné à la
programmation uniquement.
Retrait / Remplacement de la batterie
Lorsqu'un produit a été installé avec une batterie, retirez et remplacez la batterie seulement si
l’alimentation est éteinte ou si l’environnement n’est pas dangereux.
Vision™PLC+HMI
Unitronics
7
Veuillez noter qu'il est recommandé de sauvegarder toutes les données conservées dans la RAM, afin
d'éviter de perdre des données lors du changement de la batterie lorsque l'alimentation est coupée. Les
informations sur la date et l'heure devront également être réinitialisées après la procédure
Wiring
▪Do not touch live wires.
▪Install an external circuit breaker. Guard against short-circuiting in external wiring.
▪Use appropriate circuit protection devices.
▪Unused pins should not be connected. Ignoring this directive may damage the device.
▪Double-check all wiring before turning on the power supply.
Caution
▪To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm).
▪Do not use tin, solder, or any substance on stripped wire that might cause the wire
strand to break.
▪Install at maximum distance from high-voltage cables and power equipment.
Wiring Procedure
Use crimp terminals for Use crimp terminals for wiring;
- Controllers offering a terminal block with pitch of 5mm: 26-12 AWG wire (0.13 mm2–3.31 mm2).
- Controllers offering a terminal block with pitch of 3.81mm: 26-16 AWG wire (0.13 mm2–1.31 mm2).
1. Strip the wire to a length of 7±0.5mm (0.270–0.300“).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure a proper connection.
4. Tighten enough to keep the wire from pulling free.
▪Input or output cables should not be run through the same multi-core cable or share
the same wire.
▪Allow for voltage drop and noise interference with I/O lines used over an extended distance.
Use wire that is properly sized for the load.
▪The controller and I/O signals must be connected to the same 0V signal.
I/Os
V130/V350/V130J/V350J/V430J-T2 models comprise a total of 12 inputs and 12 transistor outputs.
Input functionality can be adapted as follows:
12 inputs may be used as digital inputs. They may be wired in a group via a single jumper
as either npn or pnp.
According to jumper settings and appropriate wiring:
- Inputs 10 and 11 can function as either digital or analog inputs.
- Inputs 0, 2 and 4 can function as high-speed counters, as part of a shaft-encoder,
or as normal digital inputs.
- Inputs 1, 3 and 5 can function as either counter reset, as part of a shaft-encoder,
or as normal digital inputs.
- If inputs 0, 2 and 4 are set as high-speed counters (without reset), inputs 1, 3 and 5 can function
as normal digital inputs.
Vision™PLC+HMI Installation Guide
8
Unitronics
Input Jumper Settings
The tables below show how to set a specific jumper to change input functionality. To access the I/O
jumpers, you must open the controller according to the instructions beginning on page 11.
▪Incompatible jumper settings and wiring connections may seriously damage the controller.
▪Do not move JP2.
Digital Inputs 0-11: Set Type
Set to
JP1 (all Inputs)
npn (sink)
A
pnp (source)*
B
Inputs 10/11: Set as Digital or Analog
Set to
JP5 (Input 10)
JP6 (Input 11)
Digital*
A
A
Analog
B
B
Analog Inputs AN0/AN1: Set Type
Set to
JP3 (AN0)
JP4 (AN1)
Voltage*
A
A
Current
B
B
*Default settings
I/O Wiring
npn (sink) Input
Input wiring
HSC input wiring
Vision™PLC+HMI
Unitronics
9
pnp (source) Input
Input wiring
HSC input wiring
Shaft-encoder
Analog Input
Analog input wiring, current (2/3-wire)
Analog input wiring, current (4-wire), Voltage
▪Shields should be connected at the signal’s source.
▪The 0V signal of the analog input must be connected to the controller’s 0V.
Vision™PLC+HMI Installation Guide
10
Unitronics
Transistors Outputs
▪Outputs 0 to 6 can be used as PWM outputs.
Power Supply
The controller requires an external 24VDC power supply.
▪The power supply must include double insulation. Outputs must be rated as
SELV/PELV/Class2/Limited Power.
▪Use separate wires to connect the functional
earth line (pin 3) and the 0V line (pin 2) to the
system earth ground.
▪Install an external circuit breaker. Guard
against short-circuiting in external wiring.
▪Double-check all wiring before turning
on the power supply.
▪Do not connect either the ‘Neutral’ or ‘Line’
signal of the 110/220VAC to device’s 0V pin
▪In the event of voltage fluctuations or non-
conformity to voltage power supply
specifications, connect the device to
a regulated power supply.
Earthing the PLC+HMI
To maximize system performance, avoid electromagnetic interference by:
▪Mounting the controller on a metal panel.
▪Connect each common and ground connection directly to the earth ground of your system.
▪For ground wiring uses the shortest and thickest possible wire.