manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Victaulic
  6. •
  7. Control Unit
  8. •
  9. Victaulic FireLock 247 Series User manual

Victaulic FireLock 247 Series User manual

Other Victaulic Control Unit manuals

Victaulic FireLock NXT 768 Series User manual

Victaulic

Victaulic FireLock NXT 768 Series User manual

Victaulic 725S Series User manual

Victaulic

Victaulic 725S Series User manual

Victaulic Vic-300 MasterSeal 761 Series User manual

Victaulic

Victaulic Vic-300 MasterSeal 761 Series User manual

Victaulic 769N FireLock NXT Series User manual

Victaulic

Victaulic 769N FireLock NXT Series User manual

Victaulic 5-Year Rebuild Kit User manual

Victaulic

Victaulic 5-Year Rebuild Kit User manual

Victaulic 751 FireLock Series User manual

Victaulic

Victaulic 751 FireLock Series User manual

Victaulic FireLock NXT 764 Series User manual

Victaulic

Victaulic FireLock NXT 764 Series User manual

Victaulic I-869E-3D User manual

Victaulic

Victaulic I-869E-3D User manual

Victaulic 768N FireLock NXT Series User manual

Victaulic

Victaulic 768N FireLock NXT Series User manual

Victaulic FireLock 756 Series User manual

Victaulic

Victaulic FireLock 756 Series User manual

Victaulic 809N User manual

Victaulic

Victaulic 809N User manual

Victaulic 769N FireLock NXT Series User manual

Victaulic

Victaulic 769N FireLock NXT Series User manual

Victaulic KOIL-KIT 799 Series User manual

Victaulic

Victaulic KOIL-KIT 799 Series User manual

Victaulic FireLock 758-LPA Series User manual

Victaulic

Victaulic FireLock 758-LPA Series User manual

Victaulic I-769N User manual

Victaulic

Victaulic I-769N User manual

Victaulic 867-4UF User manual

Victaulic

Victaulic 867-4UF User manual

Victaulic 867-7UF User manual

Victaulic

Victaulic 867-7UF User manual

Victaulic FireLock NXT 769 Series User manual

Victaulic

Victaulic FireLock NXT 769 Series User manual

Victaulic 751 FireLock Series User manual

Victaulic

Victaulic 751 FireLock Series User manual

Victaulic End Caps User manual

Victaulic

Victaulic End Caps User manual

Victaulic FireLock NXT 769N Series User manual

Victaulic

Victaulic FireLock NXT 769N Series User manual

Victaulic FireLock NXT 764 Series Guide

Victaulic

Victaulic FireLock NXT 764 Series Guide

Victaulic FireLock NXT 776 Series User manual

Victaulic

Victaulic FireLock NXT 776 Series User manual

Victaulic FireLock I-756 Series User manual

Victaulic

Victaulic FireLock I-756 Series User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

INSTALLATION OF THE SERIES 247
The Series 247 FireLock Residential Zone Control Riser Module
includes the module body, a UL or ULC Listed and FM Approved
waterflow detector, a pressure gauge with shutoff valve (provision for
draining), and an alarm test module available with different orifice sizes
(K-factors). In addition, an optional pressure relief valve kit is available.
Refer to the “Installation of the Optional Pressure Relief Valve Kit”
section.
NOTE CONCERNING WATERFLOW DETECTOR INSTALLATION AND
MAINTENANCE INSTRUCTIONS VERSUS RISER MANIFOLDS, AS
STATED FROM THE WATERFLOW DETECTOR MANUFACTURER: “The
section ‘Installation Guidelines’ suggests mounting the detector at least
6 inches/152 mm from a fitting that changes the direction of water flow
and no less than 24 inches/610 mm from a valve or drain. This is a
general statement that is superseded when a riser manifold assembly
is listed or approved by agencies such as UL and/or FM. The agency
approval takes precedence because this configuration has been tested
and its operation validated.”
NOTICE
• The Series 247 can be installed in either the horizontal
(left-to-right or right-to-left flow) or vertical (up) position.
The flow direction arrow MUST point toward the
sprinkler distribution, as shown in the drawing above.
1. Install the Series 247 into the system using Victaulic couplings for
grooved-end pipe. Always refer to the instructions, supplied with
the coupling, for complete installation requirements.
2. For the NPT threaded drain outlet, follow standard piping practices
to make the threaded connection. NOTE: The nominal drain size is
1 inch/25 mm. The drawings, shown on page 2, provide examples
of alternative ways to make the threaded drain connection with
a street elbow to avoid interference with couplings on the water
supply side and sprinkler distribution side of the module body.
3. Apply thread sealant to the threads of the pressure gauge. Install
the pressure gauge into the module body, as shown in the drawing
above. Make sure the face of the gauge is visible.
4. Connect the water-flow detector to the alarm system in accordance
with the instructions supplied.
5. To install the optional pressure relief valve, follow the instructions
in the “Installation of the Optional Pressure Relief Valve Kit”
section.
6. Perform the system flow test, as outlined in the “System Flow
Test” section.
WARNING
• Read and understand all instructions before attempting to install any Victaulic products.
• Depressurize and drain the piping system before attempting to install, remove, adjust, or maintain
any Victaulic products.
• Wear safety glasses, hardhat, and foot protection when working with Victaulic piping products.
Failure to follow these instructions could result in serious personal injury and/or property damage.
1 - 2-inch/33.7 - 60.3-mm Sizes
Waterow
Detector Pressure
Gauge
From Water
Supply
To Sprinkler
Distribution
To Building Drain
Module Body
Test/Drain Valve Shuto Valve
Pressure Gauge
Shuto Valve
I-247_1
FireLock®Residential Zone Control Riser Module Assembly
SERIES 247
I-247INSTALLATION INSTRUCTIONS
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2012 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REV_C
SYSTEM FLOW TEST
WARNING
• DO NOT operate the “Test/Drain Valve” under pressure.
Make sure the “Shutoff Valve” is in the “Closed”
position before operating the “Test/Drain Valve.”
Failure to follow these instructions could result in serious
personal injury and property damage.
Notify the authority having jurisdiction, remote station alarm monitors,
and anyone in the affected area that the system flow test is being
conducted.
1. Before performing the system flow test, confirm that all valves are
in their normal operating positions (“Shutoff Valve” in “Closed”
position, “Test/Drain Valve” in “Drain” position, and pressure
gauge shutoff valve in “Open” position).
2. Turn the thumb screw on the handle of the “Test/Drain Valve”
counterclockwise. Place the handle of the “Test/Drain Valve” in the
“Test” position.
3. Place the “Shutoff Valve” in the “Open” position.
4. Verify that the water-flow detector is operating properly and that
the alarms have sounded.
5. When the system flow test is complete, place the “Shutoff” valve in
the “Closed” position.
6. Place the “Test/Drain Valve” back to the “Drain” position. Hand-
tighten the thumb screw on the handle.
EXAMPLES OF ALTERNATIVE WAYS TO MAKE THE THREADED DRAIN CONNECTION
The following drawings provide examples of alternative ways to make the threaded drain connection to avoid interference with couplings on the water
supply side and sprinkler distribution side of the module body. NOTE: These graphics show the Series 247 installed with the optional pressure relief
valve kit.
When installing a street elbow directly into the drain, the street elbow must be threaded into the drain
before the Series 247 is installed into the system with grooved pipe and grooved pipe couplings.
If the Series 247 was installed in the system before the connection to the drain was made,
install a close nipple and a straight coupling before installing the street elbow.
I -247_ 2
FireLock®Residential Zone Control Riser Module Assembly
SERIES 247
I-247
INSTALLATION INSTRUCTIONS
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2012 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REV_C
INSTALLATION OF THE OPTIONAL PRESSURE
RELIEF VALVE KIT
CAUTION
• There must be NO shutoff valves between the Series
247 with pressure relief valve and the building drain.
• The pressure relief valve MUST be unrestricted in order
to discharge to the drain.
Failure to follow these instructions could result in
improper operation.
The following instructions apply to a Series 247 with pressure relief
valve installed in either the horizontal (left-to-right or right-to-left
flow) or vertical (up) position. The pressure relief valve is rated to
175 psi/1206 kPa.
1. Make sure all instructions in the “Installation of the Series 247”
section have been followed.
2. Remove the plugs from the drain port and the pressure relief valve
port. Refer to the drawings above.
3. Apply thread sealant to the threads of the close nipple and
pressure relief valve.
4. Install the close nipple into the drain port, as shown above.
5. Install the pressure relief valve into the pressure relief valve port,
as shown above.
6. Connect the drain tubing from the drain port’s close nipple to the
pressure relief valve using the barbed fittings and hose clamps
provided.
7. Follow all steps in the “System Flow Test” section.
PRESSURE RELIEF VALVE KIT OPTION
Drain Tubing
Pressure
Relief Valve
Close Nipple
Barbed Fitting
Elbow
Hose Clamp
Barbed
Fitting
Hose Clamp
Pressure
Relief Valve
Port
Drain Port
1 - 2-inch/33.7 - 60.3-mm Sizes
I-247_ 3
FireLock®Residential Zone Control Riser Module Assembly
SERIES 247
I-247INSTALLATION INSTRUCTIONS
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2012 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REV_C
FireLock®Residential Zone Control Riser Module Assembly
SERIES 247
I-247INSTALLATION INSTRUCTIONS
I-247
For complete contact information, visit www.victaulic.com
I-247 5375 REV C UPDATED 02/2012 Z000247000