QUICK RESPONSE
ELO PENDENT
SPRINKLER VK377
(STORAGE-DENSITY/AREA)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
T
elephone:
269-945-9501
T
echnical
Services:
877-384-5464
Fax:
269-818-1680
Email:
[email protected]Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 2 of 6
Form No. F_030993 22.04.14 Rev 22.1
4. INSTALLATION
Refer to appropriate NFPA, FM Global, and/or any other applicable installation standards.
5. OPERATION
During fire conditions, when the temperature around the sprinkler reaches its operating temperature, the heat-sensitive liquid in the
glass bulb expands, causing the bulb to shatter, releasing the pip cap assembly. Water flowing through the sprinkler orifice strikes
the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinkler Model VK377 is available through a network of domestic and international distributors. See The Viking Corporation
web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
TABLE 1: ORDERING INFORMATION
Instructions: Using the sprinkler base part number,
(1) add the suffix for the desired Finish
(2) add the suffix for the desired Temperature Rating.
Sprinkler
Base Part
No.
Size 1: Finishes 2: Classifications and Temperature Ratings
NPT
Inch
BSP
mm Description Suffix1Classification Nominal
Rating
Bulb
Color
Max. Ambient
Ceiling
Temperature3
Suffix
08337 3/4 20 Brass A Ordinary 155 °F (68 °C) Red 100 °F (38 °C) B
17489 1/2 15 Chrome F Intermediate 175 °F (79 °C) Yellow 150 °F (65 °C) D
White Polyester 4,5,6 M-/W Intermediate 200 °F (93 °C) Green 150 °F (65 °C) E
Black Polyester 4,5,6 M-/B High 286 °F (141 °C) Blue 225 °F (107 °C) G
ENT 4,5,6 JN
Example: 08337MB/W = VK377 with White Polyester Finish and 155 °F (79 °C) Nominal temperature rating. This sprinkler is to be
installed into an area with a maximum ambient temperature of 100 °F (38 °C) meaning if the area will experience temperatures above
the maximum ambient rating, you shall use a higher temperature-rated sprinkler.
Accessories
Sprinkler Wrenches (see Figure 1):
A. Standard Wrench: Part No. 05118CW/B (available since 1981).
B. Socket Wrench (for recessed or coated sprinklers): Part No. 11663W/B2(available since 2001).
Sprinkler Cabinet:
A. Up to 6 sprinklers: Part number 01724A (available since 1971).
B. 6-12 Sprinklers: Part number 01725A (available since 1971).
Footnotes
1. Where “-” is shown, insert the desired Temperature Rating suffix.
2. Requires a 1/2” ratchet which is not available from Viking.
3. Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
4. UL Listed as corrosion resistant.
5. FM Approved as a corrosion resistant.
6. The corrosion resistant coating has passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and
do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway.