VPro F User manual

OSRFN23A-EN
1/13
NIPPON VALVE CONTROLS, INC.
Instruction manual
Electric
Actuated Butterfly Valve
F
F
N
F
E
F
P
SP-1519
Please read this manual before installation and use.
GENERAL
It composed of wafer type butterfly valve and high-power electric
actuator. (Proportional control)
Actuator
PDX : For AC / DC power.
PHX : For AC / DC power.
Valve
F type FCD450 body.
FN type FCD450 body.
FE type Aluminum alloy diecast body. (lightweight)
FP type For Corrosion resistance. (Polypropylene body)
PRODUCT CODE
F type F - 1 D - - -
FN type (For JIS 5K / 10K) F N 1 D - - -
FE type F E 1 L T - - -
FP type F P 1 Q Q E - - -
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11)
(1) Actuator
PDX
PHX
(2)
Valve
F- FN FE FP
(3)
Voltage
1 : 100 / 110 V AC
2 : 200 / 220 V AC
0 : 24 V DC
3 : 24 V AC
(4) Sizing code
0 : Standard
1 : Light
2 : Heavy
(5) Connection
1 : JIS 10K
(6) Body material
D : FCD450
L : ADC12
Q : PP
(7) Disc material
D : FCD450
U : SUSF316 / SCS14
A : CAC703
T : SCS13A
J : PPS
Q : PP
(8) Seat material
E : EPDM
B : NBR
V
: FKM
(9) Size [mm]
ex. 80 A ® 080
(10) Option
EA : Alarm output board
EI : 4 to 20 mA
Indication signal board
L0 : Auxiliary limit switch
L2 : Auxiliary limit switch
(11) Operation mode
Nil : Mode A
J : Mode B
(11) Input signal (PDX)
It corresponds to various
control input signals.

OSRFN23A-EN
2/13
VALVES SPECIFICATIONS
Water Oil Air, Gas Steam Chemicals Sea water Slurry Negative pressure
F FN FE FP type
Valve type F FN FE FP
Design Wafer type Wafer type Wafer type Wafer type
Connection JIS Flanges 10K JIS Flanges 5K / 10K JIS Flanges 10K JIS Flanges 10K
Fluid
Max pressure 1 MPa 0.5 MPa 1 MPa 0.98 MPa 1 MPa 0.7 MPa
Size [mm] 050 to 250 300 050 to 200 040 to 300 040 to 150 200 to 300
Material Body FCD450 FCD450 ADC12 PP
Disc FCD450 (CNi plated)
CAC703
SUSF316 / SCS14
FCD450 (CNi plated)
CAC703
SUSF316 / SCS14
SCS13A PP
Seat EPDM NBR FKM EPDM NBR EPDM NBR EPDM
Stem seal O-ring NBR FKM NBR NBR EPDM
PRESSURE & TEMPERATURE RATING
F FN FE FP
Seat material Fluid temp. Use
EPDM -20 to +80 °C
NBR -10 to +60 °C
FKM -5 to +80 °C
NOTE) • EPDM is not recommended for hydrocarbon-based oil or grease.
• Hot water can be used at temperatures of up to 80 °C (FE: 90 °C). Steam cannot be used.
• CAC703 and EPDM are suitable for seawater. (F, FN)
INHERENT FLOW CHARACTERISTIC
F FN FE FP
Cv
value
(%)
Valve opening
(%)
Cv
value
(%)
Valve opening
(%)
Cv
value
(%)
Valve opening
(%)
Range ability 30:1 Range ability 30:1 Range ability 30:1

OSRFN23A-EN
3/13
ELECTRIC ACTUATOR SPECIFICATIONS
PDX type
Actuator type
(:Voltage code) PDX-300- PDX-700- PDX-02K- PDX-06K-
Voltage 100 / 110 V AC ±10 % 50/60 Hz (Code: 1)
200 / 220 V AC ±10 % 50/60 Hz (Code: 2)
24 V AC ±10 % 50/60 Hz (Code: 3)
24 V DC (Code: 0)
Rated torque [Nm] 21 50 140 400
Operation time [s] 6 to 20, Variable 15 to 50, Variable 30 to 100, Variable 90 to 300, Variable
Power consumption
(Max) [VA]
AC power 100
DC power 80
AC power 150
DC power 120
Motor DC motor (VIC: voltage, current control)
Overload protection Current limiter
Method of operation Proportional control
Input signal 4 to 20 mA 1 to 5 V (Input resistance: 250 ) (Standard)
0 to 5 V 0 to 10 V 2 to 10 V (Input resistance: more than 1 M )
0-135 to 0-1 k Potentiometer input (Applied voltage: 5 V DC)
Operation *¹ [Mode A]
[Mode B]
SHUT by decreased signal « OPEN by increased signal
SHUT by increased signal « OPEN by decreased signal
[Forced open / shut] It takes priority over the input signal.
C-S is ON ® SHUT C-O is ON ® OPEN Common in mode A / B
Indication signal 0 mA : SHUT « 1 mA : OPEN (External load resistance: less than 3 k)
Common in mode A / B
Override switch It takes priority over the input signal. Common in mode A / B
Dry contact / Transistor, Open collector. (Input signal current: 6 mA 15V DC)
Operating range SHUT: 0 to 40% OPEN: 50 to 100%
Resolution Less than 0.5 % Less than 0.2 %
Duty cycle 50% 30 min.
Ambient
temperature -20 to 55 °C
Space heater 3 W
Manual operation Manual over-ride with clutch. (Direct operation / 06K: Operation by manual shaft.)
Enclosure Equivalent to IP65 (IEC 60529)
Housing material Aluminum alloy die cast (acrylic resin baking finish)
Wire connection Terminal Block: M3, Ground terminal: M3
Conduct port 2-G1/2 Attachments: Cable gland (for 6 to 12 mm cable), plug.
*¹ Change by DIP switch. (Standard ® Potentiometer input or 0 to 5 V 0 to 10 V 2 to 10 V)
*² Change by DIP switch. (Standard ® Mode B)

OSRFN23A-EN
4/13
ELECTRIC ACTUATOR SPECIFICATIONS
WIRING
PDX Setting with DIP SW
• Operation
Mode A Mode B
• Input signal
4 to 20 mA / 1 to 5 V
0-135 to 0-1 k
Potentiometer input / 0 to 5 V
0 to 10 V 2 to 10 V
Note) Input signal circuit is non-isolated. Do not connect DC (minus) wire to other DC (minus) common.
ADJUSTMENT OF ACTUATOR
PDX Dead band
Turn the trimmer clockwise for wide the dead band as
necessary. It is useful to prevent the hunting reaction
of actuator. *Each trimmer on a built-in control board.
Operating range
Turn clockwise and adjust valve/damper to open side.
• Adjust the closed position by SHUT trimmer.
• Adjust the open position by OPEN trimmer.
Operating speed (Speed control)
Slow by turn the S.C. trimmer counterclockwise.
Fast by turn the S.C. trimmer clockwise.
At factory shipment, the S.C trimmer is set to the mid
position. Operation time with the override switch
cannot be adjusted with S.C. trimmer.
M
S.LS
O.LS
DIPSW
4
321
ON
OFF
ZERO SPAN
D.B. S.C.
SHUT OPEN
0〜40% 50〜100%
T2
T1
-
+
O
S
C
B
R
W
+
-
-
+
+
-
+
-
R
W
B
R
W
C
B
R
〜
AL(AlarmLED)
Groundterminal(M3)
Motor
(Indicationsignal)
Dead
band Speed
control
(Operationrange)
Potentiometer
1KΩ
Indication
signal
0to1mA
Voltage
100/110VAC
200/220VAC
24VAC
24VDC
OverrideSW
OPEN
SHUT
Positionerboard
Inputsignal
4to20mA
1to5V
Inputsignal
0to5V
0to10V
2to10V
Resistance
input
0-135Ω
to
0-1KΩ
(100/110VAC)
(200/220VAC)
(Rcore
transformer)
4321
ON
OFF
4321
ON
OFF
4321
ON
OFF
4321
ON
OFF
4321
ON
OFF
4321
ON
OFF
ZERO SPAN
SHUT OPEN
D.B.
AL
S.C.
D.B. S.C.
SHUT OPEN
SPANZERO
ON
OFF
(S2) (S3)DIPSW(S1)
1 2 3 4
T1T2 W RBCSO+-
Deadband
wide
Speedcontrol
fast
Operatingrange
open open
Indicationsignal
decrease increase
Positionerboard
PDX
SHUT
LED
OPEN
LED

OSRFN23A-EN
5/13
ELECTRIC ACTUATOR SPECIFICATIONS
PHX type
Actuator type
(:Voltage code) PHX-300- PHX-700- PHX-02K- PHX-06K-
Voltage 100 / 110 V AC ±10 % 50/60 Hz (Code: 1)
200 / 220 V AC ±10 % 50/60 Hz (Code: 2)
24 V AC ±10 % 50/60 Hz (Code: 3)
24 V DC (Code: 0)
Rated torque [Nm] 21 50 140 400
Operation time [s] AC: 1.2 to 2.5
DC: 2 to 2.5
(Max 8)
AC: 3.5 to 7
DC: 4.5 to 7
(Max 22)
AC: 11 to 23
DC: 15 to 23
(Max 78)
AC: 35 to 70
DC: 45 to 70
(Max 230)
The operation time is the time when it is operated by the override switch.
Operation time with the override switch cannot be adjusted with S.C. trimmer.
At factory shipment, the S.C trimmer is set to the fastest position.
Power consumption
(Max) [VA] 120
Motor Brushless DC motor (PWM Control)
Overload protection Current limiter
Method of operation Proportional control
Input signal 4 to 20 mA / 1 to 5 V (Input resistance: 250 )
Operation *¹ [Mode A]
[Mode B]
SHUT by decreased signal « OPEN by increased signal (Standard)
SHUT by increased signal « OPEN by decreased signal (Option: J)
[Forced open / shut] It takes priority over the input signal.
C-S is ON ® SHUT C-O is ON ® OPEN Common in mode A / B
Indication signal 0 mA : SHUT « 1 mA : OPEN (External load resistance: less than 3 k)
Common in mode A / B
Override switch It takes priority over the input signal. Common in mode A / B
Dry contact / Transistor, Open collector. (Input signal current: 6 mA 15V DC)
Operating range SHUT: 0 to 40 % OPEN: 50 to 100 %
Resolution Less than 0.2 %
Duty cycle 100 %
Ambient temperature -20 to 55 °C
Space heater 3 W
Manual operation Manual over-ride with clutch. (Direct operation / 06K: Operation by manual shaft.)
Enclosure Equivalent to IP65 (IEC 60529)
Housing material Aluminum alloy die cast (acrylic resin baking finish)
Wire connection Terminal Block: M3, Ground terminal: M3
Conduct port 2-G1/2 Attachments: Cable gland (for 6 to 12 mm cable), plug.
*¹ Change by DIP switch. (Standard ® Mode B)

OSRFN23A-EN
6/13
ELECTRIC ACTUATOR SPECIFICATIONS
WIRING
PHX Setting with DIP SW
• Mode setup
Mode A Mode B
• AC / DC mode change
ON ® AC power OFF ® DC power
Note) AC / DC mode change is
Factory-adjusted.
Note) Input signal circuit is non-isolated. Do not connect DC (minus) wire to other DC (minus) common.
ADJUSTMENT OF ACTUATOR
PHX Dead band
Turn the trimmer clockwise for wide the dead band as
necessary. It is useful to prevent the hunting reaction
of actuator. *Each trimmer on a built-in control board.
Operating range
Turn clockwise and adjust valve/damper to open side.
• Adjust the closed position by SHUT trimmer.
• Adjust the open position by OPEN trimmer.
Operating speed (Speed control)
Slow by turn the S.C. trimmer counterclockwise.
Fast by turn the S.C. trimmer clockwise.
Note) The operation time is the time when it is operated
by the override switch.
Operation time with the override switch cannot be
adjusted with S.C. trimmer.
At factory shipment, the S.C trimmer is set to the
fastest position.
-
+
O
S
C
I+
I-
T2
T1
1
DIPSW
OFF
2 3
ON
ZERO SPAN
D.B. S.C.
SHUT OPEN
0〜40% 50〜100% S.LS
O.LS
M
+
-
-
+
+
-
AL(AlarmLED)
Dead
band Speed
control
Potentiometer
1KΩ
Brushless
DCmotor
Groundterminal(M3)
(Indicationsignal)
(Operationrange)
Indication
signal
0to1mA
Voltage
100/110VAC
200/220VAC
24VAC
24VDC
Inputsignal
4to20mA
1to5V
OverrideSW
SHUT
OPEN
Positionerboard
(100/110VAC)
(200/220VAC)
(Rcore
transformer)
1
OFF
2 3
ON 1
OFF
2 3
ON
1
OFF
2 3
ON 1
OFF
2 3
ON
DIPSW
1
ON
OFF
T1T2I-I+CSO+-
2 3
ZERO SPAN
SHUT OPEN
D.B.
AL
S.C.
D.B. S.C.
SHUT OPEN
SPANZERO
Deadband
wide
Speedcontrol
fast
Operatingrange
open open
Indicationsignal
decrease increase
Positionerboard
PHX

OSRFN23A-EN
7/13
ELECTRIC ACTUATOR SPECIFICATIONS
OPTIONAL PARTS
Specifications Code No. PDX PHX Remarks
Input signal 4 to 20 mA or 1 to 5 V Nil Mode A (Standard)
and J Mode B
operation 0-135 to 0-1 k Potentiometer input or 0 to 5 V F Mode A
K Mode B
0 to 10 V G Mode A
N Mode B
2 to 10 V H Mode A
M Mode B
Auxiliary limit switch L0 For standard signal
(Select limit switch depending on the load) L2 For micro load signal
Alarm output board EA EI and EA
4 to 20 mA Indication signal board EI cannot be used together.
*Auxiliary limit switch: Please refer to the specifications.
WIRING (OPTION)
L0, L2 Auxiliary limit switch EA Alarm output board EI 4 to 20 mA Indication signal board
At CLOSE side, LC and LS is ON.
At OPEN side, LC and LO is ON.
ON point can be reset by
adjusting the cam.
NO : Normally open
NC : Normally closed
Alarm SW will be ON, when
overload protector works.
Error ® 11 and 12 is ON.
Normal ® 11 and 13 is ON.
Cannot be used with EI option.
The angle range of 4 to 20 mA can be
adjusted by ZERO / SPAN trimmer on
control board. Output signal (0 to 1 mA)
cannot be used together.
com.
LO
LS
OLS
SLS
LC
SHUToutput
OPENoutput
Actuatorwiring
OLSSLS
OFF
ON
SHUT OPEN
13
12
11com.
NO
NC
Actuatorwiring
Alarmoutput
board
-
+
12
11
-
+
ZERO SPAN
+
-
+
-
4〜20mA
Actuatorwirin:PDX,PHX
Actuator
Positionerboard
4〜20mA
EIOption
Unavailable
0〜1mA

OSRFN23A-EN
8/13
ELECTRIC ACTUATOR SPECIFICATIONS
DIMENSIONS
PDX PHX
Parts name
1 Body 5 Terminal block 9 Transformer 13 Rubber packing
2 Motor cover 6 Limit switch 10 Drive shaft
3 Motor 7
SW setting cam
11 Manual clutch
4 Control board 8 Potentiometer 12 Manual shaft (For 06K)
11
58
7
6
9
12
13
2
3
4
1
10
PDX-300, 700 PDX-02K PDX-06K
PHX-300, 700 PHX-02K PHX-06K 175
220
115
217.5
156
2-G1/2
105
175
160
92.5
189
115
2-G1/2
105
175
160
92.5
167
115
2-G1/2
3 8
13
5
9
6
7
1
11
10
1
11
10
2
4
3 8
13
5
9
6
7
2
4

OSRFN23A-EN
9/13
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
HANDLING & STORAGE
HANDLING
Do not drop or throw the product as it may break.
STORAGE
• Store away from dust, moisture and direct sunlight.
If possible, store in the original package.
• Do not remove a dust proof cap until the piping.
CHECKING
• Check the product code, power supply, and voltage
before installation.
• Make sure that the bolts are not loose.
• The DIP switch should be set up before the power is
turned on. Do not touch unnecessary switches.
INSTALLATION
PRECAUTIONS
• Flush the pipeline carefully before installing the valve.
Foreign particles, such as sand or pieces of welding
electrode, will damage the disk and seats.
• Seat has ribs for tight gasket seating. Do not use
gasket.
• Valve is shipped closed. (allows quick piping.)
• The butterfly valve should be piped upstream of the
elbow. When piping downstream from the elbow,
considered a straight line that is at least five times
the length of the pipe.
• The valve stem should be mounted perpendicular to
the flow for biased fluid.
• Disc interference may also occur when valve is
installed in pipeline with smaller than normal inside
diameter such as thick wall pipe, or lining pipe.
Suitable corrective measurement must be taken (taper
boring the pipe or pipe liner, etc.)
• When you use a vinyl chloride flange, there is a
caliber to be internal off the corners. Please cut off
the corners with reference to the following. (F, FN)
Valve size [mm] Chamfer
[mm]
FN F
150 150 1.5
- 200 2.5
- 250 3
- 300 2
• Avoid oil or grease when using EPDM seat.
PIPING FLANGES (F, FN, FE)
• Class JIS 5K and JIS 10K pipe flanges can be used
for FN series. See the drawing below for centering the
valve with bolts.
JIS 5K JIS 10K
• Wafer type butterfly valve is put between two seats of
flanged-end and tightened with long bolts.
• Before bolts are tightened, valve should be centered
within the bolts to prevent possible disc interference or
damage by contact with the pipe or flange.
• Tighten all bolts using crossover method to load the
joint evenly.
• When using a resin flange, if the connecting bolt is
tightened too much, the flange may deform and
leak.
Valve size [mm] Recommended
torque [N
·
m]
F FN FE
050
065
080
100
050
065
080
100
040
050
065
080
100
20
125
150
200
125
150
200
125
150
200
25
250
300 - 250
300 30
Slow Fast Slow Fast

OSRFN23A-EN
10/13
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
CAUTION ON PLASTIC VALVE (FP)
Flange connection
• Use same material as same as opposite piping
flanged. For metal piping, use flanged washer
and it is considered that there is no heavy piping
stress.
• When the piping, wick gap between a pipe and a
valve and a bending cause by an angle
difference, it may cause switching incompatible
breakage, and leakage from fluid.
• Shaft, face to face dimension distance and
flanged angle unit correctly.
• Use the flanged bolt on by bolt side and nut
side, tighten all bolts using crossover method to
load the joint evenly.
Valve size [mm] Recommended
torques [N
·
m]
040
050
065
080
20
100
125
150
25
200
250
300
60
Expansion measure of pipe line
• Heat expansion occurs in pipe line depends on
by temperature change after piping and
temperature condition of internal fluid.
Compression or contraction by heat stress acts
also on a valve. Especially for metal piping, it
happens to plastic valve as weak in intensity.
Perform expansion treatment before or after a
valve and it is considered that a burden is not
placed on valve.
ENVIRONMENT
• Do not install in place where corrosive gas is present
or where vibration is heavy (0.5 G or more).
• When radiant heat causes the surface temperature of
the control unit to exceed 55 °C, provide an
appropriate shielding plate.
• If there is a possibility that the fluid and drive part
freeze, please take measures to prevent freezing.
POSITIONING
Should be positioned through 90° upward from
horizontal. Provide space around the product to allow
manual operation, inspection and replacement work.
Maintenance space for upper part of actuator.
PDX PHX More than 120 mm
OTHER NOTES
Until the wiring is completed there must be no
condensation or flooding in the interior of the actuator,
after piping. Protective caps on the cable gland are
not waterproof.

OSRFN23A-EN
11/13
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
WIRING
PRECAUTIONS
• Remove the actuator cover before wiring.
• Two G1/2 electrical connections are provided with a
cable gland and plug. Usable cable size is 6 to 12
mm.
• When using a flexible tube, dew condensation may
occur inside the actuator due to respiration from the
inside of the tube and malfunction may result. Seal the
flexible tube connector part with a sealant.
• Sealants that affect the electrical contacts should not
be used inside the electric actuator.
• If long distance wiring or low voltage operation, check
that terminal voltage is in the proper range.
• Input signal circuit is non-isolated.
Do not connect DC (minus) wire to other DC (minus)
common.
CONNECTION
• Do not wiring outdoors on a rainy day.
• Check the power supply and voltage.
Connect the signal as shown in the wiring diagram.
Do not connect unnecessarily terminal.
• Check whether the MODE change DIP SW on a
circuit board substrate is set up correctly.
• When wiring, if wiring of a signal is mistaken, it will not
operate correctly. Contact us when you use two valve
or more by one controller or indicator.
• Actuator should be electrically grounded.
Use the terminal marked ( ) inside the actuator.
PREVENT DEW CONDENSATION
• When installing the cover after wiring, perform the bolt
by the temporary tightening procedure and the
permanent tightening procedure to tightly and securely
tighten the rubber packing so that water does not
enter from the outside.
• Tighten the cable gland nut so that there is no leakage
from the wire entrance.
CONTROL
INPUT SIGNAL
• Use shielded wire for signal wiring where high level
noise is generated or when the wiring distance is long.
• Control with a 1 to 5 V input signal becomes an input
resistance 250 . Provide a voltage that can safely
20mA or more than.
DC POWER SUPPLY
• Battery or full wave rectification can be used.
• Consider an inrush current of motor.
(It is 1.5 to 3 times of consumed current.)
• When using a DC voltage, be selected the wire
thickness by the wiring distance.
• Do not use power supply that require more than
1 second with rise and fall time.
INPUT SIGNAL AND OPERATION MODE
The input signal and operation mode are set as
follows. (Factory shipped)
Input signal 4 to 20 mA or 1 to 5 V
Operation mode Mode A
Operation SHUT by decreased signal.
OPEN by increased signal.
OPERATION
TESTING
• Make sure that power supply voltage is correct. Also
check operating position, wiring, speed and signals.
• During trial operation, check that valve movement and
output signal are correct.
CONFIRM THE OPERATING CONDITION
• Adjust fluid condition, controller setting, sensor etc. so
that stable control is achieved.
• When used in an unstable control state, the life of the
actuator and the valve will be shortened.
• The desired control state is stable at the target value.
Adjust the PID setting value of the controller when
overshooting the target value greatly, when not
converging for a long time or hunting operation. Also,
when the time delay is large, please consider the
sensor position.
DUTY CYCLE (PDX)
Confirm that the operation frequency is within the
specified duty cycle.
Use beyond the load time rate range will affect
product life. Also, it may cause burnout.
Duty cycle is a value that regulates the opening /
closing frequency of the actuator.
The meaning of 50 % 30 minutes for Duty cycle is
that 15 minutes (50 % of 30 minutes) operation is
possible. The calculated value obtained by dividing
15 minutes by the operation time is the number of
times of operation within 30 minutes.
ATTENTION
• Do not change an unnecessary dip switch.
• Keep power supplied for built-in space heater to
prevent condensation inside actuator.
• Do not touch the moving parts of actuator in
operation.
• Never put anything on the actuator or make it into a
foothold.

OSRFN23A-EN
12/13
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
MANUAL OPERATION
PRECAUTIONS
• Be sure to turn off the power before manual operation.
• Operate manually with reference to the opening
degree label. Do not turn beyond the fully open / fully
closed position. Operation failure may occur during
automatic operation.
THE WAY OF OPERATION
PDX PHX (06K)
Manual operation can be possible by pulling down
manual clutch knob. Set the knob to manual
position and operate the joint by using an
adjustable wrench in the SHUT/OPEN direction.
When it becomes in the position besides the range
of operation in the case of manual operation, it may
stopped automatic moving.
In case the manual clutch knob is not easy to pull
down, try moving joint or manual shaft to the
opposite direction by wrench. For automatic
operation, reset the knob to automatic position.
Be sure to confirm that knob is reset completely.
Before automatic operation, be sure to remove
wrench.
MAINTENANCE
• To prevent electric shock, be sure to turn off the power
when removing the actuator cover.
• Do the routine maintenance at least once in half a
year.
Inspection items
• Confirm operation of opening and closing.
• Confirm that an actuator is not hot excessively.
• Confirm existence of abnormal noise and
vibration during operation.
• Confirm whether screws are loose or not.
• Confirm that water or condensation no remains
in the actuator.
• Confirm the fluid temperature or pressure.
• Confirm the leak from valve stem.
• Confirm the bolt tightening torque.

OSRFN23A-EN
Document is subject to change without notice.
NIPPON VALVE CONTROLS, INC.
1-21-19 Meieki minami, Nakamura-ku, Nagoya 450-0003 JAPAN
TEL: 81-52-582-6435 FAX: 81-52-582-6439
13/13
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
TROUBLE SHOOTING
Problem Cause Solution
Actuator
does not
move.
Faulty wiring. Correct the wiring.
Voltage and
input signal are
not coming.
Check the voltage and
input signal.
Incorrect
voltage.
When it's burned out by
excess voltage, replace
the actuator.
Connection or
wiring is not
correct.
Correct the miswiring
and misconnection.
Be careful not to
mistake the plus and
minus of wiring.
Short the
circuit, contact
failure.
Review wires and
connection.
Motor is too
old.
Replace the actuator.
Repair in our factory.
LED lamp (S or O) on
the board is lit, but the
motor does not move.
PDX
Operation is
unstable.
Excess surge
or voltage was
applied.
• Replace the control
board or limit switch.
(Repair in our
factory)
• Replace the actuator.
Rainwater
entered the
actuator.
• Dry the inside.
• Replace the actuator.
Added high
harmonics
noise from an
inverter.
Attachment a filter for
each inverter maker
option.
Effect of high
level noise.
Use the shielded wire
and ground the wiring.
Separate signal wire
from power line.
Stop in the
mid position.
(Input signal
1 to 5 V)
Signal voltage
source capacity
shortage.
Use a voltage source
that can be made to
flow more than 20 mA.
Please contact us.
Problem Cause Solution
Stop in the
mid position.
There is a
foreign object in
the butterfly
valve.
Remove a foreign
object.
Valve is
distorted.
Replace the valve.
Overload
protector runs
because of
over-torque.
Motor protection circuit
returns by the signal of
operation of an
opposite direction. Turn
on the power again.
Alarm LED
is lit.
Stop
automatic
moving after
manual
operation.
Manual clutch
knob is not
reset.
Reset manual clutch
knob.
Out of
operating
range. (06K)
Reset by manual
operation.
Leakage
from seat
Damaged on
valve seat.
Replace the valve.
Replace the seat
F
Leakage
from stem
O-ring is worn. Replace the valve.
Replace the O-ring
F
For more information contact
NIPPON VALVE CONTROLS, INC. for consultation.
This manual suits for next models
3
Table of contents
Other VPro Control Unit manuals
Popular Control Unit manuals by other brands

Garden Controls
Garden Controls LIGHT TIMER user guide

Rockwell Automation
Rockwell Automation 1797-IE8 installation instructions

Habasit
Habasit PMR-07 General manual use and maintenance

ICP DAS USA
ICP DAS USA ECAT-201x EtherCAT Slave I/O user manual

Moxa Technologies
Moxa Technologies MiiNePort W1 Series user manual

HOLOVISION
HOLOVISION 101 Installation instructions manual