manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Viking
  6. •
  7. Ventilation Hood
  8. •
  9. Viking Designer Series User manual

Viking Designer Series User manual

Viking Installation Guide
Designer Series
Built-In 18” H. Hoods
Viking Range Corporation
111 Front Street
Greenwood, Mississippi 38930 USA
2
NNOOTTEE::IIFFIINNSSTTAALLLLIINNGGHHOOOODDWWIITTHH
WWAARRMMIINNGGSSHHEELLFFPPAANNEELL,,IINNSSTTAALLLL
WWAARRMMIINNGGSSHHEELLFFPPAANNEELLFFIIRRSSTT..
IIMMPPOORRTTAANNTT--
PPLLEEAASSEERREEAADDAANNDDFFOOLLLLOOWW
•Before beginning, please read these instructions
completely and carefully.
•Do not remove permanently affixed labels, warnings, or
plates from the product. This may void the warranty.
•Please observe all local and national codes and
ordinances. If no local codes are applicable, wire in
accordance with the National Electrical Code,
ANSI/NFPA 70-1990.
••CChheecckkwwiitthhaaqquuaalliiffiieeddaannddttrraaiinneeddiinnssttaalllleerroorrllooccaall
ccooddeessffoorrmmaakkeeuuppaaiirrrreeqquuiirreemmeenntt,,iiffaannyy..
•TThheeiinnssttaalllleerrsshhoouullddlleeaavveetthheesseeiinnssttrruuccttiioonnsswwiitthhtthhee
ccoonnssuummeerrwwhhoosshhoouullddrreettaaiinnffoorrllooccaalliinnssppeeccttoorr’’ssuusseeaanndd
ffoorrffuuttuurreerreeffeerreennccee..
This hood is for residential installation only and is not
designed for installation over a commercial product.
Make sure power is off at the main circuit breaker or fuse
box before making connections. TTooaavvooiiddrriisskkooffffiirree,,
eelleeccttrriiccsshhoocckk,,oorriinnjjuurryyttooppeerrssoonnss,,ttuurrnnoofffftthheeeelleeccttrriicciittyy
ttootthheehhooooddffrroommtthheeppoowweerrssuuppppllyybbeeffoorreesseerrvviicciinnggoorr
cclleeaanniinngg..
Viking Range hoods are equipped with variable speed
controls for blowers. These units will not function with a
single
speed ventilator. All Viking Range ventilator kits are
designed specifically for use with Viking Range hoods.
Use of
any non-Viking Range ventilator kit will void the hood
warranty.
WWAARRNNIINNGG
TTOORREEDDUUCCEETTHHEERRIISSKKOOFFFFIIRREE,,EELLEECCTTRRIICCAALLSSHHOOCCKK,,
OORRIINNJJUURRYYTTOOPPEERRSSOONNSS,,OOBBSSEERRVVEETTHHEEFFOOLLLLOOWWIINNGG::
1. Installation work and electrical wiring must be done by
qualified person(s) in accordance with all applicable
codes and standards, including fire-rated construction.
2. Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fuel
burning equipment to prevent back drafting. Follow
the heating equipment manufacturer’s guideline and
safety standards such as those published by the
National Fire Protection Association (NFPA), and the
American Society for Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE), and the local code
authorities.
3. When cutting or drilling into wall or ceiling, do not
damage electrical wiring and other hidden utilities.
4. Ducted fans must always be vented to the outdoors.
5. WWAARRNNIINNGG!!::To reduce the risk of fire, use only metal
ductwork.
6. CCAAUUTTIIOONN!!::To reduce risk of fire and to properly
exhaust air, be sure to duct air outside. Do not vent
exhaust air into spaces within walls or ceilings, or into
attics, crawl spaces, or garages.
CCAAUUTTIIOONN
For general ventilating use only. Do not use
to exhaust hazardous or explosive materials
and vapors.
WWAARRNNIINNGG
TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK,
OR INJURY TO PERSONS, RANGEHOODS MUST BE
INSTALLED WITH THE VENTILATORS THAT ARE
SPECIFIED ON THEIR CARTON INDICATING
SUITABILITY WITH THIS MODEL. OTHER VENTILATORS
CANNOT BE SUBSTITUTED.
WWAARRNNIINNGG
TTOORREEDDUUCCEETTHHEERRIISSKKOOFFAARRAANNGGEETTOOPPGGRREEAASSEE
FFIIRREE::
1. Never leave surface units unattended at high
setting. Boilovers cause smoking and greasy
spillovers that may ignite. Heat oils slowly on
low or medium settings.
2. Always turn hoon ON when cooking at high
heat or when cooking flaming foods.
3. Clean ventilating fans frequently. Grease should
not be allowed to accumulate on fan or filter.
4. Use proper pan size. Always use cookware
appropriate for the size of the surface element.
BBAASSIICCSSPPEECCIIFFIICCAATTIIOONNSS
IINNTTEERRIIOORRAANNDDEEXXTTEERRIIOORRPPOOWWEERRHHOOOODDSS
RREECCOOMM..NNUUMMBBEERROOFF112200VVAACC//6600HHzz
DDEESSCCRRIIPPTTIIOONNCCFFMM11HHAALLOOGGEENNFFIILLTTEERRSSSSPPAACCEERRSSMMAAXX..AAMMPPSS33
((iinntt..--iinntteerriioorr;;eexxtt--eexxtteerriioorrLLIIGGHHTTSS((IInntteerriioorr//EExxtteerriioorr))
1188””HH..WWaallll
30”W.* 300 int/600 int./1200 int./900 ext./1200 ext. 2 2 0 2.4/4.6/6.6/6.6/3.9
36”W.* 300 int/600 int./1200 int./900 ext./1200 ext. 2 2 1 2.4/4.6/6.6/6.6/3.9
42”W.* 600 int./1200 int./900 ext./1200 ext. 2 3 0 4.6/6.6/6.6/4.0
48”W. 1200 int./1200 ext./1500 ext. 3 3 0 7.0/4.3/5.1
AAPPPPRROOXXIIMMAATTEERREECCOOMMMMEENNDDEEDDMMAAXX..DDUUCCTT
MMOODDEELLNNUUMMBBEERRCCFFMM11DDUUCCTTSSIIZZEERRUUNN22((fftt..))
FFoorrUUsseewwiitthhhhooooddss::
VIV300 (interior) 300 7” round 50
VIV600 (interior) 600 7” round 50
VIV1200 (interior) 1200 10” round 50
VEV900 (exterior) 900 10” round 50
VEV1200 (exterior) 1200 10” round 50
VEV1500 (exterior) 1500 10” round 75
PPRROOPPEERRIINNSSTTAALLLLAATTIIOONN//DDUUCCTTIINNGGIISSEEXXTTRREEMMEELLYYIIMMPPOORRTTAANNTTTTOOEENNSSUURREEMMAAXXIIMMUUMMPPEERRFFOORRMMAANNCCEEFFRROOMMAANNYY
VVEENNTTIILLAATTIIOONNPPRROODDUUCCTT
1. •All CFMs stated are based on tests at .1 static pressure: without applying static pressure, CFM would be greatly
overstated.
2. •Duct run length is for general reference only; for longer duct runs, increase duct size and contact a qualified and trained
installer.
•Straight runs and gradual turns are best; for example, each 90oelbow is equivalent to 5-10 feet (1.52 - 3.05 cm) of
straight run.
•Never use flexible duct; it creates back pressure/air turbulence and greatly reduces performance.
•Proper performance is dependent upon proper ducting; make sure that a qualified and trained installer is used.
••CChheecckkwwiitthhaaqquuaalliiffiieeddaannddttrraaiinneeddiinnssttaalllleerroorrllooccaallccooddeessffoorrmmaakkeeuuppaaiirrrreeqquuiirreemmeenntt,,iiffaannyy..
3. •Max. amp rating for hoods includes recommended ventilator kit rating; all products must be hard wired direct with 2-
wire with ground.
**11220000CCFFMM((oorr11550000CCFFMMiiffaapppplliiccaabbllee))eexxtteerriioorrvveennttiillaattoorrsshhoouullddbbeeuusseeddwwhheenniinnssttaalllleeddoovveerr
rraannggeess/
/rraannggeettooppsswwiitthhggaassggrriillll..
3
4
HHEEIIGGHHTTOOFFHHOOOODD
The bottom of the hood should be 30” (76.2 cm) min. to 36” (91.4 cm) max. above the countertop. This would
typically result in the bottom of the hood being 66” (167.6 cm) to 72” (182.9 cm) above the floor. For best
performance, it is recommended that the bottom of the hood be 30” (76.2 cm) to 33” (83.8 cm) above the
countertop. These dimensions provide for safe and efficient operation of the hood.
CClleeaarraanncceeDDiimmeennssiioonnss
18”
(45.7 cm)
30”
(76.2 cm) Min.
36”
(91.4 cm) Max.
36”
(91.4 cm)
CCoouunntteerrttoopp
5
PPRREEPPAARRIINNGGFFOORRHHOOOODDIINNSSTTAALLLLAATTIIOONN
Plan where the ductwork will be located. See pages 8-11 for rough-in dimensions. Install proper-sized duct work, and
roof or wall cap for the type of blower you are using. Recommended hood locations for the most common
installations are shown on page 2.
Adjust your measurements for various heights of ceilings, soffits,
cabinets, or ranges/rangetops.
Roof Cap
7” Round
Duct
Roof Cap
10”
Round
duct
Duct Cover
or Soffit
Duct Cover
or Soffit
300 or 600 CFM
Interior-Power - Typical Ductwork
1200 CFM
Interior-Power - Typical Ductwork
Exterior Blower
10” Round
Duct
Duct
Cover
or Soffit
12”
(30.5 cm)
900, 1200, or 1500 CFM
Exterior-Power - Typical Ductwork
12”
(30.5 cm)
IINNSSTTAALLLLIINNGGHHOOOODDCCAANNOOPPYY
Center the wood strip (acquired locally - see drawing for dimensions) and attach to wall. Using the slot located on
the backside of the canopy, place the hood onto the wood strip. Secure the hood to strip with mounting screws
provided. Make sure that the wood strip mounting screws are driven into the framing and not just the drywall. Use
additional mounting screws (and wall anchors if necessary) in the other holes.
NNOOTTEE::BBEECCAAUUSSEEOOFF
TTHHEEWWEEIIGGHHTTOOFFTTHHEE
HHOOOODD--MMAAKKEESSUURREE
TTHHAATTTTHHEEWWOOOODDSSTTRRIIPP
MMOOUUNNTTIINNGGSSCCRREEWWSS
AARREEDDRRIIVVEENNIINNTTOOTTHHEE
FFRRAAMMIINNGGAANNDDNNOOTT
JJUUSSTTTTHHEEDDRRYYWWAALLLL..IITT
MMAAYYBBEENNEECCEESSSSAARRYYTTOO
DDRRIILLLLAADDDDIITTIIOONNAALL
HHOOLLEESSIINNTTHHEEC
CAANNOOPPYY
FFOORRPPRROOPPEERR
AALLIIGGNNMMEENNTT..
EELLEECCTTRRIICCAALLSSUUPPPPLLYY
Run 120 VAC electrical power cable from service panel to installation location. See “Basic Specifications” on page 13
for the maximum amp requirements.
Top
Mounting
Holes Wood Strip
(acquired locally- 11/2” x3/4”)
Slot for Wood
Strip
Rear Mounting
Holes
11/2”
(3.8 cm)
3/4”(1.9 cm)
113/16”
(4.6 cm)
6
IINNSSTTAALLLLIINNGGRROOUUGGHH--IINNPPLLAATTEEAANNDDCCOONNNNEECCTTIINNGGDDUUCCTT--IINNTTEERRNNAALLPPOOWWEERR
((AAllssoosseeeeiinnssttrruuccttiioonnssssuupppplliieeddwwiitthhvveennttiillaattoorrkkiitt))
1. Attach rough-in plate to studs in the inside, top of hood with four (4) #10-24 nuts provided.
2. Connect ductwork using supplied transition and damper (transition and damper are part of rough-in plate on some
models). Use duct tape to make all joints secure and air tight. In some installations, it is easier to attach transition
to plate before attaching plate to hood.
3. Remove wire box cover. Remove a knockout from the wiring box. Feed 6” of power cable through opening and
attach cable to wiring in wiring box with appropriate connector. WWAARRNNIINNGG: MAKE SURE ELECTRICAL SUPPLY IS
OFF.
4. Wire black to black, white to white, and green or bare wire beneath green ground screw. Replace wire box cover.
5. Plug the rough-in plate power cord into the receptacle located on the top side of the light panel.
Top of Hood
Studs
Nuts
Rough-in
Plate
Wire box cover
Nuts
Studs
3-prong power
supply plug-in
2-prong blower plug-in
Receptacles are located
behind and above control
panel
7
IINNSSTTAALLLLIINNGGTTHHEEVVEENNTTIILLAATTOORRSS
VVIIVV330000oorrVVIIVV660000--IInntteerriioorr--PPoowweerrVVeennttiillaattoorrKKiitt((330000oorr660000CCFFMM))
(also see instructions supplied with ventilator kit)
1. Make sure barrel nuts and wing nut are engaged halfway onto
threaded stud.
2. Lift ventilator into canopy - may be easier to turn
ventilator side ways to lift into canopy then rotate
into mounting position.
3. Lift ventilator allowing barrel nuts to come
through large end of keyhole opening.
4. Slide ventilator to the right, engaging barrel
nuts into small end of keyhole openings and
engaging studs with wing nut in slot on right side
of ventilator. Make sure discharge openings
match.
5. Tighten barrel nuts and wing nut.
6. Plug the ventilator power cord into the receptacle
located on the topside of the light panel.
600 CFM Blower
Rough-in
Plate Studs
Barrel Nuts
Top of Hood
Wingnut
Remove rear filter support before installing
blower. After installation is complete,
reinstall the rear filter support.
VVIIVV11220000--IInntteerriioorr--PPoowweerrVVeennttiillaattoorrKKiitt((11220000CCFFMM))
(also see instructions supplied with ventilator kit)
1. Make sure barrel nuts and wing nut are engaged
halfway onto threaded stud.
2. Lift ventilator into canopy - may be easier to turn
ventilator side ways to lift into canopy then rotate into
mounting position.
3. Engage tab on ventilator with slot in rough-in plate
AND engage slot in ventilator with barrel nut on
threaded stud.
4. Push ventilator towards the back of hood to fully
engage.
5. Use a long, flat-head screwdriver to tighten the barrel
nut securely.
6. Plug the ventilator power cord into the receptacle
located on the topside of the light panel.
1200 CFM Blower
Top of
Hood
Slot
Rough-in Plate
Studs
Barrel Nut
Transition
9”
(22.9 cm)
Remove rear filter support before
installing blower. After installation
is complete, reinstall the rear filter
support.
8
IINNSSTTAALLLLIINNGGRROOUUGGHH--IINNPPLLAATTEEAANNDDCCOONNNNEECCTTIINNGGDDUUCCTT--EEXXTTEERRNNAALLPPOOWWEERR
((AAllssoosseeeeiinnssttrruuccttiioonnssssuupppplliieeddwwiitthhvveennttiillaattoorrkkiitt))
1. Run 10” round steel ductwork, from exterior blower to the installationlocation. For best performance, use the
straightest possible duct run and the fewest number of elbows. Tape all joints.
2. Run 120 VAC electrical power cable from service panel and from remote blower to installation location.
3. Remove wiring box cover. Remove knockouts from the wiring box. Feed 6” of power cable through the openings
and attach cables to wiring box with appropriate connectors.
4. Wire black to black, white to white, and green or bare wire beneath green ground screw. Replace wiring box
cover.
5. Attach rough-in plate to the studs at the inside
top of hood with (4) #10-24 nuts provided.
6. Connect ductwork to rough-in plate and tape
joint.
7. Plug the rough-in plate power cord into the
receptacle located on the top side of the light panel.
Receptacles are located behind and above
control panel
10” (25.4 cm)
Round Duct
Wire from
breaker goes
to three prong
female plug.
Wire from blower goes
to two prong male
plug
3-prong power supply
plug-in
2-prong blower plug-in
9
RROOOOFFIINNSSTTAALLLLAATTIIOONN
EEXXTTEERRIIOORR--PPOOWWEERRVVEENNTTIILLAATTOORR
VVEEVV//ddeevv990000--EExxtteerriioorrPPoowweerrVVeennttiillaattoorrKKiitt((990000CCFFMM))
(also see instructions supplied with ventilator kit)
1. Locate the blower on the rear slope of the roof. Place
it in a location to minimize duct run. The location
should be free of obstacles (T.V. leads, electrical lines,
etc.). Bear in mind, if the blower top is level with the
roof peak, it will not be seen from the street. Keep
this approximate location in mind as you work from
within the attic.
2. Mark a point halfway between rafters.
3. Drill a guide hole through the roof at this point.
4. From the outside, use the guide hole as a starting
point.
A. Use a T-square to measure 81/2” (21.6 cm) to the
left of the guide hole, then down 103/8” (26.4 cm)
to locate the bottom left corner of the layout.
B. Mark the rectangular cutout and remove only the
shingles in this area.
5. Mark an 11” (27.9 cm) diameter circle centered on the
guide hole and mark the center of the 11/4” (3.2 cm)
diameter electrical wiring hole.
6. Cut out the roof board(s) along the 11” (27.9 cm)
diameter circle and drill a 11/4” hole as marked.
7. For flat roof installations, build a curb that will mount
the blower at a minimum pitch of 2/12. Discharge end
of the blower should be pointed away from prevailing
winds.
8. Remove roofing nails from the upper two-thirds of the
shingles around the cutout area. Carefully lift the
shingles to allow the back flashing sheet on the
blower housing to fit under them.
9. Center the blower ring in the 11” (27.9 cm) diameter
hole, making sure that the 11/4” (3.2 cm) diameter
electrical wiring hold aligns with the hole in the wiring
box.
10. Attach the blower to the roof with the six screws
provided. It is recommende that the screws be
located inside the blower housing. All six holes in the
back panel must be filled, or any moisture that may
get inside the housing could leak into the house.
11. Using a good grade of roofing cement, seal all of the
shingles around the housing and flashing sheet as
well as the mounting screw heads.
12. Bring electrical wiring through the hole in the wiring
box and secure it according to local codes.
13. Make the electrical connections with the proper
connector for the type of wiring being used.
Connect white to white, black to black, and the green
or bare wire to green.
14. Replace wiring box cover and screws. Do not pinch
wiring under the cover.
15. Check for free movement of the damper before
installing housing cover and screws.
16. Turn on power and check operation of the blower.
Guide
Hole
11” (27.9
cm) dia. hole
71/4” (18.4 cm)
11/4” (3.2 cm) dia. hole
81/2” (21.6 cm)
103/8”
(26.4 cm)
201/2”
(52.1 cm) 91/8”
(23.2 cm)
203/4” (52.7 cm)
2”(5.1 cm)
2”(5.1 cm)
6 3/4”
(17.1 cm)
28 1/4”
(71.8 cm)
25”
(63.5 cm)
Black
to
Black
120 VAC
Line In White to
White
Green to
Green
RROOOOFFCCUUTTOOUUTT
RREEMMOOVVEESSHHIINNGGLLEESS
10
WWAALLLLIINNSSTTAALLLLAATTIIOONN
EEXXTTEERRIIOORR--PPOOWWEERRVVEENNTTIILLAATTOORR
VVEEVV990000--EExxtteerriioorr--PPoowweerrVVeennttiillaattoorrKKiitt((990000CCFFMM))
1. Choose a position on the outside wall. Min. 24” (61.0
cm from ground may vary depending on local codes
or location. Make sure that no wall studs, pipes or
wires run through the opening area.
2. Drill a guide hole at the center of the opening area.
3. From the outside, use the guide hole as a starting
point to lay out the installation.
A. Use a T-square to measure 103/4” (27.3 cm) to the
left of the guide hole, then 127/8” (32.7 cm) to
locate the top-left corner of the layout.
B. Starting from the top -left corner, mark a 25”
(63.5 cm) by 281/2” (72.4 cm) rectangle on wall
located from guide hole.
4. Cut a rectangular hole in the siding only. Do not cut
the sheathing. Nail down all siding ends.
5. Mark an 11” (27.9 cm) diameter circle centered on the
guide hole and mark the center of the 11/4” diameter
electrical wiring hole.
6. Cut the 11” (27.9 cm) hole in the sheathing and drill
the 11/4”(3.2 cm) as marked.
7. Place a large bead of caulk on the back side of the
housing along the outer edge.
8. Center the blower ring in the 11” (27.9 cm) diameter
hole, making sure that the 11/4” (3.2 cm) diameter
electrical wiring hole aligns with the hole in the wiring
box.
9. Attach blower to the wall with the six screws
provided. It is recommended that the screws
be located inside the blower housing. All six
holes in the back panel must be filled, or any
moisture that may get inside the housing could
leak into the house.
10. Using a good grade of caulk, seal all around the
mounting screw heads.
11. Bring electrical wiring through the hole in the
wiring box and secure it according to local
codes.
12. Make the electrical connections with the proper
connector for the type of wire being used.
Connect white to white, black to black, and
green or bare wire to green.
13. Replace wiring box cover and screws. Do not
pinch wiring under cover.
14. Check for free movement of the damper before
installing housing cover and screws.
15. Turn on power and check operation of the blower.
16. Top and side flanges of the back plate may be
covered with trim strips. Do not block grill opening at
bottom with trim. It will adversely affect performance
of the blower.
Black
to
Black
120 VAC
Line In White
to
White
Green to
Green
11” (27.9 cm)
dia. hole
Guide
Hole
91/8”
(23.2 cm)
71/4” (18.4 cm)
11/4” (3.2 cm)
Dia. Hole
12 7/8”
(32.7 cm)
28 1/4”
(71.8 cm)
25” (63.5 cm)
103/4”
(27.3 cm)
WWAALLLLCCUUTTOOUUTT
11
RROOOOFFIINNSSTTAALLLLAATTIIOONN
EEXXTTEERRIIOORR--PPOOWWEERRVVEENNTTIILLAATTOORR
VVEEVV11220000--EExxtteerriioorrPPoowweerrVVeennttiillaattoorr((11220000CCFFMM))
(also see instructions supplied with ventilator kit)
1. Locate the blower on the rear slope of the roof.
Place it in a location to minimize duct run. The
location should be free of obstacles (T.V. leads,
electrical lines, etc.). Bear in mind, if the blower top
is level with the roof peak, it will not be seen from
the street. Keep this approximate location in mind
as you work from within the attic.
2. Mark a point halfway between rafters.
3. Drill a guide hole through the roof at this point.
4. From the outside, use the guide hole as a starting
point to lay out the installation.
A. Use a T-square to measure 913/16” (24.9 cm) to
the left of the guide hole, then 1211/16” (32.2
cm) to locate the top-left corner of the layout.
B. Starting from the top-left corner, mark the
rectangular cutout and remove only the shingles
in this area.
5. Mark an 11” (27.9 cm) diameter hole centered on
the guide hole. Mark the center of the 11/4” (3.2
cm) diameter electrical wiring hole.
6. Cut out the roof board(s) along the 11” (27.9 cm)
diameter circle and drill a 11/4” hole as marked.
7. For flat roof installations, build a curb that will
mount the blower at a minimum pitch of 2/12.
Discharge end of the blower should be pointed
away from prevailing winds.
8. Remove roofing nails from the shingles around the
top and sides of the cutout area only. Carefully lift
the shingles to allow the back flashing sheet on the
blower housing to fit under them.
9. Center the blower ring in the 11” (27.9 cm)
diameter hole, making sure that the 1 ¼” (3.2 cm)
diameter electrical wiring hold aligns with the hole
in the wiring box.
10. Attach the blower to the roof with the six screws
provided. It is recommended that the screws be
located inside the blower housing. All six holes in
the back panel must be filled, or any moisture that
may get inside the housing could leak into the
house.
11. Using a good grade of roofing cement, seal all of
the shingles around the housing and flashing sheet
as well as the mounting screw heads.
12. Bring electrical wiring through the hole in the
wiring box and secure it according to local codes.
13. Make the electrical connections with the proper
connector for the type of wiring being used.
Connect white to white, black to black, and the
green or bare wire to green.
14. Replace wiring box cover and screws. Do not
pinch wiring under the cover.
15. Check for free movement of the damper before
installing housing cover and screws.
16. Turn on power and check operation of the blower.
20 1/2”
(52.1 cm)
BB
12 11/16”
(32.2 cm)
AA
CC
11/4” (3.2
cm) dia. hole
11” (27.9 cm)
dia. hole
RREEMMOOVVEE
SSHHIINNGGLLEESS
291/2”
(74.9 cm)
DD2” (5.1 cm)
2” (5.1 cm)
7”
(17.8 cm)
RROOOOFFCCUUTTOOUUTT
Black to
Black
Ground to
grounding
screw
120 VAC
Line In
White
to Blue
AB CD
DEV1200 18” 15” 9 13/16’ 22”
(45.7 cm) (38.1 cm) (24.9 cm) (55.9 cm)
DEV1500 21” 18” 12 5/8” 25”
(53.3 cm) (45.7 cm) (32.1 cm) (63.5 cm)
12
WWAALLLLIINNSSTTAALLLLAATTIIOONN
EEXXTTEERRIIOORR--PPOOWWEERRVVEENNTTIILLAATTOORR
VVEEVV11220000--EExxtteerriioorrPPoowweerrVVeennttiillaattoorrKKiitt((11220000CCFFMM))
1. Choose a position on the outside wall. Min. 24” (61.0 cm
from ground may vary depending on local codes or location.
Make sure that no wall studs, pipes or wires run through
the opening area.
2. From inside, mark and drill a guide hole at the center of
the opening area.
3. From the outside, use the guide hoel as a starting point to
lay out the installation.
A. Use a T-square to measure 1113/16” (30.0 cm) to the
left of the guide hole, then 1411/16” (37.3 cm)
tolocate the top-left corner of the layout.
B. Starting from the top-left corner, mark a 22” (55.9
cm) by 291/2” (74.9 cm) rectangle on wall located
from guide hole.
4. Cut a rectangular hole in the siding only. Do not cut the
sheathing. Nail down all siding ends.
5. Mark an 11” (27.9 cm) diameter circle centered on the
guide hole and mark the center of the 11/4” diameter
electrical wiring hole.
6. Cut the 11” (27.9 cm) hole in the sheathing and drill the
11/4”(3.2 cm) as marked.
7. Place a large bead of caulk on the back side of the
housing along the outer edge.
8. Center the blower ring in the 11” (27.9 cm) diameter hole,
making sure that the 11/4” (3.2 cm) diameter electrical wiring
hole aligns with the hole in the wiring box.
9. Attach blower to the wall with the six screws provided. All
six holes in the back panel must be filled, or any moisture
that may get inside the housing could leak into the house.
10. Using a good grade of caulk, seal all around the mounting
screw heads.
11. Bring electrical wiring through the hole in the wiring box and
secure it according to local codes.
12. Make the electrical connections with the proper connector
for the type of wire being used. Connect white to blue,
black to black, and green or bare wire to grounding screw.
13. Replace wiring box cover and screws. Do not pinch wiring
under cover.
14. Check for free movement of the damper before installing
housing cover and screws.
15. Turn on power and check operation of the blower.
16. Top and side flanges of the back plate may be
covered with trim strips. Do not block grill opening
at bottom with trim. It will adversely affect
performance of the blower.
WWAALLLLCCUUTTOOUUTT
BB
3”
(7.6 cm)
1411/16
(37.3 cm)
CC
AA
11”
(27.9 cm)
dia. hole
11/4” (3.2 cm)
dia. hole
Black to
Black
120
VAC
Line In
Ground to
grounding
screw
Filter
Spacer
Mesh Filter
FFIILLTTEERR//SSPPAACCEERRIINNSSTTAALLLLAATTIIOONN
1. Install spacer(s) in center of filters.
2. Number of spacers and mesh filters:
Spacers - 36”W only
Mesh Filters - Wall Hoods
30” W., 36” W., - 2 filters
42” W., 48” W. - 3 filters
29 1/2”
(74.9 cm)
White to
Blue
ABC
DEV1200 22” 17” 11 13/16”
(55.9 cm) (43.2 cm) (30.0 cm)
DEV1500 25” 20” 14 5/8”
(63.5 cm) (50.8 cm) (37.2 cm)
WWIIRRIINNGGDDIIAAGGRRAAMM
EEXXTTEERRIIOORRVVEENNTTIILLAATTOORR
13
EEXXTTEERRIIOORRVVEENNTTIILLAATTOORRDDIIMMEENNSSIIOONNSS
10” Dia.
203/4” (52.7 cm)
241/2”
(62.2 cm)
43/4”
(12.1 cm)
14”
(35.6 cm)
243/4”
(62.9 cm)
151/2”
(39.4 cm)
281/4”
(71.8 cm)
VVEEVV990000
DDEEVV11220000
DDEEVV11550000
221/8”
(56.2 cm)
BB
101/8”
25.7 cm
AA
291/2”
(74.9 cm)
10”
(25.4 cm)
Dia.
Opening for wiring
Flashing
Flashing
Opening for
wiring
3 1/2”
(8.9 cm)
6 1/4”
(15.9 cm)
5”
(12.7 cm)
3” (7.6 cm)
14 13/16”
(37.6 cm)
11 13/16”
(30.0 cm)
AB
DEV1200 18” 22”
(45.7 cm) (55.9 cm)
DEV1500 21” 25”
(53.3 cm) (55.9 cm)
14
WWAALLLLHHOOOODDDDIIMMEENNSSIIOONNSS
ttaallllttrraaddiittiioonnaall--lleeddggeelleessss//
ttaallllttrraaddiittiioonnaall--lleeddggee
1”
(2.5 cm)
1 1/2”
(3.8 cm) 1 1/2”
(3.8 cm)
12”
(30.5 cm)
18”
(45.7 cm)
24” (61.0 cm)
18”
(45.7 cm)
24” (61.0 cm)
7/8”
(2.2 cm)
9”
(22.9 cm)
SSIIDDEEVVIIEEWW
EEXXTTEERRNNAALLPPOOWWEERRSSIIDDEEVVIIEEWW
IINNTTEERRNNAALLPPOOWWEERR
9 3/4”
(24.8 cm)
TTrraannssiittiioonn
VVIIVV11220000OOnnllyy
BB
8 1/4”
(20.9 cm)
5 15/16”
(15.1 cm)
3”
(7.6 cm)
6 7/16”
(16.4 cm)
2 1/2”
(6.4 cm)
AA
3300””WW..,,3366””WW..,,4422””WW..
EEXXTTEERRNNAALLPPOOWWEERR--VVEEVV990000oorrVVEEVV112200003300””WW..,,3366””WW..,,4422””WW..
IINNTTEERRNNAALLPPOOWWEERR--VVIIVV330000,,VVIIVV660000,,oorrVVIIVV11220000
24”
(61.0 cm)
4 5/8”
(11.7 cm)
18 3/4”
(47.6 cm)
9 1/8”
(23.2 cm)
9 5/8”
(24.4 cm)
9 3/8”
(23.8 cm)
AA
AB
30” W. Models 29 7/8” (75.9 cm) 14 15/16” (37.94 cm)
36” W. Models 35 7/8”(91.1 cm) 17 15/16” (45.56 cm)
42” W. Models 41 7/8” (106.4 cm) 20 15/16” (18.18 cm)
48” W. Models 47 7/8” (121.6cm) 23 15/16” (60.8 cm)
**NNOOTTEE::
VVIIVV660000--77””
VVIIVV11220000--1100””
15
23 15/16”
(60.8 cm)
47 7/8” (121.6 cm)
83/16”
(20.7 cm)
65/8” (16.8 cm)
515/16” (15.1cm)
21/2”(6.35 cm)
3” (7.62 cm)
183/4” (47.6 cm)
91/2”
(24.1 cm)
91/4”
(23.5 cm)
83/8”
(21.3 cm)
51/2”
(14.0 cm)
5/8” (1.6 cm)
120
V
9 3/4”
(25.4 cm) dia. cutout
120
V
4488””WW..
EEXXTTEERRNNAALLPPOOWWEERR--VVEEVV11220000oorrVVEEVV11550000
4488””WW..
IINNTTEERRNNAALLPPOOWWEERR--VVIIVV11220000
47 7/8” (121.6 cm)
23 15/16”
(60.8 cm)
WWIIRRIINNGGDDIIAAGGRRAAMM
DDEESSIIGGNNEERRSSEERRIIEESS
BBUUIILLTT--IINNHHOOOODDSS
REFER ONLY TO
FEATURES EQUIPPED
WITH THIS UNIT.
F20040L (PS1005VR)
VIKING RANGE CORPORATION
111 Front Street
Greenwood, Mississippi 38930 USA
(662) 455-1200
For product information
call 1-888-VIKING1 (845-4641)
or visit the Viking Web site at
vikingrange.com

Other manuals for Designer Series

5

This manual suits for next models

6

Other Viking Ventilation Hood manuals

Viking DCWL3944 User manual

Viking

Viking DCWL3944 User manual

Viking VBCV3038 User manual

Viking

Viking VBCV3038 User manual

Viking DBCV3638 User manual

Viking

Viking DBCV3638 User manual

Viking DCIH3604 User manual

Viking

Viking DCIH3604 User manual

Viking VBCV3038 User manual

Viking

Viking VBCV3038 User manual

Viking VWH3010SS User manual

Viking

Viking VWH3010SS User manual

Viking DCWH3042SS User manual

Viking

Viking DCWH3042SS User manual

Viking Tuscany CTVWH360 User manual

Viking

Viking Tuscany CTVWH360 User manual

Viking VMOR506 User manual

Viking

Viking VMOR506 User manual

Viking RDWHC3042SS User manual

Viking

Viking RDWHC3042SS User manual

Viking 24" User manual

Viking

Viking 24" User manual

Viking RVCH330SS User manual

Viking

Viking RVCH330SS User manual

Viking VCIH3608 User manual

Viking

Viking VCIH3608 User manual

Viking VIPR182R User manual

Viking

Viking VIPR182R User manual

Viking DCIH User manual

Viking

Viking DCIH User manual

Viking DBCV3082 User manual

Viking

Viking DBCV3082 User manual

Viking DCWH User manual

Viking

Viking DCWH User manual

Viking Tuscany TVWH360 User manual

Viking

Viking Tuscany TVWH360 User manual

Viking VMOR205SS User manual

Viking

Viking VMOR205SS User manual

Viking MVLH636SS Installation guide

Viking

Viking MVLH636SS Installation guide

Viking DTWN3048SS User manual

Viking

Viking DTWN3048SS User manual

Viking VWH 10"H User manual

Viking

Viking VWH 10"H User manual

Viking F20560 Setup guide

Viking

Viking F20560 Setup guide

Viking DCH3042SS User manual

Viking

Viking DCH3042SS User manual

Popular Ventilation Hood manuals by other brands

Beco CFB 6437 WHA user manual

Beco

Beco CFB 6437 WHA user manual

Novy Phantom Cable Operating and installation instructions

Novy

Novy Phantom Cable Operating and installation instructions

GE PVB98STSS installation instructions

GE

GE PVB98STSS installation instructions

FALMEC MIRA TOP Installation sheet

FALMEC

FALMEC MIRA TOP Installation sheet

Whirlpool AKR473.1/IX Health & safety, use & care and installation guide

Whirlpool

Whirlpool AKR473.1/IX Health & safety, use & care and installation guide

Pelgrim RSK930L Instructions for use

Pelgrim

Pelgrim RSK930L Instructions for use

Franke FMY 905 HE user manual

Franke

Franke FMY 905 HE user manual

Bertazzoni KT60PRO1XA installation manual

Bertazzoni

Bertazzoni KT60PRO1XA installation manual

ELICA HCI91631XH manual

ELICA

ELICA HCI91631XH manual

Broan Best K29 Brochure & specs

Broan

Broan Best K29 Brochure & specs

BORETTI M-System MEPK-9050 operating instructions

BORETTI

BORETTI M-System MEPK-9050 operating instructions

Miele DA 229-2 Operating and installation instructions

Miele

Miele DA 229-2 Operating and installation instructions

Zanussi IH 9048 Instructions for use

Zanussi

Zanussi IH 9048 Instructions for use

Bertazzoni KG90CONX installation instructions

Bertazzoni

Bertazzoni KG90CONX installation instructions

Hotpoint HHB6.7AD operating instructions

Hotpoint

Hotpoint HHB6.7AD operating instructions

Smeg PASC7801FPX quick guide

Smeg

Smeg PASC7801FPX quick guide

Miele DA 7090 W Operating and installation instructions

Miele

Miele DA 7090 W Operating and installation instructions

Fisher & Paykel APEX RH900 installation instructions

Fisher & Paykel

Fisher & Paykel APEX RH900 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.