Valcom PagePac Plus V-5323100 User manual

Issue 1
1 947180
PAGEPAC PLUS CONTROLLER (V-5323100) AND
CONTROLLER WITH POWER SUPPLY (V-5323105)
by
PagePac®
INTRODUCTION
The PagePac® Plus System consists of the Controller,
AmpliCenter, and up to 3 Zone Expansion Units, providing
up to 56 paging and/or control zones. The self-powered
Controller comes with its own power supply, enabling it to
control paging and control zones utilizing a paging amplifier
other than the AmpliCenter.
Dimensions/Weight
• 16.0”W x 1.8”H x 6.9”D
(40.64cm x 4.5cm x 17.5cm)
2.0 lbs. (0.9 kg)
SPECIFICATIONS
FEATURES
• 8 Zones Paging or Control • Night Bell
• Contact Closure Inputs or Outputs • 7 Alert Tones
• Loop Start, Ground Start, CO Port, Analog Station • Page Zone Groups
or Dry Loop Access • Flexible Numbering Plan
• Controller with Power Supply for Applications with
Distributed Amplified Speakers or Amplifiers other than PagePac
INSTALLATION
1. Mount the PagePac® Plus Controller and Zone Expansion Units, if any, to either a wall
(see Figure 1), cabinet or a rack (below the AmpliCenter or other amplifier) (see Figure 2).
Note: When installing the PagePac Plus Controller, leave at least four inches of space above and below
for proper ventilation.
Install the paging equipment in a ventilated room where there is easy access to speaker cabling (prefer-
ably in the telephone equipment room).
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

2 947180
Figure 1. Wall Mounted Hardware
Figure 2. Rack Mounted Hardware
2. Connect background music input wires to Left and Right terminals if stereo, or, Left and Ground if not.
See Figure 3.
Note: The optional audio source can be a CD or tape player, AM, FM, or commercial radio, or other
audio device.
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

3 947180
If more than one AmpliCenter is used in the paging system, each one can be connected to the same
music source, or different audio device, if desired.
Figure 3. Music Input Connections on AmpliCenter
3. Plug modular cord into connectors “To Amp” on Controller and “Page In” on AmpliCenter
(see Figure 4).
Note: If an amplifier other than the AmpliCenter is used, refer to page 10. There you will find wiring dia-
grams and notes.
Figure 4. Page In Connection from Controller to AmpliCenter
4. Connect 8-pin Molex connector from AmpliCenter to Controller (see Figure 5).
Note: Connectors can only go in one way. DO NOT force in.
If you are using another type of amplifier, refer to the example system setups.
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

4 947180
Figure 5. 8-pin Molex Connector from AmpliCenter to Controller
1. Set the AmpliCenter Telephone Mode Selection Switch to Dry Loop 600 Ohms (Far left setting).
See Figure 6.
Figure 6. AmpliCenter Mode Switch Setting
2. Connect 8-pin Molex from Controller to Zone Expansion Unit(s), if used. See Figure 7.
Note: Up to 3 Zone Expansion Units can be used, providing up to 56 paging and/or control zones.
Figure 7. 8-pin Molex Connector from Controller to Zone Expansion Unit(s)
CAUTION:
Damage to Controller will occur if the Molex connector (from AmpliCenter) is
plugged into the right connector (This goes to Zone Expansion Units).
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

5 947180
3. Set DIP switches on each Zone Expansion Unit, if any. See Figure 8.
Note: These DIP switches must be set correctly in order for the Controller to recognize the additional
zones.
Figure 8. Setting Zone Expansion Unit DIP Switches
4. Using a small standard screwdriver, make the following adjustments:
a. Adjust the Low Frequency Cut Off control to center position. This control cuts out the low fre-
quency bass so that horns and small speakers are not over-driven and distorted by excessive
bass energy. Cut-off frequency is continuously adjustable from 50Hz (full CCW rotation) to 400 Hz
(full CW rotation). See Figure 9.
b. Adjust the Page VOX (voice activated) sensitivity to the fully counterclockwise position.
c. Adjust Music Input level to the center position. Clockwise rotation will increase the level. Listen
and set to a comfortable level.
d. Adjust Music Ducking level to the fully counterclockwise position. This feature allows music to
continue to be heard during a page, but at a reduced level. The range is less than –40 dB (full
CCW) to –6 dB (full CW). If music is not connected, set to full CCW.
Figure 9. Sound Level Adjustments on AmpliCenter
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

6 947180
5. Set Telephone Mode switch on Controller to match host telephone system interface port type.
See Figure 10.
Figure 10. Setting Controller Telephone Mode Switch
6. Connect cable from host telephone system to Controller Page Input.
See Figure 11.
Note: Depending on the type of host telephone system interface port, the connection may differ slightly
from the illustration to the right. A direct 4-conductor cord from the Controller to the telephone system
can also be used, bypassing the connector block.
Figure 11. Connecting Host Telephone System to Controller
7. Connect two wires from the night bell analog station port on the host telephone system to Controller
night bell (N.B.) input. See Figure 12.
Figure 12. Night Bell Connection to Controller
BLACK
GREEN
RED
YELLOW
CONNECT GREEN WIRE TO SYSTEM TIP T
CONNECT RED WIRE TO SYSTEM RING R
CONNECT BLACKWIRE TO THE PAIREDDRY CONTACTCONTROL LEADGROUND
CONNECT YELLOW WIRE TO THE PAIRED DRY CONTACT CONTROL LEAD C1
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

7 947180
8. Set the Zone Option switches on the Controller and Zone Expansion Units, if any.
Note: For each zone used, no matter what its function, this switch needs to be set to one of three set-
tings for proper zone operation.
The Controller has eight switches for zones 1-8. Each subsequent Zone Expansion Unit has switches for
zones 9-24, 25-40, and 41-56.
Figure 13. Setting Zone Option Switches on Controller and Zone Expansion Units
CONNECTING SPEAKERS
Connect each speaker to the appropriate Home Run or Speaker-to-speaker wiring scheme as shown on
the floor plan. See Figure 14.
Figure 14. Speaker Wiring Methods
70V
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

8 947180
Figure 15. Contact Closure Zone Wiring to Controller
3. Test speaker wiring for short circuits.
Measure the resistance of each home run wiring with an ohmmeter. Any pair indicating a value of less
than 15 Ohms must be rechecked for possible shorted wiring or speakers. Correct any problems and
retest.
4. Make zone connections to Controller and any Zone Expansion Units. See Figure 15.
The zone connectors on the Controller and Zone Expansion Units can accommodate up to two 22 AWG
wires or four 24 AWG wires per zone output.
Note: DO NOT over tighten zone connector screws.
Check zone option switch setting with Zone Map and Zone Configuration Tables as you connect each
zone (A 70V audio output setting going to other than speakers may damage other equipment).
INPUT
CONTACT
CLOSURE
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

9 947180
POWERING UP SYSTEM
With all zones wired and connected to the Controller and Zone Expansion Units (if any), initial testing
can begin. Refer to Controls and Indicators, Terminals and Connector. Once initial testing is done, you
can begin to program the Controller with the features for each zone.
1. Plug the power cord into the AC input connector on the AmpliCenter. The following should happen:
a. The green Power LED on the AmpliCenter will turn on and stay on.
b. The green Page Access LED on the AmpliCenter also turns on, but will go out after a few
seconds.
c. On the Controller, verify that the green Phone System Enabled LED if off, and that the yellow
Attendant Access Enabled LED is off.
e. If background music is connected, adjust the Music In Input Level control on the AmpliCenter(s)
for an acceptable level.
NOTE: If an amplifier other than the AmpliCenter is used, make sure it is powered up and verify the
Controller LEDs.
2. Make an All Zone test page. Readjust sound levels by adjusting speaker tap settings, if required.
a. Readjust Music Input level to the desired loudness relative to paging loudness.
b. Some loudspeaker taps may have to be re-adjusted to get even coverage at all locations. Be sure
that the final speaker tap setting totals do not exceed the power rating of the AmpliCenter.
3. Begin programming the Controller (refer to Programming Section).
SELF-POWERED CONTROLLER CONNECTIONS
The wiring diagrams in Figures 16 through 18 illustrate the connection of the Self-Powered Controller
with other amplifiers. In this way, most features associated with the Controller can be utilized with ampli-
fiers other than the AmpliCenter. Refer to Tables 1 and 2 for gain and sensitivity settings.
CONTROLLER TO GENERIC AMPLIFIER
To install the Controller to a Generic Amplifier (see Figure 16):
1. Connect 0dBu or 0dBm output to amplifier audio input.
Note: Refer to Tables 1 and 2 for proper audio input requirements and volume control settings.
2. Connect Amplifier Audio Output (70.7V) to Amplified Audio Input on Controller.
3. Adjust Controller volume control (see Table 1).
4. If required, connect control input to amplifier from Controller zone set to “output contact closure.”
5. Connect background music input, if any.
6. Connect host telephone system to Controller.
7. Plug power pack connector into Controller.
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

10 947180
Figure 16. Connection of the Self-Powered Controller to Generic Amplifiers
Table 1. Controller Adjustable Output Levels
Controller Volume Control Setting 600 Ohm Impedance Output Low Impedance Output
Full Counter Clockwise -12 dBm (195mV rms) -6 dBu (388mV rms)
Full Clockwise 0 dBm (.775V rms) +6 dBu (1.5V rms)
*NOTE: The generic amplifiers input must be dry, no battery or voltage can be present Condition: -12 dBm on the telephone
interface or -12 dBu on the attendant access input, both outputs are terminated with 600 ohms.
TELEPHONE INPUT OR
AUX INPUT
(DRY INPUT, NO BATTERY OR
VOLTAGE CAN BE PRESENT)
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

11 947180
CONTROLLER TO AMPLIFIED SPEAKERS
To install a Controller to Amplified Speakers (see Figure 17):
1. Connect 0dBu output from Controller to Amplified Audio input of Controller.
2. Adjust Controller volume control to mid point.
3. Connect amplified speakers to each zone connector.
4. Set zone option switches to Amplified Audio Output.
5. Connect host telephone system to Controller.
6. Plug Power Pack connector into Controller.
Figure 17. Self-Powered Controller Driving Amplified Speakers
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

12 947180
CONTROLLER TO D-SERIES AMPLICENTER
To install a Controller to a D-Series AmpliCenter (see Figure 18):
1. Connect 6-conductor cord from Controller (To Amp) to AmpliCenter Page Input.
2. Connect 70V audio out from AmpliCenter to Controller Amplified Audio terminals.
3. Connect host telephone system input to Controller.
4. Plug power pack connector into Controller.
Figure 18. Self-Powered Controller Connected to the PagePac D-Series AmpliCenter
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

13 947180
PROGRAMMING THE CONTROLLER
The Controller is programmed to enable each zone to have different zone features, if required. There are
two ways to do the programming. One is via the RS-232 serial port on the Controller which is connected
to an IBM compatible (DOS) PC using the optional programming software.
An advantage of using a PC to configure the Controller is that screens can be viewed on the monitor to
aid in selecting the zones for various options. A re-programming of the entire system can be done before
downloading the configuration to the controller, saving down time. Furthermore, the old configuration can
be saved and used again.
The other method works via the telephone access port (like calling to make a page), which accepts only
touchtone telephone keypad inputs (DTMF) tones. The Controller has the ability to retain all program-
ming options in non-volatile EEPROM memory or as a .CFG (configuration) file on a personal computer.
PROGRAMMING STEPS
The Zone Option switches on the rear of the Controller and Zone Expansion units must be set to match
the zone option selected for programming. The slide switch for each zone must be manually set to Con-
tact Closure (to switch on/off a device, such as a door security lock, remote amplifier, etc.), Input Contact
Closure, or Audio Output, depending on the mode selected for each zone.
IMPORTANT! It is recommended that the paging zone decisions be made and filled in on the Zone Map
and Configuration Tables, located on pages 32-35 prior to setting zone option switches and
programming.
* * ENTER PROGRAMMING MODE
1. From any DTMF telephone in the system, dial the paging access extension.
2. Dial the Connect Password (if optioned).
You will hear the paging system dial tone.
3. Dial * *
You will hear confirmation tone, then dial tone. Now programming may begin.
1 0 RESET TO FACTORY DEFAULTS
1. Dial 1 0
You will hear two beeps from the Controller.
2. Dial 2 5 3 2 7
After a long pause, you will hear 3 beeps from the Controller. The controller is now set to factory default
conditions.
3. Program the system options (refer to the following paragraphs).
You may exit the programming mode by dialing #.
CAUTION:
The Zone Option switches must be set before the system is powered up, and
therefore before programming commences.
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

14 947180
2 0 DEFINE LENGTH OF ALIAS NUMBERS
This system option allows you to set the length (3 or 4 digits) of the ALIAS number field. The default is 2
digits. If you wish to assign ALIAS numbers to the paging zones, you must set the length parameter. The
ALIAS number is the dialing extension for the zone. If no ALIAS numbers are used, the Physical Zone
Code is the dialing extension for a zone.
First access the PagePac Plus system and enter the programming mode by pressing ∗∗and then
entering your Programming password (if optioned). You may exit the programming mode by dialing #.
Note: This MUST be done before “Zone Map Option – Assigning ALIAS Numbers,” later in this section.
1. Dial 2 0 to select this option.
Hear a DOUBLE beep.
Press 3 or 4 to set length of ALIAS numbers (number of digits dialed to reach paging zone).
Hear TRIPLE beeps.
3. To verify the setting, dial 2 1 and repeat step 2 above.
2 2 SET SERIAL PORT BIT RATE
The speed (bit rate) of the controller's RS-232 serial port can be set to the rate of the computer monitor
or visual display. Default is 9600 bps. The bit rate may be changed at any time, but the Controller must
be reset (power off then on again) in order to take effect.
1. Dial 2 2 to select this option
Hear a DOUBLE beep.
2. Dial a code to select the Serial Port Bit Rate
0to select 300 bps
1to select 1200 bps
2to select 2400 bps
3to select 4800 bps
4to select 9600 bps
5to select 14400 bps
6to select 19200 bps
Hear TRIPLE beeps.
3. To verify the status of this option, dial 23and repeat step 2 above.
2 4 INHIBIT DIAL TONE DETECT
Supervision of the Station/Centrex Access mode is accomplished in 3 ways, by monitoring the loop cur-
rent and the audio signal (including dial tone), and a forced disconnect timer. This option (only applicable
in the station access mode) enables you to defeat the dial tone detect function in order to send a tone via
the Telephone Interface to the output.
1. Dial 2 4 to select this option.
Hear a DOUBLE beep.
2. Dial 0to turn Enable, or 1to turn Inhibit.
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

15 947180
Hear TRIPLE beeps.
3. To verify the condition (OFF/ON) of the Dial Tone Detect option, dial 2 5 and repeat step 2 above.
3 0 SET CONNECT PASSWORD
This feature will not become active until the first time you enter a password, via the programming mode.
The factory default is NO password. The Connect password operates as a security block into the paging
system, restricting paging access to authorized users.
Note: You may want to use a short Connect password (2 or 3 digits only) for ease of use.
1. Dial 3 0 to select this option.
Hear a DOUBLE beep.
2. Enter the Password you wish to use (up to 6 digits). If the password has fewer than 6 digits, enter the
#to terminate the string.
Note: For example, 123456 is a valid password entry. 123# is also a valid password entry, resulting in
the password 123.
If you already have entered a password and want to remove it (to have NO password), just enter the #
alone. Hear TRIPLE beeps.
To verify that the new Connect password has been established, dial 3 1 and repeat step 2 above.
3 2 SET PROGRAMMING PASSWORD
Establishing a Programming password will restrict access to the programming mode of the PagePac
Plus paging system. It is recommended that access to programming be restricted to the System Admin-
istrator, Telecommunications Manager, or other selected users.
Note: Your Connect and Programming passwords should not be the same. If this feature is active and
the system has been accessed via the telephone interface, then after the first digit of your Programming
password is pressed, the dial tone will stop and will not be returned until the correct password is entered
or until the user hangs up and re-enters the system.
This feature will become active once any programming password has been entered via the programming
mode. You are not required to establish such a password. The factory-set default programming pass-
word is ∗∗.
1. Dial 3 2 to select this option.
Hear a DOUBLE beep.
2. Enter the Password you wish to use (up to 6 digits). If the password has fewer than 6 digits, enter the
#to terminate the string.
If you already have entered a password and now want to remove it (to have NO password), just enter the
#alone.
For example, 234567 is a valid password entry. 234# is also a valid password entry, resulting in the
password 234.
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

16 947180
Hear TRIPLE beeps.
3. To verify that the new Programming password has been established, dial 3 3 and repeat step 2
above.
Forgot the Password? If either or both the connect password and programming password are forgot-
ten, it will be necessary to call the Help line (refer to page ii) for instructions how to erase the two pass-
words and be able to enter new ones.
4 0 TURN CONFIRMATION TONE ON/OFF
When the option is ON, a tone will be sent to the telephone interface after a zone has been selected and
before a page can be made. The default setting is ON.
1. Dial 4 0 to select this option.
Hear a DOUBLE beep.
2. Dial 0to turn OFF, or 1to turn ON.
Hear TRIPLE beeps.
3. To verify the Confirmation Tone condition (OFF or ON), dial 4 1 and repeat step 2 above.
4 2 TURN PRE-ANNOUNCEMENT TONE ON/OFF
This tone is very similar to the initial talk-back warning tone, in the sense that it is sent to a zone when
the zone is accessed. This tone will be sent out to both the zone selected and to the telephone interface.
After this tone is sent, you may begin your page message. Default is ON.
1. Dial 4 2 to select this option.
Hear a DOUBLE beep.
2. Dial 0to turn OFF, or 1to turn ON.
Hear TRIPLE beeps.
3. To verify the condition (OFF or ON) of the pre-announcement tone, dial 4 3 and repeat step 2 above.
4 4 SET TALKBACK WARNING TONE
This tone is intended to alert a person that their conversation is being monitored through the paging sys-
tem loudspeaker. If Talkback is optioned for YES, then the choices will be Initial, 30 Second Repetition,
or Off. The default setting for this parameter is Initial and 30 Second Repetition.
1. Dial 4 4 to select this option.
Hear a DOUBLE beep.
2. Dial 0to turn OFF, 1to select INITIAL tone only, or 2to select Initial and 30 Second repeat.
Hear TRIPLE beeps.
3. To verify the condition of the Talkback Warning tone, dial 45and repeat step 2 above.
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

17 947180
5 0 SET VOX DISCONNECT TIMING
The system will hang up on a page if no audio is detected for the programmed amount of time. The
default time is 30 seconds, but can be varied from 10 seconds to 60 seconds, in 10 second increments,
or can be disabled completely.
1. Dial 5 0 to select this option.
Hear a DOUBLE beep.
2. Dial the code to select a duration for the VOX Disconnect Timing:
0to turn OFF
1to select 10 seconds4 to select 40 seconds
2to select 20 seconds5 to select 50 seconds
3to select 30 seconds6 to select 60 seconds
Hear TRIPLE beeps.
3. To verify the duration of the VOX Disconnect Timing, dial 5 1 and repeat step 2 above.
5 2 ENABLE COMPUTER MONITOR
This option selects a device to be connected to the Controller RS-232 port, a computer monitor for log-
ging of all paging activity or a visual message display. The default setting is Computer Monitor.
By selecting Computer Monitor (the default option), the system is enabled to monitor activity on Atten-
dant Access, Telephone Interface, and Night Bell inputs. This feature requires that a PC computer be
connected to the RS-232 port of the Controller. Whenever the input becomes active, ASCII characters
will be sent out the RS-232 port (DB9 pin connector) to the computer. The ASCII characters will be inter-
cepted by a special software package in the computer that logs the time, date, input zone, type of activ-
ity, zone that was paged, and duration of the activity. All such input activity to the paging system can then
be viewed (and recorded) on the computer.
By selecting Display, the monitoring activity described above enables commands to be sent to a visual
message display where preprogrammed messages are displayed.
1. Dial 5 2 to select this option.
Hear a DOUBLE beep.
2. Dial the 0to select Computer Monitor, or 1to select Visual Display
Hear TRIPLE beeps.
3. To verify the status of this option, dial 53and repeat step 2 above.
If a Computer Monitor or visual message display has been connected and Controller software loaded,
you will need to select the types of paging inputs to be displayed or recorded. See next programming
option “Input Computer Monitor.”
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

18 947180
5 4 SELECT INPUT TO COMPUTER MONITOR
This option turns ON or OFF the inputs of Attendant Access, Telephone Access, and Night Bell to be
recorded and displayed by the Computer Monitor if you have activated it in Step 10. Default is OFF for all
three.
You will repeat this procedure 3 times in order to reset all three inputs.
1. Dial 5 4 to select this option.
Hear a DOUBLE beep.
2. Dial the code to select an option for one of the three inputs:
0to turn OFF the Attendant Access.
1to turn ON the Attendant Access.
2to turn OFF the Telephone Access.
3to turn ON the Telephone Access.
4to turn OFF the Night Bell.
5to turn ON the Night Bell.
Hear TRIPLE beeps.
3. To verify the status of this option, dial 5 5 and repeat step 2 above.
5 6 SET SUPERVISED TRUNK MODE
If the host telephone system does not have a supervised trunk option this feature does not apply.
Proceed to Step 14.
Note: Once the option has been configured, you should place the Controller Telephone Mode switch to
the Ground Start position. Connect the telephone interface to a Loop Start trunk on the host system
using a standard two-conductor (not four-conductor) RJ-11 cable.
The Supervised Trunk access mode provides both VOX Disconnect and Forced Disconnect timeouts.
When the Controller detects that the it has been off hook for two minutes, it opens the trunk circuit for
one second, ending the call. Also, if no voice activity is detected for the period specified by the VOX Dis-
connect programming option (normally 30 seconds), or if the telephone is overridden by a higher priority
activity (i.e., attendant access), the call is disconnected.
Note: The Ground Start and Station Access modes are not available when the Controller is configured
for Supervised Trunk mode. Supervised Trunk mode must be turned off to re-enable these access
modes.
1. Dial 5 6 to select this option
Hear a DOUBLE beep.
2. Press 0to turn OFF, or 1to turn ON
Hear TRIPLE beeps.
3. To verify the condition (ON/OFF) of the Supervised Trunk mode, dial 5 7 and repeat step 2 above.
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

19 947180
5 8 SPECIFY ZONE MICROPHONE
This option allows you to specify that a zone microphone is attached to the Attendant Access interface.
When the Zone Microphone option is enabled (ON), the controller will wait for a zone to be selected from
the microphone keypad before it makes a page. When disabled (OFF), the controller reverts to its normal
(All Call) operation.
1. Dial 5 8 to select this option
Hear a DOUBLE beep.
2. Dial 0to turn OFF, or 1 to turn ON
Hear TRIPLE beeps.
3. To verify the condition (OFF/ON) of the Zone Microphone option, dial 59and repeat step 2 above.
GENERAL ZONE AND ZONE GROUP CONFIGURATIONS
General Zone and Zone Group Configurations are options that apply to selected zones or groups, not to
the entire system. The steps following Copy Command, describe each option.
1 2 COPY COMMAND
The COPY command can be used to copy the configuration of a zone that has already been optioned, to
one or more additional zones. This saves re-entering the same parameters over again, to duplicate the
parameters of an existing zone.
1. Dial 1 2 to activate COPY command.
Hear a DOUBLE beep tone.
2. Enter the zone number that you wish to copy from (i.e., 01).
Hear DOUBLE beep tone.
3. Enter the zone number of the beginning of the range of zones you wish to copy to.
Hear a DOUBLE beep tone.
4. Enter the zone number of the END of the zone range to be copied to.
Hear a TRIPLE beep tone.
Note: Program the Controller using the physical zone number.
For example, to copy the parameters of zone 01 to all other zones, the range zone 02 to 56 would be
entered in this step and the next. To copy to a single zone (for example, 02) enter that zone number as
both the beginning and the end of the range (02 to 02). In this step, enter only the beginning zone of the
zone range.
6 0 ZONE MAP OPTION -- ASSIGNING ALIAS NUMBERS
Note: Before doing this option, you MUST do “Define Length of ALIAS Numbers” (see Step 3).
Zone Map permits you to assign the dialing code, called the ALIAS zone code, that you will dial to
access a particular zone by telephone (i.e., instead of dialing 02 to make a page, you could dial 2202).
The factory default is NONE: no ALIAS numbers are pre-programmed. The zones are identified by their
2-digit Physical Zone Codes (01 thru 56 and groups 81-88) as the default condition.
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com

20 947180
Digit string length for an ALIAS code can be 3 or 4 digits, but all ALIAS codes must have the same num-
ber of digits. (Refer to Step 3) The ∗and #digits are not applicable digits for zone ALIAS numbers.
Note: If ALIAS numbers are enabled, you MUST use them for programming from now on. When an
ALIAS number for a zone is changed, all the previous zone options for that zone will be transferred to the
new zone number.
Refer to your own Zone Map and the Example Zone Map at the end of this programming section.
1. Dial 6 0 to select this option.
Hear a DOUBLE beep.
2. Enter the 2-digit PHYSICAL zone/group code, of the zone to be given an ALIAS number.
Hear a DOUBLE beep.
3. Enter the ALIAS zone/group number you have chosen.
Hear TRIPLE beeps.
4. To verify the assignment of an ALIAS to a selected zone or group, dial 6 1 and repeat steps 2 and 3
above.
6 2 TYPE OF ZONE: INPUT OR OUTPUT
The choices here are INPUT #1, INPUT #2, and OUTPUT. Be sure the manually selectable Zone Option
switch on the rear of the Controller or Zone Expansion Unit is set to match the type of zone selected
(input or output). Input #1 would be used for an emergency alert, say a connection to your alarm system.
Input #2 would be a lower priority, say a doorbell input.
Note: The INPUT #1 option must only be assigned to physical zones 1 through 8 (on the Controller).
The factory default is OUTPUT (i.e., all zones are output type, by default).
1. Dial 6 2 to select this option.
Hear a DOUBLE beep.
2. Enter the number of the zone or zone group to be optioned. Use ALIAS numbers, if optioned.
Otherwise, use Physical zone/group numbers.
Hear a DOUBLE beep.
3. Press 0 to designate the zone as OUTPUT
Press 1to designate it as INPUT #1, or
Press 2 to designate it as INPUT #2.
Hear TRIPLE beeps.
4. To verify the zone type assignment, dial 6 3 and repeat steps 2 and 3 above.
Technical Manuals Online! - http://www.tech-man.comTechnical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Other manuals for PagePac Plus V-5323100
1
This manual suits for next models
1
Table of contents
Other Valcom Controllers manuals

Valcom
Valcom V-9932 User manual

Valcom
Valcom PagePac V-5335100 User manual

Valcom
Valcom V-1092 User manual

Valcom
Valcom V-2000A User manual

Valcom
Valcom PagePac Plus V-5323100 User manual

Valcom
Valcom Pagepac Plus V-5335621 User manual

Valcom
Valcom V-1092 User manual

Valcom
Valcom V-1092 User manual

Valcom
Valcom VL-9998RM User manual

Valcom
Valcom V-1092 User manual