Westlock ICoT PA Installation instructions

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 1 of 206
ICoT PA
INTELLIGENT VALVE POSITIONER
INSTALLATION & OPERATING
MANUAL
IOM: Tech-477 Revision:
Prepared By: Leiser
Marcos de Souza
Date:
4/1/2015
Drafting Work Order:
21424
ECN:
Reviewed By: Jason
Moorehead
Date: 6/2/15 Approved By: Adam Buga
Date:6/17/15
This IOM contains confidential information and is issued in confidence on the condition that it be returned on demand and not be
copied, reproduced, disclosed to others or used in manufacture of the subject matter thereof without the written consent of Westlock

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 2 of 206
Revision History
Revision
4/1/15
Initial release
Westlock Controls Offices
USA
Westlock Controls Corp.
280 North Midland Ave, Suite 258, Saddle Brook, NJ 07663
Phone: (201) 794-7650 •Fax: (201) 794-0913
Email: [email protected]
Internet http://www.westlockcontrols.com
Europe
Westlock Controls UK
22 Chapman Way, Tunbridge Wells
Kent, England TN23EF
Phone: 011-44-189-251-6277 •Fax: 011-441-892-516279
Email: [email protected]
Internet: http://www.westlockuk.com
South America
Westlock Equipamentos de Controle Ltda.
Sales:
Al. Araguaia, 2044 – Sl. 1101, Bloco B
Edifício CEA – Alphaville
Barueri – São Paulo – Brazil
06455-000
Tel: + 55 11 2588-1400
Fax: + 55 11 2588-1410
Email: [email protected]
Internet: http://www.westlock.com.br
Operations:
Av. Antonio Bardella, 3000
Galpões 2A e 2B – Alto da Boa Vista
Sorocaba – São Paulo – Brazil
18085-852
Tel: + 55 15 2102-7400
Fax: + 55 15 2102-7400
Asia
Westlock Controls Singapore
Sales:
King's Centre #04-01
390 Havelock Road
Singapore
169662
Phone: +65 676 858 00 •Fax: 011-441-892-516279
Email: [email protected]
Internet: http://www.westlockuk.com

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 3 of 206
TableofContents
1Introduction ............................................................................................................ 8
1.1Product Certification........................................................................................... 8
1.2Warnings............................................................................................................ 8
1.3Description ......................................................................................................... 9
1.4Principles of Operation..................................................................................... 10
1.4.1Enclosures................................................................................................. 10
1.4.2Position Feedback ..................................................................................... 10
1.4.3Local Graphic LCD .................................................................................... 12
1.5Special Features .............................................................................................. 12
2Technical Specifications ...................................................................................... 13
3Order Guide ......................................................................................................... 14
4Definitions ............................................................................................................ 15
5Installation............................................................................................................ 19
5.1Mounting Positioner on a Rotary Actuator........................................................ 19
5.2Mounting Remote Positioner on a Rotary Actuator .......................................... 21
5.3Mounting Positioner on a Linear Actuator ........................................................ 23
5.4Mounting Remote Positioner on a Linear Actuator........................................... 25
5.5Pneumatic Connection ..................................................................................... 27
5.6SPECIAL NOTE Flow Capacity........................................................................ 28
5.7Setting of switches on a rotary ICoT ................................................................ 28
5.8Calibration ........................................................................................................ 29
5.8.1Enter Calibration (Menu Level) .................................................................. 29
5.8.2Automatic Calibration (ACAL).................................................................... 30
5.8.3Manual Calibration (MCAL) ....................................................................... 31
5.8.4Configure the Positioner’s Parameters (Cofg) ........................................... 32
5.8.5Manual Override of Input Signal via On-Board Keypad (Stro) ................... 34
5.8.6Node Address Assigning (Node Add) ........................................................ 34
5.9Description of Menus ....................................................................................... 35
5.9.1Description of Functions ............................................................................ 36
6Field Wiring.......................................................................................................... 40
7Maintenance and Repair...................................................................................... 41
7.1Preliminary Checks .......................................................................................... 41

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 4 of 206
7.1.1Voltage ...................................................................................................... 41
7.1.2Electrical Connection................................................................................. 41
7.1.3Pneumatic Connection............................................................................... 42
7.1.4Magnetic Position Feedback...................................................................... 42
7.1.5Supply Pressure ........................................................................................ 42
7.1.6Positioner Pressure Rating ........................................................................ 42
7.2FAQ’s ............................................................................................................... 43
7.3LCD Alert Codes and Error Messages ............................................................. 44
7.3.1LCD Alert codes ........................................................................................ 44
7.3.2LCD Error Messages ................................................................................. 44
8Fieldbus Network ................................................................................................. 52
8.1PROFIBUS Overview....................................................................................... 52
8.1.1About PROFIBUS PA ................................................................................ 52
8.2PROFIBUS PA – Profile................................................................................... 52
8.3The Function Blocks Application ...................................................................... 52
8.3.1Block Modes .............................................................................................. 53
8.3.2Common Parameters................................................................................. 55
8.3.3Quality and Status ..................................................................................... 55
8.3.4Read Back ................................................................................................. 55
8.3.5Fault State ................................................................................................. 55
8.3.6Slot ............................................................................................................ 56
8.3.7The Physical Block .................................................................................... 56
8.3.8Transducer Block....................................................................................... 57
8.3.9Analog Input Block..................................................................................... 77
8.3.10Analog Output Block............................................................................... 78
8.4Cyclic Data Exchange ...................................................................................... 79
9DTM ..................................................................................................................... 82
9.1Description ....................................................................................................... 82
9.2Initial Setup ...................................................................................................... 82
9.2.1ICoT PA DTM installation .......................................................................... 82
9.2.2Creating a PACTware project .................................................................... 84
9.2.3Writing Data to Device............................................................................... 87
9.2.4Reading Cyclic........................................................................................... 88

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 5 of 206
9.2.5Manipulating graphs .................................................................................. 88
9.3Calibration and Configuration........................................................................... 90
9.3.1Identification .............................................................................................. 90
9.3.2Transducer ................................................................................................ 91
9.4Variables .......................................................................................................... 99
9.4.1Trend Curve display .................................................................................. 99
9.4.2Process Variables.................................................................................... 100
9.5Diagnostics..................................................................................................... 100
9.5.1Simulation Analog Output ........................................................................ 100
9.5.2Simulation Analog Input........................................................................... 101
9.5.3Alert ......................................................................................................... 101
9.5.4Full Stroke Test ....................................................................................... 104
9.6Diagnosis ....................................................................................................... 105
9.6.1Device Diagnosis..................................................................................... 105
9.6.2Alarm AO ................................................................................................. 107
9.6.3Alarm AI................................................................................................... 108
9.7Adjust Value ................................................................................................... 110
9.7.1Servo PID Manual Tuning........................................................................ 110
9.7.2Servo PID Step response ........................................................................ 111
9.7.3Analog Output.......................................................................................... 112
9.7.4Analog Input ............................................................................................ 113
9.8Characterization Curve .................................................................................. 114
9.9PA Profile ....................................................................................................... 115
9.9.1Physical Block ......................................................................................... 115
9.9.2Transducer Block..................................................................................... 120
9.9.3Function Analog Output Block ................................................................. 128
9.9.4Function Analog Input Block .................................................................... 132
10EDD ................................................................................................................... 138
10.1Description.................................................................................................. 138
10.2Initial Setup ................................................................................................. 138
10.3Calibration and Configuration ..................................................................... 139
10.3.1Identification ......................................................................................... 139
10.3.2Basic Setup .......................................................................................... 140

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 6 of 206
10.3.3Advanced Setup ................................................................................... 141
10.3.4Feedback Configuration ....................................................................... 141
10.3.5Units ..................................................................................................... 142
10.3.6Valve and Actuator Info ........................................................................ 143
10.3.7Calibration ............................................................................................ 143
10.3.8Slew Rate Setup................................................................................... 145
10.3.9Clock .................................................................................................... 146
10.3.10LCD Contrast, Serial Number, Revision ............................................... 148
10.3.11Servo PID Tuning ................................................................................. 150
10.3.12Characterization Curve......................................................................... 154
10.4Process Variables & Trend Curves............................................................. 157
10.4.1Process Variables ................................................................................ 158
10.4.2Trend Curve display ............................................................................. 159
10.4.3Readback & Setpoint (AO) ................................................................... 160
10.4.4Output (AO).......................................................................................... 161
10.5Diagnostics ................................................................................................. 162
10.5.1Update diagnostics............................................................................... 162
10.5.2Device Status ....................................................................................... 162
10.5.3Alert...................................................................................................... 164
10.5.4Full Stroke Test .................................................................................... 167
10.6PA Profile – Block View .............................................................................. 168
10.6.1Physical Block ...................................................................................... 169
10.6.2Function Analog Output Block .............................................................. 173
10.6.3Transducer Block ................................................................................. 178
10.6.4Function Analog Input Block................................................................. 186
11References ........................................................................................................ 191
12Appendix A – Procedure to Adjust the Low Pressure Setting ............................ 192
13Appendix B – Procedure to Remove Electronics Cover and Electronic
Canister ............................................................................................................. 193
14Appendix C – Procedure to Check Transducer Operation ................................. 194
15Appendix D – General Maintenance Standard Flow .......................................... 195
16Appendix E - Grounding Schematic ................................................................... 198
Appendix F – Controlled Drawing ...................................................................... 199

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 7 of 206
17Appendix G – Procedure to Reset the Non-Volatile Memory to Factory
Settings.............................................................................................................. 201
18Appendix H - Controlling the ICoT PA Position using the Proficore Ultra
Interface, ProfiCaptain software......................................................................... 202

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 8 of 206
1 Introduction
1.1 Product Certification
IEC Ex FMG 06.0002x
Ex ia IIC T4
(Tamb = -40°C to +80°C)
II 1 G
Ex ia IIC T4
II 1 G
(Ta = -40°C to +80°C)
FM09 ATEX 0028
IS / I,II,III / 1 / ABCDEFG / T4 Ta = 85°C
WD-11704; Entity; Type 4,
10/AEx ia/Ex ia/IIC/T4 Ta= 80°C
WD-11704; Entity; Type 4X
NI/I /2 /ABCD;S/II, III/2/FG/ Ta= 85°C Type 4
This product is designed for use in intrinsically safe systems when
connected through the correct barriers.
1.2 Warnings
Never remove enclosure cover or make/break electrical connections
with power connected to the unit.
Perform all wiring in accordance with site and local codes and the
National Electric Code ANSI-NFPA-70 (US) or the Canadian Electric
Code Part I (Canada) for the appropriate area classifications.
Confirm that the ICoT POSITIONER model being installed is approved
for the hazardous area (consult unit identification label).
Ensure that approved and properly sized IS barriers are used in
installations with IS approved ICoT POSITIONERS (confirm entity
parameters from product ID label).
Confirm that power supplied to unit is within rated specifications listed
on the unit identification label.
Protect the unit from exposure to aggressive substances or
atmospheres to ensure that hazard rating is not compromised.
Disconnect power to and the inlet air supply before conducting any
service or maintenance. Avoid the introduction of any contaminants
into the manifold/valve assembly.

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 9 of 206
1.3 Description
The ICoT 5500 (ICoT PA) provides intelligence for the
control valve through a microprocessor-based system
utilizing the PROFIBUS PA protocol. Accurate
measurement of valve stem position, input signal,
actuator pressure, cycle time and cycle count data can
be recorded during normal operation.
The positioner has a local LCD display, which indicates
valve position, set-point in percentage open, calibration
status, alarms status and whether the ICoT is in local or
fieldbus control. If a failure condition occurs, an error
message is displayed on the local LCD display and
communicated to the Host system via fieldbus.
The ICoT PA is an electro-pneumatic servo system that
continuously controls the position of a valve based on
the fieldbus input signal. The ICoT senses valve position
via a non-contact Hall Effect sensor and controls valve
position through a current to pressure transducer
The ICoT PA is a two wire, polarity insensitive
instrument that receives both signal and power from the bus. Current consumption of the
ICoT is 12.5mA with an operating voltage of 9 – 32 Vdc.
The ICoT PA version allows calibration and access to on-line diagnostic information via
hand-held terminal or through software.
A set of hermetically sealed non-contact limit switches is an option that can be integrally
supplied with the ICoT PA.

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 10 of 206
1.4 Principles of Operation
1.4.1 Enclosures
The ICoT PA Positioner can be built in three different enclosure materials: engineered
resin, 316 stainless steel and aluminum.
1.4.2 Position Feedback
Non-Contact Position Feedback
To provide consistently accurate performance information, all linkages, levers and
connecting rods, from the positioner to the control valve have been eliminated from
the design. Valve position sensing is performed totally by non-contacting means
based upon characterization of magnetic flux strength as a function of position.
Housing
Material:
Housing
Material:
316 Stainless

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 11 of 206

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 12 of 206
Remote Position Control
Since valve position feedback to the ICoT PA positioner is
accomplished by non-contacting means, the ICoT PA has
the unique ability to be mounted remotely (up to a distance
of 50 feet, optionally 150 feet) from the device it is
controlling. In the event the control valve is located in a high
vibration or extremely corrosive environment, the non-
contact position feedback feature allows for isolated
placement of the positioner.
1.4.3 Local Graphic LCD
The ICoT PA
positioner is supplied with a digital
communication interface PA or a 3-button keypad interface. Both
versions are furnished with a graphic LCD, and allow for automated
calibration of the positioner. The local LCD provides a multitude of
onsite diagnostic information. The LCD shows input current, set-
point and current position. The values displayed range from 0.0% to
100.0%. Displayed resolution is in 0.1% increments, however,
internal calculations are maintained at higher precision.
1.5
Special Features
On-Board Sensors
The ICoT PA positioner has the capability to monitor its operation. If an error or failure condition
occurs, it will be displayed on the local LCD, or if the positioner is supplied with a PA interface,
the error codes will be displayed on a hand held terminal or a PC maintenance station.
Note: Error codes are denoted on a label affixed to the LCD flip-up protective cover.
Local Keypad
The positioner is provided with a ruggedized 3-button keypad. The keypad can be
used for zero and span adjustments, as well as valve characterization and gain
adjustments.
Intelligent Calibration via PA
The parameters of the ICoT PA-IS positioner are fully accessible via PROFIBUS.
Manual or Automatic calibration can be initiated via the bus and parameters for altering internal
servo loop tuning are fully configurable. In this manner, positioner performance may be
optimized with a wide combination of valves and actuators via PROFIBUS.
Negligible Bleed
Designed to consume the least possible amount of control air at steady state, the ICoT 5500
Series positioner can greatly reduce the air consumption of your process and reduce the
demand on instrument air compressors. To increase reliability, the ICoT PA employs a patented
Westlock Controls
ICoT PA Rev 1.01.00
25.5°C
R %PS 50.0 %SP 50.0
PA-CTR
OK

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 13 of 206
lapped spool and floating sleeve design. This balanced construction relies on an air bearing
which eliminates any metal to metal contact.
2 Technical Specifications
Input
Signal: Two wire PROFIBUS PA
Voltage: 9 to 32 VDC (Max 35V)
Current Consumption: 12.5 mA
Pressure: 15 - 45 psi (Low)
40 - 120 psi (High)
Instrumentation air quality must be in
accordance with ISO 8573-1 “Air Quality
Standards”
(See Pneumatic Connection Section 5.5
for more details)
Output
Flow Rate: 8.0 scfm @ 25 psi (Low)
16.2 scfm @ 90 psi (High)
Pressure: 0 to 45 psi (Low)
0 to 120 psi (High)
Actuator: Single Acting or Double Acting
Performance
Resolution: ± 0.2% Full Travel
Linearity: ± 0.5% Full Scale (Rotary)
± 1.0% Full Scale (Linear)
Hysteresis: ± 0.2% Full Scale
Repeatability: ± 0.2% Full Scale
Operating Temp: -40C to 85C
(-40F to 167F)
LCD readable:-20C to 70C
(-40F to 158F)
Thermal Coefficient: ± 2% / 100C
Air Consumption:
0.03 scfm @ 25 psi (Low)
0.08 scfm @ 90 psi (High)
Stroke: 0.25 to 24 inches (Linear)
45 to 95 degrees (Rotary)
Position Feedback: Magnetic (Non-
Contact)
Diagnostics:
PROFIBUS PA Protocol,
Software Utilizing PROFIBUS PA
Protocol
Enclosure
Material: Engineered Resin, Aluminum,
Stainless Steel
IP Rating: IP 66
Weight: 3.3 Kg / 7.2 Pounds (resin,
standard flow manifold)
Air Connections:
1/4” NPT or 1/4”BSP (STD Flow)
3/8”NPT or BSP (High Flow)
Conduit Connection:
1/2” NPT (Standard)
M20 (Optional)
EMC (Electromagnetic Compatibility)
IEC 61000-6-2:2005 Electromagnetic
compatibility (EMC) – Immunity for
industrial environments

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 14 of 206
IEC 61000-6-4:2006 Electromagnetic
compatibility (EMC) – Emission
standard for industrial environments
IEC 61326-2:2005 Electrical equipment
for measurement, control and laboratory
use - EMC requirements
3 Order Guide
The ICoT PA positioner is designed to handle a wide range of control valve applications. Please use the
following ordering guide to help choose the ICoT positioner that best suits the application.
ICoT 5500 (ICoT PA) Positioner Ordering Guide
INTELLIGENT POSITIONERS PROFIBUS PA
ICoT 5500
SEE BELOW FOR HAZARDOUS RATINGS
Base Model
55 PROFIBUS PA
Actuator Type
1 Linear* (Free magnet assy. Include up to 2-1/2” stroke; strokes>2-1/2”, consult factory)
3 Rotary
Mounting Style
0 Direct Mount (ICoT mounted on actuator)
5 Remote Mount (ICoT mounted remote from actuator)
7 NAMUR Mount (order with stainless NAMUR mounting kit separately)
8 Mod Mount (for Tyco MRP and 79U actuators only; supplied with mounting kit)
Hazardous Rating
NI Non-incendive (Class I, Div. 2, Groups A, B, C, D Class II, Div. 2, Groups F, G)
IS Intrinsically Safe (Class I, Div. 1 & 2, Groups A, B, C, D Class II, Div. 1, Groups E, F, G with approved I.S. barrier)
AI Intrinsically Safe – ATEX EX ia IIC T4 approved
II Intrinsically Safe – IEC Ex ia IIC T4 approved
Housing Material
E Engineered Resin
S 316 Stainless Steel (Not listed for Hazardous Rating. Pending Approvals) (Mounting Style 0 & 5 only)
A Aluminum (Not listed for Hazardous Rating. Pending Approvals) (Mounting Style 0 & 5 only)
Supply Pressure
H High Pressure (40-120 psi)
L Low Pressure (15-45 psi)
V High Flow (40-120 psi, for larger actuators)
S Super High Flow (40 – 120 psi, 5.5 CV)
Calibration/Communication
P 3-button on-board keypad & PROFIBUS PA Protocol
Conduit Entry
A One 1/2" NPT (F)
B One M20 (F)
Limit Switch Options
0 None
2 Two SPST hermetically Sealed switches** (NOT available w/ Mounting Style 7 or 8)
Position Transmitter Output
A None
Pneumatic connections
N 1/4” NPT (3/8” NPT with High Flow Option)
B 1/4” BSP (3/8” BSP with High Flow Option)
F 1/4” NPT w/ Filter-Regulator Assembly (3/8” NPT with High Flow Option)
55 3 5 IS E H P A 2 A N = Model Number 5535ISEHPA2AN
* Linear valve stroke and fail position must be specified at time of quotation.
** Not available with “Linear” Actuators type or “Remote Mounting Style”

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 15 of 206
Note: When ordering a liner ICoT PA positioner, (option “1” for the third digit in the part number). Be prepared
to supply the exact stroke length and fail direction of the application.
4 Definitions
This section contains definitions to all acronyms or abbreviations used in this document.
Some of them were extracted from IEC, ISO and PNO documents as referred in the
‘References’ section.
Table 4-1
Definitions and Acronyms
Acronym Definitions
0x Prefix to indicate that the number is in the Hexadecimal
format, i.e. 0x05 (=5) or 0x0a (=10) or 0xfe(=254)
AI Analog Input
AO Analog Output
ASN.1 Abstract Syntax Notation 1
Auto Automatic mode
Cas Cascade mode
CCITT International Telegraph and Telephone Consultative
Committee
DC Direct Current
DCS Distributed Control System
DD Device Description
DDL Device Description Language
DI Discrete Input
DO Discrete Output
EUC End User Council
FB Function Block
FBAP Function Blocks Application Process
fieldbus PROFIBUS PA
Gbit/s Gigabits per second
HW Hardware
IEC International Electro technical Commission
IMan Initialization Manual mode

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 16 of 206
Definitions and Acronyms
Acronym Definitions
IP Internet Protocol
IS. Intrinsically Safe
ISA The International Society for Measurement and Control
ISO International Organization of Standards
kbit/s kilobits per second
kHz kilohertz
LAN Local Area Network
LAS Link Active Scheduler
LO Local Override mode
mA Milliampere
Man Manual mode
Mbit/s Megabits per second
MV Measured Variable
OD Object Dictionary
OOS or O/S Out Of Service mode
OSI Open Systems Interconnect
PC Personal Computer
PDU Protocol Data Unit
PHY Physical Layer
PID Proportional, Integral, Derivative
PLC Programmable Logic Controller
PV Process Variable
RCas Remote-Cascade mode
Rout Remote-Output mode
SW Software
TB Transducer Block
TCP/IP Transport Control Protocol/Internet Protocol
VCR Virtual Communication Relationship
VFD Virtual Field Device

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 17 of 206
Definitions and Acronyms
Acronym Definitions
GSD General Station Description File
EDD Electronic Device Description
PNO The PROFIBUS Nutzerorganisation e.V. (PROFIBUS User
Organization)
PROFIBUS Process Field Bus
PROFIBUS DP PROFIBUS Decentralized Periphery
PROFIBUS PA PROFIBUS Process Automation
MBP Manchester Bus Powered
DTM Device Type Manager
PROFIBUS-related definitions1
GSD
A TXT file to inform to help the configuration system to know the capability of each device.
The GSD file name has the identification number (ident number), and each PROFIBUS
device type has a unique ident number. If you know the ident number, you can find easily
the GSD file.
Cyclic Data Transfer
At device startup the master configured the data to be exchange cyclic. The GSD provide
the information needs for the master to configure the cyclic data transfer automatically.
Acyclic Data Transfer
Asynchrony data transfer. The master requests a data and receives it from the slave.
Basic Device
A Basic Device is any device not having the capability to communicate on PROFIBUS
fieldbus segment.
Bus
A set of segments (DP and PA) connected via repeaters or couplers. Allow up to 128
devices.
Communications Stack
It is a layered software supporting communication between devices. A Communications
Stack is device communications software, which provides encoding and decoding of User
Layer messages, deterministic control of message transmission, and message transfer.
Device Coupler
A device coupler is a physical interface between a PROFIBUS DP segment and
PROFIBUS PA segment.
Electronic Device Description (EDD)
1For the complete list of definitions please see the Profile for Process Control Devices - Version 3.02 - April
2009

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 18 of 206
Electronic Device Description (EDD) provides an extended description of each object in the
device, and includes information needed for a control system or host to understand the
meaning of data. Used by the Siemens PDM.
FISCO
Fieldbus Intrinsic Safe COncept. Allows more power to an IS segment for approved FISCO
devices, allowing for more devices per IS segment.
FNICO
Fieldbus Non-Incendive COncept allows more power to a fieldbus segment in a Zone 2
Area, thus enabling more devices per segment than is possible with a FISCO solution.
Interoperability
Interoperability is the capability for a device from one manufacturer to interact with that of
another manufacturer on a fieldbus network without loss of functionality.
Intrinsic safety (IS)
Intrinsic Safety is a protection method for safe operation of electronic equipment in
explosive atmospheres even under irregular operating conditions. It assures that the
available electrical and thermal energy in the system is always lower than the amount that
could cause ignition of the hazardous atmosphere.
Mode
Control block operational condition, such as manual, automatic, or cascade.
Segment
A Segment is a section of a PROFIBUS fieldbus terminated in its characteristic impedance.
Segments can be linked by Repeaters to form a longer fieldbus. Each segment can include
up to 32 H1 devices.
Spur
A Spur is a PA branch line connecting to the Trunk that is a final circuit. A Spur can vary in
length from 1 m (3.28 ft.) to 120 m (394 ft.).
Function Block (FB)
Function Blocks (FBs) are built into fieldbus devices as needed to achieve the desired
control functionality. Automation functions provided by FBs include Analog Input (AI),
Analog Output (AO), Discrete Input (DI) and Discrete Output (DO).
Device Type Manager
Device Type Manager is a device specific software component provide by the device
manufacture together with its device. This software is implemented following the FDT
specification.
FDT
FDT is a technology where it standardizes the communication between the device and the
application to provide sophisticated views of the device data for configuration, maintenance
and operation.

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 19 of 206
5 Installation
5.1 Mounting Positioner on a Rotary Actuator
Step 1. Mount bracket and inner beacon coupler to actuator. If actuator shaft has a tapped
hole, fasten using proper flat head screw. If actuator does not have a tapped hole, fasten
using set screws on side of coupler. (See Figure 5-1)
Figure 5-1

WESTLOCK CONTROLS CORPORATION
280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
10/5/2013 TECH-477/D.W.O. 21424 Page 20 of 206
Step 2. Press fit the inner beacon to the inner beacon coupler. The inner beacon needs to
be properly oriented. Use the symbols on the top of the inner beacon to mount as shown in
Condition 1 or Condition 2. (See Figure 5-2). Condition 1 and Condition 2 show the
placement of the inner beacon with respect to the positioner housing while the actuator is in
the fail position.
Step 3. Mount the positioner to the bracket. As stated in Step 2 make sure that the
positioner is mounted in a fashion that properly orients it with respect to the inner beacon.
Condition 1: Actuator fails in a clockwise direction.
Spring Return
Output Port 2 is plugged
Output Port 1 is piped to turn the actuator counter
clockwise
Double Acting
Output Port 2 is piped to turn the actuator clockwise
Output Port 1 is piped to turn the actuator counter
clockwise
Placed at 6:00
II Placed at 3:00
Condition 2: Actuator fails in a counter clockwise
direction.
Spring Return
Output Port 2 is plugged
Output Port 1 is piped to turn the actuator clockwise
Double Acting
Output Port 2 is piped to turn the actuator counter
clockwise
Output Port 1 is piped to turn the actuator clockwise
Placed at 9:00
II Placed at 6:00
Figure 5-2
This manual suits for next models
1
Table of contents
Other Westlock Valve Positioner manuals
Popular Valve Positioner manuals by other brands

cascade corporation
cascade corporation 55K installation instructions

Bray
Bray 6P Series Operation and maintenance manual

Baker Hughes
Baker Hughes Masoneilan SVI3 Special instructions

Lincoln Electric
Lincoln Electric POSIMATIC PS03 Safety instruction for use and maintenance

Bürkert
Bürkert 8791 Assembly instructions

Samson
Samson 4763 Mounting and operating instructions