ACTpro 1520e/1500e Door Controller
Installation and Operating Instructions
Installations-undBetriebsanleitung(DE)
Installations-ogbetjeningsvejledning(DA)
Instruccionesdeinstalaciónyfuncionamiento(ES)
Instructionsd’installationetd’utilisation(FR)
Istruzionidiinstallazioneefunzionamento(IT)
Installations-ochdriftsinstruktioner(SV)

Dataanddesignsubjecttochangewithoutnotice./Supplysubjecttoavailability.
©2018CopyrightbyVanderbiltInternational(IRL)Ltd.
Wereserveallrightsinthisdocumentandinthesubjectthereof.Byacceptanceofthedocumenttherecipientacknowledgestheserightsand
undertakesnottopublishthedocumentnorthesubjectthereofinfullorinpart,nortomakethemavailabletoanythirdpartywithoutourprior
expresswrittenauthorization,nortouseitforanypurposeotherthanforwhichitwasdeliveredtohim.
Hereby,VanderbiltInternational(IRL)LtddeclaresthatthisequipmenttypeisincompliancewiththefollowingEUDirectivesforCEmarking:
•Directive2014/30/EU(ElectromagneticCompatibilityDirective)
•Directive2014/35/EU(LowVoltageDirective)
•Directive2011/65/EU(RestrictionoftheuseofcertainhazardoussubstancesDirective)
ThefulltextoftheEUdeclarationofconformityisavailableat:http://van.fyi?Link=doc01
DatenundDesignkönnenohnevorherigeAnkündigunggeändertwerden./LieferungjenachVerfügbarkeit.
©2018CopyrightbyVanderbiltInternational(IRL)Ltd.
AlleRechteandiesemDokumentunddemdarinbehandeltenThemavorbehalten.DerEmpfängererkenntdieseRechteanundwirddieses
DokumentohneunserevorherigeschriftlicheGenehmigungkeinemDrittenganzoderteilweisezugänglichmachenoderfüreinenanderenals
denvorgesehenenZweckverwenden.
HiermiterklärtVanderbiltInternational(IRL)AG,dassdiesesgerätetypsdenAnforderungendenfolgendenEU-RichtlinienfürdieCE-
Kennzeichnungentspricht:
•Richtlinie2014/30/EU(RichtlinieüberelektromagnetischeVerträglichkeit
•Richtlinie2014/35/EU(Niederspannungsrichtlinie)
•Richtlinie2011/65/EU(BeschränkungderVerwendungbestimmtergefährlicherStoffe)
DervollständigeTextderEU-Konformitätserklärungstehtunterhttp://van.fyi?Link=doc01zurVerfügung.
Dataogdesignkanbliveændretudenvarsel./Tilføjsubjekttiltilgængelighed.
©2018CopyrightbyVanderbiltInternational(IRL)Ltd.
Viforbeholderosallerettighedertildettedokumentogdetsindhold.Vedataccepteredokumentetanerkendermodtagerendisserettighederog
forpligtersigtilikkeatoffentliggøredokumentetellerdetsemneisinhelhedellerdelvistelleratstilledemtilrådighedfortredjemanduden
forudgåendeudtrykkeligskriftligtilladelsefraoselleratbrugedettilandreformålenddet,dervargældende,dadetblevleverettildenne.
HermederklærerVanderbiltInternational(IRL)Ltd,atdenneudstyrstypeerioverensstemmelsemedfølgendeEU-direktiverforCE-
mærkning:
•Direktiv2014/30/EU(direktivetomelektromagnetiskkompatibilitet)
•Direktiv2014/35/EU(lavspændingsdirektivet)
•Direktiv2011/65/EU(begrænsningafanvendelsenafvissefarligestoffer)
DenfuldeordlydafEU-overensstemmelseserklæringenertilgængeligpå:http://van.fyi?Link=doc01
Losdatosyeldiseñosepuedenmodificarsinprevioaviso./Ofertasujetaadisponibilidad.
©2018CopyrightbyVanderbiltInternational(IRL)Ltd.
Nosreservamostodoslosderechosdeestedocumentoyelobjetodelmismo.Alaceptareldocumento,eldestinatarioreconoceestosderechos
ysecomprometeanopublicareldocumentooelobjetodelmismoensutotalidadoenparte,niponerloadisposicióndetercerossinnuestra
autorizaciónexpresapreviayporescrito,niutilizarloparaningúnotrofinquenoseaelprevistoenlaentregadelmismo.
Porlapresente,VanderbiltInternational(IRL)LtddeclaraqueestetipodeequipocumplecontodaslasdirectivasdelaUErelevantesparael
marcadoCE.
•Directiva2014/30/UE(directivadecompatibilidadelectromagnética)
•Directiva2014/35/UE(directivasobrebajatensión)
•Directiva2011/65/UE(directivasobrerestriccionesalautilizacióndedeterminadassustanciaspeligrosas)
EltextocompletodeladeclaraciónUEdeconformidadestádisponibleenhttp://van.fyi?Link=doc01
Lesdonnéesetlaconceptionpeuventêtremodifiéessanspréavis./Lafournitureduproduitdépenddesadisponibilité.
©2018CopyrightbyVanderbiltInternational(IRL)Ltd.
Nousnousréservonstouslesdroitssurcedocumentetsurl'objetdontiltraite.Parl'acceptationdecedocument,l'utilisateurreconnaîtcesdroits
etacceptedenepasreproduirenidiffuserledocumentoudespartiesdecedocumentàdestierssansnotreaccordpréalableécritetdenepas
l'utiliseràd'autresfinsquecellespourlesquellesilaétéfourni.
Parlaprésente,VanderbiltInternational(IRL)Ltddéclarequeletyped'équipementconsidéréestenconformitéavectouteslesdirectivesUE
applicablesrelativesaumarquageCE.
•Directive2014/30/UE(directivecompatibilitéélectromagnétique(CEM))
•Directive2014/35/UE(directivebassetension)
•Directive2011/65/UE(directiverelativeàlalimitationdel’utilisationdecertainessubstancesdangereuses)
Letexteintégraldeladéclarationdeconformitéauxdirectivesdel'Unioneuropéenneestdisponibleàhttp://van.fyi?Link=doc01
Datiedesignsoggettiamodifichesenzapreavviso.Forniturasoggettaalladisponibilitàdelprodotto.
©2018CopyrightbyVanderbiltInternational(IRL)Ltd.
Ilproduttoresiriservatuttiidirittisullapresentedocumentazioneesugliargomentitrattati.Accettandolapresentedocumentazionel'utente
riconosceeprendeattoditalidirittiesiimpegnaanonpubblicare,intotooinparte,ilpresentedocumento,négliargomentiivitrattati,nédi

renderlidisponibiliaterzeparti,senzapreviaautorizzazioneesplicitainformascritta,nédiutilizzaretaledocumentazioneperaltriscopiche
esulanodaifinisecondoiqualiladocumentazioneèstataconsegnataall'utentestesso.
ConlapresenteVanderbiltInternational(IRL)LtddichiarachequestotipodiapparecchioèconformeatuttelerelativeDirettiveUEperla
marcaturaCE.
•Direttiva2014/30/UE(Direttivasullacompatibilitàelettromagnetica)
•Direttiva2014/35/UE(Direttivasullabassatensione)
•Direttiva2011/65/UE(Direttivasullarestrizionedell’usodideterminatesostanzepericolose)
IltestocompletodelladichiarazionediconformitàUEèdisponibilepressohttp://van.fyi?Link=doc01
Dataogdesignkanbliveændretudenvarsel./Tilføjsubjekttiltilgængelighed.
©2018CopyrightbyVanderbiltInternational(IRL)Ltd.
Viforbeholderosallerettighedertildettedokumentogdetsindhold.Vedataccepteredokumentetanerkendermodtagerendisserettighederog
forpligtersigtilikkeatoffentliggøredokumentetellerdetsemneisinhelhedellerdelvistelleratstilledemtilrådighedfortredjemanduden
forudgåendeudtrykkeligskriftligtilladelsefraoselleratbrugedettilandreformålenddet,dervargældende,dadetblevleverettildenne.
HärmedförsäkrarVanderbiltInternational(IRL)LtdattdennatypavöverensstämmermedallarelevantaEG-direktivförCE-märkning.
•Direktiv2014/30/EG(Direktivomelektromagnetiskkompatibilitet)
•Direktiv2014/35/EG(Direktivomlågspänning)
•Direktiv2011/65/EG(Direktivombegränsningavanvändningavvissafarligaämnen)
DenfullständigatextenförEG-försäkranomöverensstämmelsefinnspåhttp://van.fyi?Link=doc01

Table of Contents
1 Overview 5
1.1Technicalspecification 5
1.1.1ACTpro1520eelectricalspecification 5
1.1.2ACTpro1520ePSUoutputvoltage 6
1.2Monitoring 6
1.3ACTpro1520ePSULEDindicators 6
2 Installation 7
2.1Mounting 7
2.2ACTpro1520epowersupply 7
2.2.1MainspowerupfortheACTpro1520e 7
2.2.2BatteryinsertionfortheACTpro1520e 7
2.2.3ACTPro1520ePSUpowerbudget 7
2.3ACTpro1500epowersupply 8
2.4TypicalwiringofACTpro1520e/1500e 9
2.4.1Wiringexitreaders 9
3 Defaulting the Controller and IP Address Configuration 10
3.1FactorydefaulttheController(DIPswitch2) 10
3.2DHCP/staticIPaddressing(DIPswitch1) 10
3.3DefaultingthestaticIPaddress 11
3.4ChangingstaticIPaddressontheACTproController 11
4 ACTpro 1520e/1500e Door Controller Status Indicators 12
© Vanderbilt 2018 EN– 4 A-100440
01.02.2018

1 Overview
ThisguidedescribestheinstallationoftheACTpro1520eand1500econtrollers.
TheACTpro1500eControllerisasingledoorIPcontrollerthatrequiresanexternal12Vor24Vpower
supply.
TheACTpro1520eControllerisasingledoorIPcontrollerwitha12VDC2APSU.
Seealso:
lhttp://van.fyi/url/ACTpro1520e
1.1 Technical specification
Technical Details
Voltage Range (Controller) 11–24VDC
Current Consumption (Controller) 350mA(Max)
Dimensions (1520e Controller) 235mmx255mmx85mm
Weight (1520e Controller) 950g
Dimensions (1500e Controller) 235mmx165mmx55mm
Weight (1500e Controller) 465g
Relay contacting rating Mainrelay5A/50VAC,AUXrelay1A/
50VAC
Operating temperature -10to+50°C
Indoor use only
1.1.1 ACTpro 1520e electrical specification
Thepowersupplyiscapableofdelivering2A.1.5Aisavailableforexternallocksandreaders,0.5Aforthe
PCBandbattery.
Electrical Specification
Input Voltage 230VAC+/-10%
Frequency 47-53Hz
Input Fuse 625mA250Vanti-surgefuse
Output Voltage 13.65V(+/-5%)
Max Load 2A@25ºC
Electronic Output fuse Yes
Battery Current ~0.5Aforabatterydischargedto~10V
Battery Protections DeepDischarge/OverCharge/ReversePolarity
© Vanderbilt 2018 EN– 5 A-100440
01.02.2018

1.1.2 ACTpro 1520e PSU output voltage
Thepowersupplyprovidestwo12Voutputs.Oneispre-wiredtopowertheACTController.Thesecondis
availabletopowerlocksandreaders.
Thefullloadcurrentsharedbetweenthetwooutputs.ACTrecommendthatamaximum of 1.5Aisused
topowerlocksandreaders.Theremaining0.5Aisusedbythecontrollerandbatterycharging.Total
currentfrombothoutputsmustnotexceed2A.SeeACTPro 1520e PSU power budgetonpage7.
1.2 Monitoring
AllfaultsincludingMainsPresentandTamperarereportedontheACTEnterprisesoftwareandviathe
webbrowserontheACTpro1520eand1500econtroller.
Mains
present
FortheACTpro1520eController,thePSUMAINSPRESENToutputispre-wiredtotheMAINS
PRESENTinput.
Output
Voltage
FortheACTpro1520eController,thePSUoutputvoltagelevelisreportedtotheACTEnterprise
softwareandonthewebbrowser.
Tamper Theenclosurelidistampermonitored.
1.3 ACTpro 1520e PSU LED indicators
Green – AC
OK IndicatesthattheACMainsiswithinspecification.
Amber – ON
BATTERY Indicatesthatthebatteryissupplyingtheoutputvoltage.
Red – FUSE
FAULT
Indicateselectronicoutputshutdownfuseisactiveandthatnopowerisbeingsuppliedtotheload.
ThemaximumcurrentthatthePSUcanguaranteeis1.5Aplus0.5Aforbatterycharging.Beyond
thisthefusewilltripandtheLEDwillstayonuntiltheloadisfullydisconnected.
Oncetheloadhasbeendisconnected,removedevicestoreducethecurrentdemandbelow1.5A.
Itisimportanttocalculatethepowerbudgetadequately.SeeInstallationonpage7formore
information.
ACTpro 1520e/1500e Door Controller – Installation and Operating Instructions Overview
© Vanderbilt 2018 EN– 6 A-100440
01.02.2018

2 Installation
TheACTpro1520e/1500eControllersareforindoorinstallationonlyandmustbeinstalledaspermanently
connectedequipment.
Anexternalmainsdisconnectdevicemustbefitted.Beforeinstallation,ensurethatthemainssupplyto
thecontrollerisdisconnected.
MainspowershouldbeconnectedtoACTproControllersbyalicensedelectricianinaccordancewith
local/nationalcodes.
2.1 Mounting
MounttheACTproControllerdirectlyontothewallwiththesuppliedscrews.
Thekeyedmountingholeshouldbescrewedfirsttothewalltoaidthemounting.
Theunitshouldbeinstalledinaventilatedareathatallowsforaccessibilityafterinstallation.
2.2 ACTpro 1520e power supply
2.2.1 Mains power up for the ACTpro 1520e
1. Attachacorrectlyratedmainscableandfastenusingthecabletie.
2. Useanapprovedexternalmainsdisconnectdevice.
3. Applymainspower.
4. Checkthatthe‘ACOK’LEDisonandmeasurethe+12Voutput.
2.2.2 Battery insertion for the ACTpro 1520e
1. Disconnectthemains.
2. Ensurethebatteryhasenoughchargetosupplytheload.
3. Connecttheredbatteryleadtothe“+”batteryterminalandtheblackleadtothe“–”terminal.
4. Applythemainspowerandcheckthatthe“ACOK”GreenLEDisilluminated.
5. Removethemainspowerandcheckthatthe“ONBATTERY”AmberLEDisilluminated.Ifthe
AmberLEDisilluminatedthebatteryisnowsupplyingtheoutput.
6. Re-applythemainspower.The“ACOK”LEDwillilluminateandthe“ONBATTERY”LEDwill
extinguish.
2.2.3 ACTPro 1520e PSU power budget
TheACTpro1520eincludesanACT12VDC2Apowersupplyunit.
0.5Aofthe2Aoutputcurrentisusedtopowerthecontrollerandsupplythebatteryrechargecurrent.A
completeaccesscontrolsystemwillrequirereadersandalockmechanism,allofwhichwillrequirepower.
© Vanderbilt 2018 EN– 7 A-100440
01.02.2018

1.5Aisavailabletopowerlocksandreaders.
Thefollowingtableshouldbeusedforcalculatingthepowerbudget.
ACTpro reader (1030/1040/1050/1060) 100mA
ACTPro MIFARE reader (1030/1040/1050) 100mA
Typical Mag Lock (consult your supplier) 800mA
Example:Powerbudgetofatypicalsingledoorreadin/outinstallation.
Total Current Available 2000mA
ACTpro Controller and Battery Recharge 500mA
ACT Reader X 2 200mA
Typical Mag Lock 800mA
Total Consumption 1500mA
Spare Capacity 500mA
Seealso:
lTechnical specificationonpage5
2.3 ACTpro 1500e power supply
TheACTpro1500erequiresanexternal12VDCor24VDCpowersupply.Thesupplyshouldbeconnected
tothe+12/24VDCand0V/GNDconnections.
ACTpro 1520e/1500e Door Controller – Installation and Operating Instructions Installation
© Vanderbilt 2018 EN– 8 A-100440
01.02.2018

2.4 Typical wiring of ACTpro 1520e/1500e
Label Description Label Description
A Doorcontact,normallyclosed F ACTreaderwirecolourcoding
B Pushtoexit,normallyopen G Ethernet:RJ45
Note:AllIPdevicemusthaveavalidIPAddress.
C Doornetworks H
Important:Placevaristoracrossalllockterminals.
Note:DiagramshowsnormallyenergisedMagnetic
Lock.
D Controllernetwork J Breakglassunit(doublepole)
EBreakglassmonitoring,normally
closed
2.4.1 Wiring exit readers
Forclockanddatareaders,wireexitreadersinparallelbutleavethesenselineunconnected.
ForWiegandreaders,wiretheDATA0oftheexitreadertoSENSEontheACTpro1520e.
Maxlength:100mwith12VDC
Cable:8corescreenedBelden9504orequivalent
ACTpro 1520e/1500e Door Controller – Installation and Operating Instructions Installation
© Vanderbilt 2018 EN– 9 A-100440
01.02.2018

3 Defaulting the Controller and IP Address Configuration
TheACTpro1520e/1500ehavetwoDIPswitches.
lDIPswitch1:DHCP
EnablesDHCPorStaticIPaddressmode.
lDIPswitch2:DEFAULT
DefaultsthecontrollerortheStaticIPaddress.
3.1 Factory default the Controller (DIP switch 2)
TheACTproControllermaybedefaultedtofactorysettings.Thiswillcompletelyerasethecontroller
memory.AllinformationincludingcarddetailswillbeerasedandthestaticIPaddresswillberesetto
192.168.1.60.
TodefaulttheACTproController:
1. PowerdowntheACTproController.
2. SettheDEFAULTDIPswitch2toON.
3. HolddowntheTamperspring.
4. ApplypowertotheACTpro1520e/1500econtrollers.
5. Waitapproximately5seconds,untilthecontrollerconfirmsdefaultcompletedbysoundingthe
buzzer.
6. ReleasetheTamper.
7. PowerdowntheACTproController.
8. SettheDEFAULTDIPswitchtoOFF.
9. Re-applypower.
3.2 DHCP/static IP addressing (DIP switch 1)
TheACTproControllerisshippedwiththeDHCPenabledandcanbeconfiguredtoobtainanIPaddress
fromaDHCPserveroruseastaticIPaddress.
1. PowerdowntheACTproController.
2. SettheDIPswitchtoitsnewposition.
a. DHCPIPaddressing:MoveDIPswitch1toON
b. StaticIPaddressing:MoveDIPswitch1toOFF
Note:DefaultstaticIPaddressis192.168.1.60.
3. Re-applypowertotheboard.
© Vanderbilt 2018 EN– 10 A-100440
01.02.2018

3.3 Defaulting the static IP address
ThestaticIPaddresscanberesettothedefaultvalueof192.168.1.60.
1. PowerdowntheACTproController.
Ensurenothingisconnectedtothetamperinputterminalandthetamperspringis
notpressed,otherwisethefollowingstepswillfactorydefaultthecontrollerlosing
allinformation.
2. SettheDHCPDIPswitch1toOFF.
3. SettheDEFAULTDIPswitch2toON.
4. Re-applypower.
5. Waitapproximately5seconds,untilthecontrollerconfirmsdefaultcompletedbysoundingthe
buzzer.
6. Removepower.
7. SettheDEFAULTDIPswitch2toOFF.
8. Re-applypower.
Note:ThestaticIPaddresscanbechangedviathewebinterfaceorusingACTSoftware.
3.4 Changing static IP address on the ACTpro Controller
1. ConnectACTproControllertotheIPnetwork.
2. OpenawebbrowseronaPC(forexample,MicrosoftInternetExplorer,GoogleChrome,etc.).
3. Enterhttp://<NetBIOSaddress>,e.g.http://ACT1520E-07116
4. Logondetails:
Username:installer
Password:999999
5. ChooseCommunicationmenuandsetthefollowing:
lStatic IP Address
lNetwork Mask
lDefault Gateway
6. PressSave.
Note:UsethenewIPaddresswhenconnectingtothe
controller.
ACTpro 1520e/1500e Door Controller – Installation and Operating Instructions Defaulting the Controller and IP Address
Configuration
© Vanderbilt 2018 EN– 11 A-100440
01.02.2018

4 ACTpro 1520e/1500e Door Controller Status Indicators
StatusindicatorsappearonthefrontoftheACTpro1520e/1500eDoorController.
Themeaningofeachindicatorisdescribedbelow.
(A) Power / System Running
ThisindicatesthattheACTpro1520e/1500ehaspower.
(B) Communications
Constantilluminationindicatesthatallenableddoorstationsareonline.
Flashingindicatesthatoneormoredoorstationsareoffline.
(C) Fault
Illuminatestoindicateafaultonthesystem.
Possiblecausesare:
lTamperopen:ACTproControllerhousingisnotclosed.
lBreakGlass:ACTproControllersprovideamethodtomonitoranEmergencybreakglassswitchviathe
B/GLinput.ThefaultLEDwillilluminateiftheEmergencybreakglassswitchisactivated.
lMainsFault:ACTpro1500eControllerwillacceptamainspresentsignalfromaPSU(pre-wiredon
ACTpro1520e).ThisiswiredintoMAINSPRESENTinputonthePCB.WhenthePSUhasnomains
supplythefaultisactive.
lDoorStationoffline:WhenoneormoreenableddoorstationsarenotcommunicatingwiththeACTpro
ControllertheFaultLEDilluminatesandtheappropriatenetworkgreenLEDonthePCBwillflash.
lLowSupplyVoltage:Whenvoltagetothe+12Vterminalislessthan+9V.
lFuseBlown:The+12VoutputontheREADERterminalsiscurrentlimitedtoprovideshortcircuit
protection.TheFaultLEDwillilluminateiftoomuchcurrentisdrawnfromthisconnection.
© Vanderbilt 2018 EN– 12 A-100440
01.02.2018

Inhalt
1 Überblick 14
1.1TechnischeSpezifikationen 14
1.1.1ElektrischeSpezifikationenderACTpro1520e 14
1.1.2AusgangsspannungdesNetzteilsderACTpro1520e 15
1.2Überwachung 15
1.3LED-AnzeigendesNetzteilsderACTpro1520e 15
2 Installation 16
2.1Montage 16
2.2ACTpro1520e-Stromversorgung 16
2.2.1AnschlussderNetzstromversorgungandieACTpro1520e 16
2.2.2EinlegendesAkkusindieACTpro1520e 16
2.2.3DasLeistungsbudgetdesNetzteilsderACTpro1520e 17
2.3ACTpro1500eStromversorgung 17
2.4TypischeVerdrahtungderACTpro1520e/1500e 18
2.4.1VerkabelungAustrittsleser 19
3 Zurücksetzen der Steuerung auf die Werkseinstellungen und Konfiguration der IP-Adresse 20
3.1SetztdieSteuerungaufdieWerkseinstellungenzurück(DIP-Schalter2) 20
3.2DHCP-/StatischeIP-Adresse(DIP-Schalter1) 20
3.3ZurücksetzenderstatischenIP-Adresse 21
3.4ÄndernderstatischenIP-AdresseanderACTpro-Steuerung 21
4 ACTpro 1520e/1500e Türsteuerung Statusanzeigen 23
© Vanderbilt 2018 DE – 13 A-100440
01.02.2018

1 Überblick
IndervorliegendenAnleitungwirddieInstallationderSteuerungenACTpro1520eund1500ebeschrieben.
DieSteuerungACTpro1500eisteineIP-Einzeltürsteuerung,dieeineexterneStromversorgungmit12oder
24Verfordert.
DieSteuerungACTpro1520eisteineIP-EinzeltürsteuerungmiteinemNetzteilvon12VDC2A.
Sieheauch:
lhttp://van.fyi?Link=ACTpro1520e
1.1 Technische Spezifikationen
Technische Details
Spannungsbereich (Steuerung) 11–24VDC
Stromverbrauch (Steuerung) 350mA(max.)
Abmessungen (1520e Steuerung) 235x255x85mm
Gewicht (1520e Steuerung) 950g
Abmessungen (1500e Steuerung) 235x165x55mm
Gewicht (1500e Steuerung) 465g
Relais-Kontaktrate Hauptrelais5A/50VAC,Hilfsrelais1A/
50VAC
Betriebstemperatur -10bis+50°C
Ausschließlich für den Einsatz in Innenräumen
1.1.1 Elektrische Spezifikationen der ACTpro 1520e
DieStromversorgunghateineStromstärkevon2A.FürexterneSchlösserundLesegerätesind1,5A
verfügbar,fürdieZentrale-LeiterplatteunddenAkku0,5A.
Elektrische Spezifikation
Eingangsspannung 230VCA+/-10%
Überwachung 47-53Hz
Sicherung Eingang 625mA250VSicherungenmitExplosionsschutz
Ausgangsspannung 13,65V(+/-5%)
Max. Last 2Abei25ºC
Sicherung elektronische Leistung Ja
Akkuspannung ~0,5AbeieinerBatterieentladungbis~10V
Schutzvorrichtungen Batterie Tiefentladung/Überladung/UmgekehrtePolarität
© Vanderbilt 2018 DE – 14 A-100440
01.02.2018

1.1.2 Ausgangsspannung des Netzteils der ACTpro 1520e
DieStromversorgungverfügtüberzwei12-V-Ausgänge.EinAusgangistfürdenBetriebderACT-
Steuerungvorgesehen.ÜberdenzweitenAusgangwerdenSchlösserundLesegerätebetrieben.
DeraufdenbeidenAusgängenliegendeLaststrom.ACTsiehtfürdenBetriebvonSchlössernund
LesegeräteneineStromstärkevonmaximal 1,5 Avor.Dierestlichen0,5AwerdenfürdieSteuerungund
dasAufladendesAkkusverwendet.DieGesamtstromstärkederbeidenAusgängedarf2Anicht
überschreiten.SieheDas Leistungsbudget des Netzteils der ACTpro 1520eaufSeite17.
1.2 Überwachung
AlleFehler,u.a.aufMainsPresent(Netzanschluss)undTamper(Sabotageschutz),werdeninderACT
Enterprise-SoftwareundüberdenWebbrowseraufdenSteuerungenACTpro1520eund1500egemeldet.
Mains Present
(Netzanschluss)
BeiderSteuerungACTpro1520eistderAusgangPSUMAINSPRESENT
(NetzanschlussamNetzteil)mitdemAusgangMAINSPRESENT(Netzanschluss)
vorverdrahtet.
Ausgangsspannung BeiderSteuerungACTpro1520ewirddieaufdemNetzteilliegendeAusgangsspannung
andieACTEnterprise-SoftwareundandenWebbrowsergemeldet.
Sabotageschutz DerGehäusedeckelverfügtübereinenSabotageschutz.
1.3 LED-Anzeigen des Netzteils der ACTpro 1520e
Grün – AC OK
(NETZSTROM OK)
Zeigtan,dassdieNetzstromversorgunginnerhalbdervorgesehenenSpezifikation
liegt.
Gelb – ON BATTERY
(ÜÜBER AKKU) Zeigtan,dassdieSteuerungaufAkkubetriebumgeschaltethat.
Rot – FUSE FAULT
(SICHERUNGSFEHLER)
Zeigtan,dassdieAusgangssicherungaktivistunddasGerätnichtmitStrom
versorgtwird.
DasNetzteilkanneinemaximaleStromstärkevon1,5Aplus0,5AfürdasAufladen
desAkkusgewährleisten.ÜberdiesemWertwirddieSicherungausgelöst,unddie
LEDleuchtetsolange,bisderLaststromkomplettgetrenntwird.
NachdemTrennendesLaststromsGeräteentfernen,umdenStromverbrauchunter
1,5Azusenken.
DieLeistungsanforderungenmüssenunbedingtkorrektberechnetwerden.Siehe
InstallationaufSeite16zuweiterenInformation.
ACTpro 1520e/1500e Türsteuerung – Installations- und Betriebsanleitung Überblick
© Vanderbilt 2018 DE – 15 A-100440
01.02.2018

2 Installation
DieSteuerelementeACTpro1520e/1500esindausschließlichfürdieInstallationinInnenräumengedacht
undmüssenalsfestangeschlosseneGeräteverbautwerden.
SiemussmiteinemexternenNetztrenngerätverbundensein.VorderInstallationsicherstellen,dassdie
NetzstromversorgungzurSteuerungunterbrochenist.
DieNetzstromversorgungmussvoneinemkompetentenElektrikerdenlokalen/nationalenVorschriften
gemäßmitdenACTpro-Steuerungenverbundenwerden.
2.1 Montage
DieACTpro-SteuerungmitdenbeiliegendenSchraubendirektanderWandanbringen.
DasschlüsselförmigeMontagelochsolltezuerstanderWandbefestigtwerden,umdieweitereInstallation
zuerleichtern.
DieSteuerungmussineinemgutbelüftetenBereichinstalliertwerden,dernachderInstallationjederzeit
gutzugänglichist.
2.2 ACTpro 1520e-Stromversorgung
2.2.1 Anschluss der Netzstromversorgung an die ACTpro 1520e
1. EingeeignetesNetzkabelanschließenundmitdemKabelbinderfestziehen.
2. EinzulässigesexternesNetztrenngerätanbringen.
3. DieNetzstromversorgungeinschalten.
4. Daraufachten,dassdieLED„ACOK“aufleuchtetundeineLeistungvon+12Vverzeichnet.
2.2.2 Einlegen des Akkus in die ACTpro 1520e
1. DieNetzstromversorgungtrennen.
2. Daraufachten,dassderAkkuausreichendaufgeladenist.
3. DasroteAkkukabelmitdemPluspolderAkkuklemmeunddasschwarzeAkkukabelmitdem
Minuspolverbinden.
4. DieNetzstromversorgungwiedereinschaltenunddaraufachten,dassdiegrüneLED„ACOK“
(NETZSTROMOK)leuchtet.
5. DieNetzstromversorgungabschaltenundsicherstellen,dassdiegelbeLED„ONBATTERY“
(ÜBERAKKU)leuchtet.LeuchtetdiegelbeLED,kommtdieStromversorgungnunüberdenAkku.
6. DieNetzstromversorgungwiedereinschalten.DieLED„ACOK“(NETZSTROMOK)leuchtetauf,
unddieLED„ONBATTERY“(ÜBERAKKU)erlischt.
© Vanderbilt 2018 DE – 16 A-100440
01.02.2018

2.2.3 Das Leistungsbudget des Netzteils der ACTpro 1520e
DerLieferumfangderACTpro1520eumfassteinNetzteilACT12VDC2A.
Mit0,5AdesAusgangsstromsvon2AwerdendieSteuerungbetriebenundderAkkuaufgeladen.Ein
vollständigesZutrittskontrollsystemumfasstLesegeräteundeinenSchließmechanismus,dieallesamtmit
Stromversorgtwerdenmüssen.FürdenBetriebderSchlösserundLesegerätesind1,5Avorgesehen.
DiefolgendeTabellesolltezurBerechnungdesLeistungsbudgetsherangezogenwerden.
ACTpro-Lesegerät (1030/1040/1050/1060) 100mA
ACTPro MIFARE-Lesegerät (1030/1040/1050) 100mA
Typisches Magnetschloss (genaue Daten erhalten Sie beim Händler) 800mA
Beispiel:LeistungsbudgeteinertypischenInstallationzumEin-undAuslesenbeiEinzeltüren.
Verfügbarer Gesamtstrom 2000mA
ACTpro-Steuerung und Aufladen des Akkus 500mA
ACT-Lesegerät X 2 200mA
Typisches Magnetschloss 800mA
Gesamtverbrauch 1500mA
Reservekapazität 500mA
Sieheauch:
lTechnische SpezifikationenaufSeite14
2.3 ACTpro 1500e Stromversorgung
DieACTpro1500ebenötigteineexterneStromversorgungvon12VDCoder24VDC.Die
StromversorgungmussüberdieAnschlüsse+12/24VDCund0V/GND(Erdung)verbundenwerden.
ACTpro 1520e/1500e Türsteuerung – Installations- und Betriebsanleitung Installation
© Vanderbilt 2018 DE – 17 A-100440
01.02.2018

2.4 Typische Verdrahtung der ACTpro 1520e/1500e
Etikett Beschreibung Etikett Beschreibung
ATürkontakt,normalerweise
geschlossen F FarbcodierungderKabeldesACT-Lesegeräts
BZumVerlassendrücken,
normalerweisegeöffnet G
Ethernet:RJ45
Hinweis:SämtlicheIP-Gerätemüssenübereine
gültigeIP-Adresseverfügen.
ACTpro 1520e/1500e Türsteuerung – Installations- und Betriebsanleitung Installation
© Vanderbilt 2018 DE – 18 A-100440
01.02.2018

Etikett Beschreibung Etikett Beschreibung
C Türnetzwerke H
Achtung:AlleSchlossklemmenmüssenmiteinem
Varistorgeschütztwerden.
Hinweis:DasDiagrammzeigteinnormalerweisemit
StromversorgtesMagnetschloss.
D NetzwerkderSteuerung J Glasbruchmelder(zweipolig)
EGlasbruchüberwachung,
normalerweisegeschlossen
2.4.1 Verkabelung Austrittsleser
BeiLesegerätenmitZeitstempelformatmüssendieAustrittsleserparallelgeschaltetwerden,dieSense-
Leitungdarfjedochnichtverbundenwerden.
BeiWiegand-LesegerätenmussDATA0desAustrittslesersmitSENSEanderACTpro1520everbunden
werden.
Max.Länge:100mmit12VDC
Kabel:Geschirmtes8-Core-KabelBelden9504odergleichwertig
ACTpro 1520e/1500e Türsteuerung – Installations- und Betriebsanleitung Installation
© Vanderbilt 2018 DE – 19 A-100440
01.02.2018

3 Zurücksetzen der Steuerung auf die Werkseinstellungen
und Konfiguration der IP-Adresse
DieACTpro1520e/1500eistmitzweiDIP-Schalternausgestattet.
lDIP-Schalter1:DHCP
AktiviertDHCPodereinestatischeIP-Adresse.
lDIP-Schalter2:DEFAULT
SetztdieSteuerungaufdiestatischeIP-Adressezurück.
3.1 Setzt die Steuerung auf die Werkseinstellungen zurück (DIP-Schal-
ter 2)
DieACTpro-SteuerungkannaufdieWerkseinstellungenzurückgesetztwerden.Dadurchwirdder
speicherderSteuerungkomplettgelöscht.SämtlicheDaten,wieKartendetails,werdengelöscht,unddie
statischeIP-Adressewirdauf192.168.1.60zurückgesetzt.
SokanndieACTpro-SteuerungaufdieWerkseinstellungenzurückgesetztwerden:
1. DieACTpro-Steuerungabschalten.
2. DenDIP-Schalter2DEFAULTaufON(EIN)stellen.
3. DenSabotageschaltergedrückthalten.
4. DieStromversorgungzurACTpro1520e/1500ewiedereinschalten.
5. Etwa5Sekundenwarten,bisdieSteuerungmiteinemTondesSummersbestätigt,dassdie
Werkseinstellungenwiederhergestelltwordensind.
6. DenSabotageschalterloslassen.
7. DieACTpro-Steuerungabschalten.
8. DenDIP-SchalterDEFAULTaufOFF(AUS)setzen.
9. DenNetzstromwiedereinschalten.
3.2 DHCP-/Statische IP-Adresse (DIP-Schalter 1)
DieACTpro-SteuerungwirdmitaktiviertemDHCPverschicktundkannsokonfiguriertwerden,dasssie
eineIP-AdressevoneinemDHCP-ServerbeziehtodereinestatischeIP-Adresseverwendet.
1. DieACTpro-Steuerungabschalten.
2. DenDIP-SchalterindieneuePositionbringen.
a. DHCP-IP-Adresse:DIP-Schalter1aufON(EIN)setzen.
b. StatischeIP-Adresse:DIP-Schalter1aufOFF(AUS)setzen.
© Vanderbilt 2018 DE – 20 A-100440
01.02.2018
This manual suits for next models
1
Table of contents
Languages:
Other Vanderbilt Controllers manuals

Vanderbilt
Vanderbilt ACTpro-100 User manual

Vanderbilt
Vanderbilt lite blue User manual

Vanderbilt
Vanderbilt ACT365-ACU User manual

Vanderbilt
Vanderbilt ACTpro-1002A User manual

Vanderbilt
Vanderbilt ACTpro-1500 User manual

Vanderbilt
Vanderbilt ACT365 VCU User manual

Vanderbilt
Vanderbilt ACT365 VCU User manual
Popular Controllers manuals by other brands

TIE
TIE AMBITECH BRAKE-PAK Installation & setup instructions

Autopilot
Autopilot APCETHD manual

HomeMatic
HomeMatic HmIP-FAL230-C6 Installation instructions and operating manual

Texmate
Texmate Tiger 320 Series manual

eltherm
eltherm ELTC-MV2 Operation manual

VF
VF OSMOBIL BOX Translation of the original operating instructions