Unitronics Vision V130-T2 User manual

Unitronics
1
Vision™PLC+HMI
User Guide
V130-33-T2/V130-J-T2
V350-35-T2/V350-J-T2
V430-J-T2
▪12 Digital Inputs, including 2 Analog,
3 HSC/Shaft-encoder inputs
▪12 Transistor Outputs
General Description
The products listed above are micro-PLC+HMIs, rugged programmable logic controllers that comprise
built-in operating panels.
Detailed Installation Guides containing the I/O wiring diagrams for these models, technical specifications,
and additional documentation are located in the Technical Library in the Unitronics website:
https://unitronicsplc.com/support-technical-library/
Item
V130-T2
V130J-T2
V350-T2
V350J-T2
V430J-T2
On-board I/O
Model Dependent
Screen
2.4"
3.5" Color Touch
4.3" Color Touch
Keypad
Yes
None
Function Keys
None
Yes
Com Port, Built-in
RS232/485
Yes
Yes
Yes*
Yes*
Yes*
USB device,
mini-B
None
None
Yes*
Yes*
Yes*
Com Ports, separate
order, user-installed
The user may install a CANbus port (V100-17-CAN), and one of the following:
•RS232/RS485 port (V100-17-RS4/V100-17-RS4X)
•Ethernet (V100-17-ET2)
•Profibus Slave (V100-17-PB1)
* V430J/V350/V350J comprises both RS232/485 and USB ports; note that only one channel may be used at a time.
Standard Kit Contents
Item
V130-T2
V130J-T2
V350-T2
V350J-T2
V430J-T2
Controller
Yes
Terminal Blocks
Yes
Battery (installed)
Yes
Slides
(2 sets of key labels)
None
Yes
None
Mounting Brackets
Yes (2 parts)
Yes (4 parts)
Rubber Seal
Yes
Vision™PLC+HMI Installation Guide
2
Unitronics
Alert Symbols and General Restrictions
When any of the following symbols appear, read the associated information carefully.
Symbol
Meaning
Description
Danger
The identified danger causes physical and property damage.
Warning
The identified danger could cause physical and property damage.
Caution
Caution
Use caution.
▪Before using this product, the user must read and understand this document.
▪All examples and diagrams are intended to aid understanding, and do not guarantee operation.
Unitronics accepts no responsibility for actual use of this product based on these examples.
▪Please dispose of this product according to local and national standards and regulations.
▪Only qualified service personnel should open this device or carry out repairs.
▪Failure to comply with appropriate safety guidelines can cause severe injury or property
damage.
▪Do not attempt to use this device with parameters that exceed permissible levels.
▪To avoid damaging the system, do not connect/disconnect the device when power is on.
Environmental Considerations
▪Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration, in
accordance with the standards given in the product’s technical specification sheet.
▪Do not place in water or let water leak onto the unit.
▪Do not allow debris to fall inside the unit during installation.
▪Ventilation: 10mm space required between controller’s top/bottom edges & enclosure walls.
▪Install at maximum distance from high-voltage cables and power equipment.
Mounting
Note that figures are for illustrative purposes only.
Dimensions: V130/V350/V130J/V350J
Vision™PLC+HMI
Unitronics
3
* Note that for models V130/V350, the bezel width is up to 8.4 mm (0.33”).
Dimensions: V430J
Model
Cut-out
View area
V130V130J
92x92 mm (3.622”x3.622”)
58x30.5mm (2.28"x1.2")
V350/V350J
92x92 mm (3.622”x3.622”)
72x54.5mm (2.95"x2.14")
V430J
122.5x91.5 mm (4.82”x3.6”)
96.4x55.2mm (3.79"x2.17")
Panel Mounting
Before you begin, note that the mounting panel cannot be more than 5 mm thick.
1. Make a panel cut-out of the appropriate size:
2. Slide the controller into the cut-out, ensuring that the rubber seal is in place.
3. Push the mounting brackets into their slots on the sides of the panel as shown in the figure below.
4. Tighten the bracket’s screws against the panel. Hold the bracket securely against the unit while
tightening the screw.
5. When properly mounted, the controller is squarely situated in the panel cut-out as shown in the
accompanying figures.
V130/V350/V130J/V350J
Vision™PLC+HMI Installation Guide
4
Unitronics
V430J
DIN-rail Mounting (V130/V350/V130J/V350J)
1. Snap the controller onto the DIN rail as
shown in the figure to the right.
2. When properly mounted, the controller is
squarely situated on the DIN-rail as
shown in the figure to the right.
UL Compliance
The following section is relevant to Unitronics’ products that are listed with the UL.
The following models: V130-33-R34, V130-J-R34, V130-T4-ZK1, V350-35-RA22, V350-J-RA22,
V350-35-R34, V350-J-R34, V430-J-R34
are UL listed for Hazardous Locations.
The following models: V130-33-B1,V130-J-B1,V130-33-TA24,V130-J-TA24,V130-33-T38,V130-J-T38
V130-33-TR20,V130-J-TR20,V130-33-TR34,V130-J-TR34,V130-33-RA22,V130-J-RA22,
V130-33-TRA22,V130-J-TRA22,V130-33-T2,V130-J-T2,V130-33-TR6,V130-J-TR6,V130-33-R34,
V350-35-B1, V130-T4-ZK1, V350-J-B1,V350-35-TA24,V350-J-TA24,V350-35-T38,V350-J-T38,
V350-35-TR20,V350-J-TR20,V350-35-TR34,V350-J-TR34,V350-35-TRA22,V350-J-TRA22,
V350-35-T2,V350-J-T2,V350-35-TR6,V350-J-TR6,V350-S-TA24,V350-JS-TA24,V350-35-RA22,
Vision™PLC+HMI
Unitronics
5
V350-J-RA22,V350-35-R34, V430-J-B1,V430-J-TA24,V430-J-T38, V430-J-R34,V430-J-RH2,
V430-J-TR34,V430-J-RA22,V430-J-TRA22,V430-J-T2,V430-J-RH6
are UL listed for Ordinary Location.
For models from series V130, V130-J, V430, that include “T4” or “J4” in the Model name, Suitable for
mounting on the flat surface of Type 4X enclosure.
For examples: V130-T4-R34, V130-J4-R34, V430-J4-T2
UL Ordinary Location
In order to meet the UL ordinary location standard, panel-mount this device on the flat surface
of Type 1 or 4 X enclosures
UL Ratings, Programmable Controllers for Use in Hazardous Locations,
Class I, Division 2, Groups A, B, C and D
These Release Notes relate to all Unitronics products that bear the UL symbols used to mark products
that have been approved for use in hazardous locations, Class I, Division 2, Groups A, B, C and D.
Caution
▪This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, or Non-
hazardous locations only.
▪Input and output wiring must be in accordance with Class I, Division 2 wiring methods and in
accordance with the authority having jurisdiction.
▪WARNING—Explosion Hazard—substitution of components may impair suitability for Class I,
Division 2.
▪WARNING –EXPLOSION HAZARD –Do not connect or disconnect equipment unless power
has been switched off or the area is known to be non-hazardous.
▪WARNING –Exposure to some chemicals may degrade the sealing properties of material
used in Relays.
▪This equipment must be installed using wiring methods as required for Class I, Division 2 as
per the NEC and/or CEC.
Panel-Mounting
For programmable controllers that can be mounted also on panel, in order to meet the UL Haz Loc
standard, panel-mount this device on the flat surface of Type 1 or Type 4X enclosures.
Relay Output Resistance Ratings
The products listed below contain relay outputs:
Programmable controllers, Models: V430-J-R34, V130-33-R34,V130-J-R34 and V350-35-R34,
V350-J-R34
▪When these specific products are used in hazardous locations, they are rated at 3A res.
▪Except for models V430-J-R34, V130-33-R34, V130-J-R34, V130-T4-ZK1 and V350-35-R34,
V350-J-R34,when these specific products are used in non-hazardous environmental conditions,
they are rated at 5A res, as given in the product’s specifications.
Communication and Removable Memory Storage
When products comprise either USB communication port, SD card slot, or both, neither
the SD card slot nor the USB port are intended to be permanently connected, while the USB port is
intended for programming only.
Removing / Replacing the battery
When a product has been installed with a battery, do not remove or replace the battery unless the
power has been switched off, or the area is known to be non-hazardous.
Vision™PLC+HMI Installation Guide
6
Unitronics
Please note that it is recommended to back up all data retained in RAM, in order to avoid losing data
when changing the battery while the power is switched off. Date and time information will also need to
be reset after the procedure.
UL des zones ordinaires:
Pour respecter la norme UL des zones ordinaires, monter l'appareil sur une surface plane de type de
protection 1 ou 4X
Certification UL des automates programmables, pour une utilisation en
environnement à risques, Class I, Division 2, Groups A, B, C et D.
Cette note fait référence à tous les produits Unitronics portant le symbole UL - produits qui ont été
certifiés pour une utilisation dans des endroits dangereux, Classe I, Division 2, Groupes A, B, C et D.
Attention
▪Cet équipement est adapté pour une utilisation en Classe I, Division 2, Groupes A, B, C et
D, ou dans Non-dangereux endroits seulement.
▪Le câblage des entrées/sorties doit être en accord avec les méthodes
de câblage selon la Classe I, Division 2 et en accord avec l’autorité compétente.
▪AVERTISSEMENT: Risque d’Explosion – Le remplacement de certains composants rend
caduque la certification du produit selon la Classe I, Division 2.
▪AVERTISSEMENT - DANGER D'EXPLOSION - Ne connecter pas ou ne débranche pas
l'équipement sans avoir préalablement coupé l'alimentation électrique ou la zone est
reconnue pour être non dangereuse.
▪AVERTISSEMENT - L'exposition à certains produits chimiques peut dégrader les propriétés
des matériaux utilisés pour l'étanchéité dans les relais.
▪Cet équipement doit être installé utilisant des méthodes de câblage suivant la norme Class I,
Division 2 NEC et /ou CEC.
Montage de l'écran:
Pour les automates programmables qui peuvent aussi être monté sur l'écran,
pour pouvoir être au standard UL, l'écran doit être monté dans un coffret avec une surface plane de
type 1 ou de type 4X.
Certification de la résistance des sorties relais
Les produits énumérés ci-dessous contiennent des sorties relais:
▪Automates programmables, modèles : V430-J-R34, V130-33-R34,V130-J-R34 and
V350-35-R34,V350-J-R34
▪Lorsque ces produits spécifiques sont utilisés dans des endroits dangereux, ils supportent
un courant de 3A charge résistive.
▪Excepté les modèles: V430-J-R34, V130-33-R34,V130-J-R34, V130-T4-ZK1 et V350-35-R34,
V350-J-R34 lorsque ces produits spécifiques sont utilisés dans un environnement non dangereux, ils
sont évalués à 5A res, comme indiqué dans les specifications du produit Plages de températures
Communication et de stockage amovible de mémoire (carte mémoire)
Produits comprend un port USB de communication, soit un port carte SD ou les deux, ni le port SD, ni
le port USB ne sont censés être utilisés en permanence, tandis que l'USB est destiné à la
programmation uniquement.
Retrait / Remplacement de la batterie
Lorsqu'un produit a été installé avec une batterie, retirez et remplacez la batterie seulement si
l’alimentation est éteinte ou si l’environnement n’est pas dangereux.
Vision™PLC+HMI
Unitronics
7
Veuillez noter qu'il est recommandé de sauvegarder toutes les données conservées dans la RAM, afin
d'éviter de perdre des données lors du changement de la batterie lorsque l'alimentation est coupée. Les
informations sur la date et l'heure devront également être réinitialisées après la procédure
Wiring
▪Do not touch live wires.
▪Install an external circuit breaker. Guard against short-circuiting in external wiring.
▪Use appropriate circuit protection devices.
▪Unused pins should not be connected. Ignoring this directive may damage the device.
▪Double-check all wiring before turning on the power supply.
Caution
▪To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm).
▪Do not use tin, solder, or any substance on stripped wire that might cause the wire
strand to break.
▪Install at maximum distance from high-voltage cables and power equipment.
Wiring Procedure
Use crimp terminals for Use crimp terminals for wiring;
- Controllers offering a terminal block with pitch of 5mm: 26-12 AWG wire (0.13 mm2–3.31 mm2).
- Controllers offering a terminal block with pitch of 3.81mm: 26-16 AWG wire (0.13 mm2–1.31 mm2).
1. Strip the wire to a length of 7±0.5mm (0.270–0.300“).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure a proper connection.
4. Tighten enough to keep the wire from pulling free.
▪Input or output cables should not be run through the same multi-core cable or share
the same wire.
▪Allow for voltage drop and noise interference with I/O lines used over an extended distance.
Use wire that is properly sized for the load.
▪The controller and I/O signals must be connected to the same 0V signal.
I/Os
V130/V350/V130J/V350J/V430J-T2 models comprise a total of 12 inputs and 12 transistor outputs.
Input functionality can be adapted as follows:
12 inputs may be used as digital inputs. They may be wired in a group via a single jumper
as either npn or pnp.
According to jumper settings and appropriate wiring:
- Inputs 10 and 11 can function as either digital or analog inputs.
- Inputs 0, 2 and 4 can function as high-speed counters, as part of a shaft-encoder,
or as normal digital inputs.
- Inputs 1, 3 and 5 can function as either counter reset, as part of a shaft-encoder,
or as normal digital inputs.
- If inputs 0, 2 and 4 are set as high-speed counters (without reset), inputs 1, 3 and 5 can function
as normal digital inputs.
Vision™PLC+HMI Installation Guide
8
Unitronics
Input Jumper Settings
The tables below show how to set a specific jumper to change input functionality. To access the I/O
jumpers, you must open the controller according to the instructions beginning on page 11.
▪Incompatible jumper settings and wiring connections may seriously damage the controller.
▪Do not move JP2.
Digital Inputs 0-11: Set Type
Set to
JP1 (all Inputs)
npn (sink)
A
pnp (source)*
B
Inputs 10/11: Set as Digital or Analog
Set to
JP5 (Input 10)
JP6 (Input 11)
Digital*
A
A
Analog
B
B
Analog Inputs AN0/AN1: Set Type
Set to
JP3 (AN0)
JP4 (AN1)
Voltage*
A
A
Current
B
B
*Default settings
I/O Wiring
npn (sink) Input
Input wiring
HSC input wiring
Vision™PLC+HMI
Unitronics
9
pnp (source) Input
Input wiring
HSC input wiring
Shaft-encoder
Analog Input
Analog input wiring, current (2/3-wire)
Analog input wiring, current (4-wire), Voltage
▪Shields should be connected at the signal’s source.
▪The 0V signal of the analog input must be connected to the controller’s 0V.
Vision™PLC+HMI Installation Guide
10
Unitronics
Transistors Outputs
▪Outputs 0 to 6 can be used as PWM outputs.
Power Supply
The controller requires an external 24VDC power supply.
▪The power supply must include double insulation. Outputs must be rated as
SELV/PELV/Class2/Limited Power.
▪Use separate wires to connect the functional
earth line (pin 3) and the 0V line (pin 2) to the
system earth ground.
▪Install an external circuit breaker. Guard
against short-circuiting in external wiring.
▪Double-check all wiring before turning
on the power supply.
▪Do not connect either the ‘Neutral’ or ‘Line’
signal of the 110/220VAC to device’s 0V pin
▪In the event of voltage fluctuations or non-
conformity to voltage power supply
specifications, connect the device to
a regulated power supply.
Earthing the PLC+HMI
To maximize system performance, avoid electromagnetic interference by:
▪Mounting the controller on a metal panel.
▪Connect each common and ground connection directly to the earth ground of your system.
▪For ground wiring uses the shortest and thickest possible wire.
Vision™PLC+HMI
Unitronics
11
Communication
▪V130/ V130J
These models comprise a built-in RS232/RS485 serial port (Port 1)
▪V430J/ V350/V350J
These models comprise built-in ports: 1 USB and 1 RS232/RS485 (Port 1).
Note that physically connecting a PC to the controller via USB suspends RS232/RS485
communications via Port 1. When the PC is disconnected, RS232/RS485 resumes.
RS232/RS485 Port
▪Turn off power before making communications connections.
Caution
▪Always use the appropriate port adapters.
Caution
▪Signals are related to the controller’s 0V; the same 0V is used by the power supply.
▪The serial port is not isolated. If the controller is used with a non-isolated external device,
avoid potential voltage that exceeds ± 10V.
▪Use RS232 to download programs from a PC, and to communicate with serial devices and
applications, such as SCADA.
▪Use RS485 to create a multi-drop network containing up to 32 devices.
Pinouts
The pinouts below show the PLC port signals.
RS232
RS485**
Controller Port
Pin #
Description
Pin #
Description
Pin #1
1*
DTR signal
1
A signal (+)
2
0V reference
2
(RS232 signal)
3
TXD signal
3
(RS232 signal)
4
RXD signal
4
(RS232 signal)
5
0V reference
5
(RS232 signal)
6*
DSR signal
6
B signal (-)
* Standard programming cables do not provide connection points for pins 1 and 6.
** When a port is adapted to RS485, Pin 1 (DTR) is used for signal A,
and Pin 6 (DSR) signal is used for signal B.
Note that it is possible to establish a PC to PLC connection using RS232 even when the PLC is set to
RS485 (this eliminates the need to open the controller to set jumpers).
To do so, remove the RS485 connector (pins 1 & 6) from the PLC and connect a standard RS232
programming cable.
Note that this is possible only if DTR and DSR signals of RS232 are not used (which is the standard
case).
Vision™PLC+HMI Installation Guide
12
Unitronics
Setting RS232/RS485 Communication Parameters, V430J
This port may be set to either RS232 or RS485 via DIP switches:
The table shows the DIP switches factory default settings. Use the table to adapt the settings.
Switch Settings
1
2
3
4
5
6
RS232*
ON
OFF
OFF
ON
OFF
OFF
RS485
OFF
ON
ON
OFF
OFF
OFF
RS485 with
termination**
OFF
ON
ON
OFF
ON
ON
* Default factory setting
** Causes the unit to function as an end unit in an RS485 network
USB Port
Caution
▪The USB port is not isolated.
Make sure that the PC and the controller are grounded to same potential.
The USB port may be used for programming, OS download, and PC access.
Setting RS232/RS485 Communication Parameters, V130/V350/V130J/V350J
This port may be set to either RS232 or RS485 via jumper.
The accompanying figure shows the jumper factory
default settings.
These jumpers may be used to:
▪Set communications to RS485, by setting both
COMM jumpers to ‘485’.
▪Set RS485 termination, by setting both TERM
jumpers to ‘OFF’.
To access the jumpers, you must open the controller
according to the instructions on page 11.
Vision™PLC+HMI
Unitronics
13
Opening the Controller
▪Before performing these actions, touch a grounded object to discharge any electrostatic charge.
▪Avoid touching the PCB board directly. Hold the PCB board by its connectors.
1. Turn off the power supply, disconnect, and dismount the controller.
2. The back cover of the controller comprises 4 screws, located in the corners.
Remove the screws, and pull off the back cover.
Changing I/O Settings
After opening the controller and exposing the I/O board, you can change the jumper settings according
to the table shown above.
Changing Communication Settings (V130/V350/V130J/V350J Only)
1. To access the communication jumpers, hold the I/O PCB board by its top and bottom connectors
and steadily pull the board off.
2. Locate the jumpers, and then change the settings as required, according to the jumpers’ settings
shown on page 10.
Closing the Controller
1. Gently replace the board. Make certain that the pins fit correctly into their matching receptacle.
Do not force the board into place; doing so may damage the controller.
2. Replace the back cover of the controller and fasten the corner screws.
Note that you must replace the back cover securely before powering up the controller.
Vision™PLC+HMI Installation Guide
14
Unitronics
Vision™PLC+HMI
V130-33-T2/V130-J-T2
V350-35-T2/V350-J-T2
V430-J-T2
Technical Specifications
Order Information
Item
V130-33-T2
PLC with Classic panel, Monochrome display 2.4"
V130-J-T2
PLC with Flat panel, Monochrome display 2.4"
V350-35-T2
PLC with Classic panel, Color touch display 3.5’’
V350-J-T2
PLC with Flat panel, Color touch display 3.5’’
V430-J-T2
PLC with Flat panel, Color touch display 4.3’’
You can find additional information, such as wiring diagrams, in the product’s installation guide
located in the Technical Library at www.unitronics.com.
Power Supply
Item
V130-T2
V130J-T2
V350-T2
V350J-T2
V430J-T2
Input voltage
24VDC
Permissible range
20.4VDC to 28.8VDC with less than 10% ripple
Max. current
consumption
See Note 1
npn inputs
210mA@24VDC
230mA@24VDC
230mA@24VDC
pnp inputs
110mA@24VDC
135mA@24VDC
135mA@24VDC
Notes:
1. To calculate the actual power consumption, subtract the current for each unused element from the maximum
current consumption value according to the values below:
Backlight
Ethernet card
V130/J
10mA
35mA
V350/J/V430J
20mA
35mA
Digital Inputs
Number of inputs
12.See note 2
Input type
See note 2
Galvanic isolation
None
Nominal input
voltage
24VDC
Input Voltage
pnp (source)
0-5VDC for Logic ‘0’
17-28.8VDC for Logic ‘1’
npn (sink)
17-28.8VDC for Logic ‘0’
0-5VDC for Logic ‘1’
Input Current
8mA@24VDC
Input impedance
3KΩ
Response Time
10ms typical, when used as normal digital
input
Input Cable length
Normal digital
Input
Up to 100 meters
High Speed Input
Up to 50 meters, shielded, see Frequency table below
Vision™PLC+HMI
Unitronics
15
High speed inputs
Specifications below apply when wired as HSC/shaft-encoder.
See Note 2
Frequency (max)
See Note 3
Cable length (max.)
HSC
Shaft-encoder
10m
30kHz
20kHz
25m
30kHz
13kHz
50m
25kHz
9kHz
Duty cycle
40-60%
Resolution
32-bit
Notes:
2. V130/V350/V130J/V350J/V430J-T2 models comprise a total of 12 inputs.
12 inputs may be used as digital inputs. They may be wired, in a group, and set to either
npn or pnp via a single jumper.
In addition, according to jumper settings and appropriate wiring:
- Inputs 10 and 11 can function as either digital or analog inputs.
- Inputs 0, 2, and 4 can function as high-speed counters, as part of a shaft-encoder,
or as normal digital inputs.
- Inputs 1, 3, and 5 can function as either counter reset, as part of a shaft-encoder,
or as normal digital inputs.
- If inputs 0, 2, 4 are set as high-speed counters (without reset), inputs 1, 3, 5 can function as normal digital
inputs.
3. pnp/npn maximum frequency is at 24VDC.
Analog Inputs
Number of inputs
2, according to wiring as described above in Note 2
Input type
Multi-range inputs: 0-10V, 0-20mA, 4-20mA
Input range
0-20mA, 4-20mA
0-10VDC
Input impedance
243Ω
>150KΩ
Maximum input rating
25mA, 6V
15V
Galvanic isolation
None
Conversion method
Successive approximation
Resolution (except 4-20mA)
10-bit (1024 units)
Resolution (at 4-20mA)
204 to 1023 (820 units)
Conversion time
One configured input is updated per scan. See Note 4
Precision
0.9%
Status indication
Yes –if an analog input deviates above the permissible range, its value will be
1024.
Notes:
4. For example, if 2 inputs are configured as analog, it takes 2 scans to update all analog values.
Vision™PLC+HMI Installation Guide
16
Unitronics
Digital Outputs
Number of outputs
12 transistor pnp (source)
Output type
P-MOSFET (open drain)
Isolation
None
Output current
(resistive load)
0.5A maximum per output
3A maximum total per common
Maximum frequency
50Hz (resistive load)
0.5Hz (inductive load)
PWM maximum frequency
0.5KHz (resistive load). See Note 2
Short circuit protection
Yes
Short circuit indication
Via software
On voltage drop
0.5VDC maximum
Power supply for outputs
Operating voltage
20.4 to 28.8VDC
Nominal voltage
24VDC
Notes:
2. Outputs 0 to 6 can be used as PWM outputs.
Graphic Display Screen
Item
V130-T2
V130J-T2
V350-T2
V350J-T2
V430J-T2
LCD Type
STN, LCD display
TFT, LCD display
TFT, LCD display
Illumination backlight
White LED
White LED
White LED
Display resolution
128x64 pixels
320x240 pixels
480x272 pixels
Viewing area
2.4"
3.5"
4.3"
Colors
Monochrome
65,536 (16-bit)
65,536 (16-bit)
Screen Contrast
Via software
(Store value to SI 7,
values range: 0 to
100%)
Fixed
Fixed
Touchscreen
None
Resistive, analog
Resistive, analog
‘Touch’ indication
None
Via buzzer
Via buzzer
Screen brightness control
Via software
(Store value to SI 9,
0 = Off, 1 = On)
Via software
(Store value to SI 9, values range: 0 to 100%)
Virtual Keypad
None
Displays virtual keyboard when the application requires
data entry.
Keypad
Item
V130-T2
V130J-T2
V350-T2
V350J-T2
V430J-T2
Number of keys
20 keys,including 10
user-labeled keys
5 programmable function keys
Key type
Metal dome, sealed membrane switch
Slides
Slides may be
installed
in the operating
panel faceplate to
custom-label the
keys. Refer to V130
Keypad Slides.pdf.
A complete set of
blank slides is
available by separate
order
Slides may be installed
in the operating panel
faceplate to custom-label
the keys. Refer to V350
Keypad Slides.pdf.
Two sets of slides are
supplied with the
controller: one set of
arrow keys, and one
blank set.
None
Vision™PLC+HMI
Unitronics
17
Vision™PLC+HMI Installation Guide
18
Unitronics
Program
Item
V130-T2
V130J-T2
V350-T2
V350J-T2
V430J-T2
Memory size
Application Logic
512KB
1MB
1MB
Images
128KB
6MB
12MB
Fonts
128KB
512KB
512KB
Operand type
Quantity
Symbol
Value
Item
V130-T2
V130J-T2
V350-T2
V350J-T2
V430J-T2
Memory Bits
4096
8192
MB
Bit (coil)
Memory Integers
2048
4096
MI
16-bit signed/unsigned
Long Integers
256
512
ML
32-bit signed/unsigned
Double Word
64
256
DW
32-bit unsigned
Memory Floats
24
64
MF
32-bit signed/unsigned
Fast Bits
1024
1024
XB
Fast Bits (coil) –not retained
Fast Integers
512
512
XI
16 bit signed/unsigned
(fast, not retained)
Fast Long Integers
256
256
XL
32 bit signed/unsigned
(fast, not retained)
Fast Double Word
64
64
XDW
32 bit unsigned (fast, not retained)
Timers
192
384
T
Res. 10 ms; max 99h, 59 min, 59.99s
Counters
24
32
C
32-bit
Data Tables
120K dynamic data (recipe parameters, datalogs, etc.)
192K fixed data (read-only data, ingredient names, etc)
Expandable via SD card. See Removable Memory below
HMI displays
Up to 1024
Program scan time
20µs per 1kb
of typical
application
15µs per 1kb
of typical
application
Removable Memory
Micro SD card
Compatible with standard SD and SDHC; up to 32GB store datalogs, Alarms, Trends,
Data Tables, backup Ladder, HMI, and OS.
See Note 6
Notes:
6.User must format via Unitronics SD tools utility.
Vision™PLC+HMI
Unitronics
19
Communication Ports
Port 1
1 channel, RS232/RS485 and USB device (V430/ V350/V350J only). See Note 7
Galvanic isolation
No
Baud rate
300 to 115200 bps
RS232
Input voltage
±20VDC absolute maximum
Cable length
15m maximum (50’)
RS485
Input voltage
-7 to +12VDC differential maximum
Cable type
Shielded twisted pair, in compliance with EIA 485
Cable length
1200m maximum (4000’)
Nodes
Up to 32
USB device
(V430/V350/V350J only)
Port type
Mini-B, See Note 9
Specification
USB 2.0 complaint; full speed
Cable
USB 2.0 complaint; up to 3m
Port 2 (optional)
See Note 8
CANbus (optional)
See Note 8
Notes:
7. This model is supplied with a serial port: RS232/RS485 (Port 1). The standard is set to either RS232 or RS485
according to jumper settings. Refer to the product’s Installation Guide.
8. The user may order and install one or both of the following modules:
- An additional port (Port 2). Available port types: RS232/RS485 isolated/non-isolated, Ethernet
- A CANbus port
Port module documentation is available on the Unitronics website.
9. Note that physically connecting a PC to the controller via USB suspends RS232/RS485 communications
via Port 1. When the PC is disconnected, RS232/RS485 resumes.
I/O Expansion
Additional I/Os may be added. Configurations vary according to module.
Supports digital, high-speed, analog, weight and temperature measurement I/Os.
Local
Via I/O Expansion Port. Integrate up to 8 I/O Expansion Modules comprising up
to 128 additional I/Os. Adapter required (P.N. EX-A2X).
Remote
Via CANbus port. Connect up to 60 adapters to a distance of 1000 meters from
controller; and up to 8 I/O expansion modules to each adapter (up to a total of
512 I/Os). Adapter required (P.N. EX-RC1).
Miscellaneous
Clock (RTC)
Real-time clock functions (date and time)
Battery back-up
7 years typical at 25°C, battery back-up for RTC and system data, including
variable data
Battery replacement
Yes. Coin-type 3V, lithium battery, CR2450
Vision™PLC+HMI Installation Guide
20
Unitronics
Dimensions
Item
V130-T2
V130J-T2
V350-T2
V350J-T2
V430J-T2
Size
Vxxx
109 x 114.1 x 68mm
(4.29 x 4.49 x 2.67”).
See Note 10
109 x 114.1 x 68mm
(4.29 x 4.49 x 2.67”).
See Note 10
Vxxx-J
109 x 114.1 x 66mm
(4.92 x 4.49 x 2.59”).
See Note 10
109 x 114.1 x 66mm
(4.92 x 4.49 x 2.59”).
See Note 10
136 x 105.1 x 61.3mm
(5.35 x 4.13 x 2.41”).
See Note 10
Weight
315g (11.11 oz)
335g (11.81 oz)
365g (12.87 oz)
Notes:
10. For exact dimensions, refer to the product’s Installation Guide.
Environment
Operational temperature
0 to 50ºC (32 to 122ºF)
Storage temperature
-20 to 60ºC (-4 to 140ºF)
Relative Humidity (RH)
10% to 95% (non-condensing)
Mounting method
Panel mounted (IP65/66/NEMA4X)
DIN-rail mounted (IP20/NEMA1)
Operating Altitude
2000m (6562 ft)
Shock
IEC 60068-2-27, 15G, 11ms duration
Vibration
IEC 60068-2-6, 5Hz to 8.4Hz, 3.5mm constant amplitude,
8.4Hz to 150Hz, 1G acceleration.
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole
discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or
temporarily withdraw any of the forgoing from the market.
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of
merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in
this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising
out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other
third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them
UG_V130_350_430-T2 12/22

This manual suits for next models

24

Other Unitronics Controllers manuals

Unitronics Samba OPLC SM43-J-R20 User manual

Unitronics

Unitronics Samba OPLC SM43-J-R20 User manual

Unitronics MJ20-MEM1 User manual

Unitronics

Unitronics MJ20-MEM1 User manual

Unitronics Vision OPLC V570-57-C30B User manual

Unitronics

Unitronics Vision OPLC V570-57-C30B User manual

Unitronics M91-19-R1 User manual

Unitronics

Unitronics M91-19-R1 User manual

Unitronics Jazz JZ20-UA24 User manual

Unitronics

Unitronics Jazz JZ20-UA24 User manual

Unitronics UniStream User manual

Unitronics

Unitronics UniStream User manual

Unitronics Jazz OPLC JZ20-R10 User manual

Unitronics

Unitronics Jazz OPLC JZ20-R10 User manual

Unitronics Vision 230 User manual

Unitronics

Unitronics Vision 230 User manual

Unitronics VisionV120-22-UN2 User manual

Unitronics

Unitronics VisionV120-22-UN2 User manual

Unitronics Vision V130-J Series User manual

Unitronics

Unitronics Vision V130-J Series User manual

Unitronics Vision V130-33-R34 User manual

Unitronics

Unitronics Vision V130-33-R34 User manual

Unitronics Uni-COM UAC-CB-01RS2 User manual

Unitronics

Unitronics Uni-COM UAC-CB-01RS2 User manual

Unitronics Vision V130-33-T2 User manual

Unitronics

Unitronics Vision V130-33-T2 User manual

Unitronics Samba SM70-J-TA22 User manual

Unitronics

Unitronics Samba SM70-J-TA22 User manual

Unitronics Vision V350-35-TU24 User manual

Unitronics

Unitronics Vision V350-35-TU24 User manual

Unitronics Vision OPLC V1040-T20B User manual

Unitronics

Unitronics Vision OPLC V1040-T20B User manual

Unitronics Vision V350-35-T2 User manual

Unitronics

Unitronics Vision V350-35-T2 User manual

Unitronics UniStream Built-in Series User manual

Unitronics

Unitronics UniStream Built-in Series User manual

Unitronics Vision V570-57-T40B User manual

Unitronics

Unitronics Vision V570-57-T40B User manual

Unitronics Vision OPLC V350-35-TA24 User manual

Unitronics

Unitronics Vision OPLC V350-35-TA24 User manual

Unitronics Jazz JZ20-J-UN20 User manual

Unitronics

Unitronics Jazz JZ20-J-UN20 User manual

Unitronics UniStream USC-B3-R20 User manual

Unitronics

Unitronics UniStream USC-B3-R20 User manual

Unitronics Vision V130-J-TA24 User manual

Unitronics

Unitronics Vision V130-J-TA24 User manual

Unitronics Samba OPLC Series User manual

Unitronics

Unitronics Samba OPLC Series User manual

Popular Controllers manuals by other brands

HALOGEN VALVE SYSTEMS Terminator Installation, operation and maintenance manual

HALOGEN VALVE SYSTEMS

HALOGEN VALVE SYSTEMS Terminator Installation, operation and maintenance manual

elco ELK 38 operating instructions

elco

elco ELK 38 operating instructions

Carrier PREMIERLINK 33CSPREMLK Installation and configuration guide

Carrier

Carrier PREMIERLINK 33CSPREMLK Installation and configuration guide

LEGRAND ALPTEC 5.2 instructions

LEGRAND

LEGRAND ALPTEC 5.2 instructions

Rice Lake 880 Performance Series Operation manual

Rice Lake

Rice Lake 880 Performance Series Operation manual

Cielo BREEZ PLUS user manual

Cielo

Cielo BREEZ PLUS user manual

TINY TNC-M14-CNC Operation manual

TINY

TINY TNC-M14-CNC Operation manual

Yudian AI-518 operation instruction

Yudian

Yudian AI-518 operation instruction

Roger PR311SE Function guide

Roger

Roger PR311SE Function guide

Linak TD4 quick guide

Linak

Linak TD4 quick guide

National Instruments NI PXI-6653 installation guide

National Instruments

National Instruments NI PXI-6653 installation guide

Altinex Wireless Touchscreen Controller CP451-008 user guide

Altinex

Altinex Wireless Touchscreen Controller CP451-008 user guide

bonitron M3460 Customer Reference Manual

bonitron

bonitron M3460 Customer Reference Manual

ESPEC P-300 CONFIGURATION AND TROUBLESHOOTING MANUAL

ESPEC

ESPEC P-300 CONFIGURATION AND TROUBLESHOOTING MANUAL

Christie E510 Technical reference

Christie

Christie E510 Technical reference

dIXEL XC450D operating instructions

dIXEL

dIXEL XC450D operating instructions

Levven GDT15 instruction sheet

Levven

Levven GDT15 instruction sheet

EME FINCOR 2230 MKII Series Equipment manual

EME

EME FINCOR 2230 MKII Series Equipment manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.