Velocity VDOT-STB-RL User manual

GLT-299-7-9 Rev. 0
Mar 23, 2018
1
Instruction Manual
VDOT-STB-RL
Relay Base
Before Installation
Please read these instructions carefully and keep for future reference.
The information in this document is subject to change without notice. For updates please refer to our website.
Note: Follow the requirements for the installation of the products in accordance with the Specifications. Otherwise
it may cause damage to equipment.
Note: Do not install the product in any location where oil, dust, iron powder, chemicals, or hydrogen sulphide may
occur or affect the product. It may cause damage to equipment.
Section 1 – INTRODUCTION
VDOT-STB-RL is a detector base with relay output for use with Zeta Control Panel series, which is designed for
use with an addressable detector. When a detector is in alarm condition, the base receives a control signal from
the detector, which has the relay operate. The rating of contact is DC30V/1A.
Section 2 – TERMINALS
VDOT-STB-RL base is supplied with 2 terminals as standard, along with a relay output terminal block of C form
contact.
The terminals of VDOT-STB-RL base are configured as follows:
-Terminal 1 = SLC positive
-Terminal 6 = SLC negative
-Terminal 3 = No connection
- Relay terminal block with N/O, N/C, and COM
! CAUTION
Do not use the products outside the rated power supply voltage range specified in
the Specifications. It may cause a fire or damage to equipment.
Do not disassemble, repair, or modify the products. It may cause a fire or electric
shock.
! CAUTION
! CAUTION
Make sure to turn the power off before commencing any wiring work. Otherwise
it may cause electric shock or damage to equipment.
ZETA ALARMS LIMITED
72-78 MORFA ROAD, SWANSEA, SA1 2EN
http://www.velocitydetection.com

GLT-299-7-9 Rev. 0
Mar 23, 2018
2
NO CONNECTION
N/O
N/C
COM
6
1
Figure 1: Position of terminals
Section 3 – DIMENSIONS
Figure 2: Dimension of VDOT-STB-RL
105(4.133)
22.5 (0.885)
mm(inch)

GLT-299-7-9 Rev. 0
Mar 23, 2018
3
Section 4 – DETECTOR MODELS
VDOT-STB-RL Base is available for use with the VDOT series detectors. It is important to use the correct detector
for each application. The standard range of detectors available is as follows:
Model
Description
Instruction Manual
VDOT-PY
Analog addressable photoelectric smoke detector
GLT-299-7-1
VDOT-PYH
Analog addressable combination photoelectric
smoke and heat detector 57℃(135°F) with 8.3℃
(15°F) rate of rise
GLT-299-7-4
VDOT-H2
Analog addressable heat detector 57℃(135°F)
with 8.3℃(15°F) rate of rise
GLT-299-7-2
VDOT-DPH
Analog addressable combination photoelectric
smoke (dual wave length) and heat detector 57℃
(135°F) with 8.3℃(15°F) rate of rise
GLT-299-7-5
Optional accessory
VDOT-ADP adapter: Use this adapter when VDOT-STB-RL is installed with a 4” square electrical box or 4”
octagonal electrical box. (Refer to “VDOT-ADP Instruction Manual” for details.)
Section 5 – INSTALLATION
The product must be installed in accordance with the applicable NFPA standards, local codes and jurisdictional
authorities. Failure to follow these instructions may result in failure of the detector to report an alarm condition.
Note: ZETA ALARMS LIMITED is not responsible for the product which is improperly installed, maintained and
tested.
Note: Use the VDOT-ADP adapter for a 4” square electrical box or 4” octagonal electrical box. VDOT-ADP
adaptor is not used for a 3-1/2” octagonal electrical box.
Electrical box
STBA-ADP adapter (optional)
EVA-STB-RL
*Screws (M4) are not included in the package
*Tapping screws (M4) are not included
in the package
Figure 3: Installation to an electrical box
VDOT-AD
P
VDOT-STB-RL

GLT-299-7-9 Rev. 0
Mar 23, 2018
4
Section 6 – CONNECTIONS
Install wiring in accordance with Figure 4 in this document.
All wiring must conform to applicable local codes, ordinances, and regulations.
Figure 4: Connection to Zeta control panel series
Figure 5: Connection to terminals
For system monitoring - for terminals 1 and 6, do not use looped wire under terminals.
Break wire run to provide monitoring of connections.
! CAUTION
Before installing the product check the continuity, polarity and insulation resistance of all wiring. Check that siting
is in accordance with the site system drawings and conforms to all applicable local codes such as NFPA 72.
In normal use, the VDOT-STB-RL base will be installed at ceiling level. Pass the field wiring through the cable
hole in the center and from the rear of the base. Hold and affix the base to the ceiling or electrical box with screws
via the base mounting holes. Connect the field wiring to the base terminals, as detailed in Section 5 and 6,
Connect to optional equipment
Output (Normal standby status)
・
Close between N/C-COM
・
Open between N/O-COM
Correct Wiring
Incorrect Wiring
Use cable AWG12-20 for SLC terminals, and cable AWG14-22 for relay terminals.
Do not connect different gauge cables at one terminal in order to prevent loosening.
! CAUTION
Do not connect cables in reverse polarity. Failure to connect the polarity correctly
could result in damage to the base and/or other equipment.
! CAUTION
CONTROL
Panel
NFU-7000
series
Loop +
Loop -
Loop +
Loop -
1
Base
6
3N/O
COM
N/C
1
Base
6
3N/O
COM
N/C
CONTROL
Panel
series

GLT-299-7-9 Rev. 0
Mar 23, 2018
5
making sure the wiring does not obstruct fitting of the detector head.
Fit the detector head by inserting it into the base and turning clockwise until the notch in the detector rim aligns
with base locking screws. To avoid unauthorized de-installation, turn the locking screw counterclockwise until the
screw comes to about 4mm(3/16”) from the rim of the base, as shown in Figure 6. The OMNIVIEWTM 360°
indicator permits visibility from any angle.
Figure 6: Position of locking screw
Note: Smoke and heat detectors are not to be used with detector guards unless the combination has been
evaluated and found suitable for that purpose.
Section 7 – MAINTENANCE
Maintenance
The VDOT-STB-RL is a high quality product engineered for reliability. In order to obtain optimum performance,
periodic maintenance is required, at lease in accordance with NFPA 72 chapter 14 “Inspection, Testing and
Maintenance”.
Routine Inspection:
Ensure the detector head and the base are secure and undamaged.
Operation Test:
The purpose of the Operational Test is to confirm the product’s correct operation.
1) When carrying out site testing of the product, the control panel shall be set to “one-man-walk test mode” prior
to the test.
2) Take any necessary precautions to limit the sounding of the alarm sounders/bells and any fire service
summoning device.
Locking Screw

GLT-299-7-9 Rev. 0
Mar 23, 2018
6
3) Operate the detector in accordance with each detector's instruction manual as mentioned in Section 4. Check
that the LED indicator on the detector illuminates. When the detector goes into an alarm status, confirm that
the output relay of the product is in operation (close between N/O and COM, open between N/C and COM).
Please note that the output relay operates if the detector is in operation even though in
the “one-man-walk test mode”. Take appropriate measures depending on the situation
in the field.
! CAUTION
Note: If the test cannot be carried out by operating the detector, remove the detector and short between terminal
3 and 6 to check the relay switches.
4) After the detector has given the alarm condition, the detector is automatically reset by control panel. It may be
necessary to allow a short time to elapse before resetting the detector.
Confirm that the output relay goes back to the initial status (open between N/O and COM, close between N/C
and COM) after the detector is reset.
Note: For detector testing and cleaning information, refer to each detector's instruction manual as mentioned in
Section 4.
Section 8 – SPECIFICATIONS
SLC Applied Voltage
Rated Range 20VDC to 38VDC
SLC Current Consumption
Standby 24μA Alarm/Activated 110μA
SLC Line impedance
Up to 50ohms, 2km(1.24mile) (Refer to * below)
RELAY
Switching capacity DC 30V/1A resistive
UL Ambient Installation Temperature
0℃(32°F) to 38℃(100°F)
Operating Temperature
-10℃(14°F) to 55℃(131°F)
Storage Temperature
-20℃(-4°F) to 60℃(140°F)
Max Relative Humidity
Up to 95% RH,non-condensing
Environment
Indoor dry use only
Terminal
Terminal for SLC: AWG12 to 20
Terminal for Relay: AWG14 to 22
Dimensions
φ105 mm x 22.5 mm H (φ4.133” x 0.885” H)
(Mount to a 3-1/2” octagonal box)
Weight
Approximately 79g (2.8 ounces)
Standard
UL268 and UL521
* Refer to the Installation and Operation Manual of Zeta Control Panel series to determine correct loop load and
maximum loop resistance for devices connected to each loop.

GLT-299-7-9 Rev. 0
Mar 23, 2018
7
FOR WARRANTY SERVICE, RETURN TO:
ZETA ALARMS LIMITED
72-78 MORFA ROAD, SWANSEA, SA1 2EN
http://www.zetaalarmsystems.com
Section 9 – WARRANTIES
1.1 Zeta warrants to the customers that:
(a) all products supplied hereunder will be of merchantable quality and will comply with any specification agreed
between Zeta and customer.
(b) it is not aware of any rights of any third party in the market which would or might render the sale of the
products, or the use of any of the trade marks on or in products, or the use of any of the trade marks on or in
relation to the products, unlawful.
1.2 In the event of any breach of the Zeta's warranty in Clause 1.1(a) whether by reason of defective materials,
production faults or otherwise, Zeta's liability shall be limited to:
(a) replacement of the products in question; or
(b) at the Zeta’s option, repayment of the price where this had been paid.
And the warranty period is three (3) years from the shipment from Zeta’s factory.
1.3 Notwithstanding anything to the contrary in this warranty terms, Zeta shall not be liable to the customer by
reason of any representation or implied warranty, condition or other term or any duty at common law, or
under the express terms of this warranty terms, for any consequential lossor damage whether for loss of
profit or otherwise and whether occasioned by the negligence of Zeta or its employees or agents or
otherwise, arising out of or in connection with any act or omission of Zeta relating to Zeta or supply of the
products, their use by any customer.
1.4 Customer shall indemnify Zeta against all loss, damages, liabilities, costs and expenses which Zeta may
suffer or incur as a result of or in connection with any breach by customer of this warranties terms or any laws
or regulations of any jurisdiction or any rules of any governing authorities.
Table of contents
Other Velocity TV Mount manuals
Popular TV Mount manuals by other brands

GEM
GEM LZ-NH2300N Specification sheet

SANUS VuePoint
SANUS VuePoint F170 installation instructions

Metra Electronics
Metra Electronics TL64 Assembly instructions

StarTech.com
StarTech.com RK219WALLV quick start guide

Mounting Dream
Mounting Dream MD2462 Installation instruction

PEERLESS
PEERLESS PARAMOUNT PF640 and assembly manual