rotork YT-3302 Series User manual

SMART POSITIONER PRODUCT MANUAL
YT-3300 / 3350 / 3303 / 3301 / 3302 SERIES (New Software)
VERSION 2.12
YT-3300 (New NCS type) YT-3350 (New NCS type)
YT-3300 + Internal Limit Switch YT-3303
(Potentiometer type) (Potentiometer type)
YT-3301 (MS Connector Type)
(Potentiometer type)
YT-3302 (Junction Box Type)
(Potentiometer type)
Rotork YTC Limited

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 2
Contents
1Introduction.................................................................................................................................................6
1.1 General Information for the users.........................................................................................................6
1.2 Manufacturer Warranty.........................................................................................................................6
1.3 Explosion Proof Warning (Only for Intrinsic safety type positioners)....................................................7
2Product Description ...................................................................................................................................9
2.1 General.................................................................................................................................................9
2.2 Main Features and Functions ...............................................................................................................9
2.3 Label Description............................................................................................................................... 10
2.4 Product Code..................................................................................................................................... 16
2.4.1 YT-3300 / 3350 series follows suffix symbols as follows............................................................... 16
2.4.2 YT-3303 series follows suffix symbols as follows.......................................................................... 18
2.4.3 YT-3301 / 3302 series follows suffix symbols as follows............................................................... 19
2.5 Product Specification......................................................................................................................... 21
2.5.1 YT-3300 / 3303 / 3350 Specification ............................................................................................. 21
2.5.2 YT-3301 / 3302 Specification......................................................................................................... 22
2.6 Certifications...................................................................................................................................... 24
2.7 Parts and Assembly........................................................................................................................... 27
2.7.1 YT-3300 / 3350.............................................................................................................................. 27
2.7.2 YT-3303......................................................................................................................................... 28
2.7.3 YT-3301......................................................................................................................................... 29
2.7.4 YT-3302......................................................................................................................................... 30
2.8 Product Dimension ............................................................................................................................ 31
2.8.1 YT-3300......................................................................................................................................... 31
2.8.2 YT-3350......................................................................................................................................... 32
2.8.3 YT-3303......................................................................................................................................... 33
2.8.4 YT-3301 / 3302.............................................................................................................................. 34
3Installation................................................................................................................................................ 35
3.1 Safety................................................................................................................................................. 35
3.2 Tools for installation........................................................................................................................... 35
3.3 Linear positioner Installation.............................................................................................................. 36
3.3.1 Linear positioner Installation of Standard lever type...................................................................... 36
3.3.1.1 Safety..................................................................................................................................... 37
3.3.1.2 Standard lever type positioner Installation Steps .................................................................. 37
3.3.2 YT-3300L / 3350L Installation of Adapter lever type (on tubeless actuator) ................................. 42
3.3.2.1 Safety..................................................................................................................................... 42
3.3.2.2 Adapter lever type positioner Installation Steps .................................................................... 43
3.4 Rotary positioner Installation ............................................................................................................. 45
3.4.1 YT-3300R / 3350R Components ................................................................................................... 45
3.4.2 YT-3303R Components................................................................................................................. 46

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 3
3.4.3 YT-3301R / 3302R remote sensor components............................................................................ 46
3.4.4 Rotary Bracket Information (Only YT-3300R / 3350R / 3303R) .................................................... 47
3.4.5 Rotary positioner Installation Steps............................................................................................... 48
4Connection - Air....................................................................................................................................... 51
4.1 Safety................................................................................................................................................. 51
4.2 Supply Pressure Condition................................................................................................................ 51
4.3 Piping Condition................................................................................................................................. 51
4.4 Connection –Piping with actuator..................................................................................................... 52
4.4.1 Single acting actuator .................................................................................................................... 52
4.4.2 Double acting actuator................................................................................................................... 53
5Connection – Power ................................................................................................................................ 54
5.1 Safety................................................................................................................................................. 54
5.2 Connection......................................................................................................................................... 55
5.2.1 Standard Terminals ....................................................................................................................... 55
5.2.2 Terminals with micro-limit switch option ........................................................................................ 56
5.2.3 Terminals with inductive proximity Limit Switch option.................................................................. 57
5.2.4 Terminals between Positioner main body and Remote sensor of YT-3301 / 3302....................... 58
5.3 Ground............................................................................................................................................... 58
6Adjustments ............................................................................................................................................. 59
6.1 Limit Switch Adjustment..................................................................................................................... 59
6.2 A/M switch adjustment....................................................................................................................... 60
6.3 Orifice Installment.............................................................................................................................. 61
6.3.1 Plate type Orifice Installment (except YT-3303)............................................................................ 61
6.3.2 Variable Orifice Adjustment (Only YT-3303) ................................................................................. 61
7Optional Sub-PCB Installment ............................................................................................................... 62
7.1 Installation steps................................................................................................................................ 62
8Maintenance ............................................................................................................................................. 64
8.1 Supply air........................................................................................................................................... 64
8.2 Seals.................................................................................................................................................. 64
9Auto Calibration and PCB Operation..................................................................................................... 65
9.1 Warning.............................................................................................................................................. 65
9.2 LCD display and buttons.................................................................................................................... 65
9.2.1 LCD display and symbols .............................................................................................................. 65
9.2.2 Button and function........................................................................................................................ 66
9.3 Menu levels........................................................................................................................................ 67
9.4 Run Mode (RUN)............................................................................................................................... 68
9.5 Configuration and Operation.............................................................................................................. 69
9.6 Calibration (CALIb) ............................................................................................................................ 73
9.6.1 Acting Type (SINGLE / dOUBLE).................................................................................................. 74
9.6.2 Auto Calibration 1 (AUTO 1).......................................................................................................... 74

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 4
9.6.3 Auto Calibration 2 (AUTO 2).......................................................................................................... 75
9.6.4 Auto Calibration 3 (AUTO 3).......................................................................................................... 76
9.6.5 Travel Zero (TVL ZERO) and Travel end (TVL ENd) .................................................................... 77
9.7 Manual Operation (MAN OPER)........................................................................................................ 78
9.7.1 Manual Operation by Set position (MAN SP) ................................................................................ 78
9.7.2 Manual Operation by Manipulator Value (MAN MV) ..................................................................... 79
9.8 Control Parameters (CTL PARM)...................................................................................................... 80
9.8.1 Dead Band (dEAdbANd)................................................................................................................ 80
9.8.2 Forward P parameter (KP UP) and reverse P parameter (KP dN)................................................ 81
9.8.3 Forward Integral time parameter (TI UP) and reverse Integral time parameter (TI dN)................ 81
9.8.4 Forward D parameter (Kd UP) and reverse D parameter (Kd dN)................................................ 82
9.8.5 GAP Parameter (GAP) .................................................................................................................. 82
9.8.6 GAP P parameter (GP).................................................................................................................. 83
9.8.7 GAP I parameter (GI)..................................................................................................................... 83
9.8.8 GAP D parameter (Gd).................................................................................................................. 83
9.8.9 Auto Dead band Mode (AUTO db) ................................................................................................ 84
9.8.10 Performance Mode (PER) ......................................................................................................... 84
9.9 Input Configuration (IN CFG)............................................................................................................. 85
9.9.1 Signal Direction (SIG NORM / REVS)........................................................................................... 85
9.9.2 Split Range Mode (SPLIT)............................................................................................................. 86
9.9.3 Custom Split Range Zero (CST ZERO)......................................................................................... 86
9.9.4 Custom Split Range End (CST ENd)............................................................................................. 87
9.9.5 Valve Flow Characterization Curves (CHAR)................................................................................ 87
9.9.6 User Set Characterization 5 Points (U5) ....................................................................................... 88
9.9.7 User Set Characterization 21 Points (U21) ................................................................................... 89
9.9.8 Tight Shut Open (TSHUT OP)....................................................................................................... 90
9.9.9 Tight Shut Close (TSHUT CL)....................................................................................................... 91
9.9.10 Target Position Ramp Up Rate (RAMP UP) and Target Position Ramp Down Rate (RAMP dN)
92
9.10 Output Configuration (OUT CFG)...................................................................................................... 94
9.10.1 Position Transmitter Direction (PTM NORM / REVS)................................................................ 94
9.10.2 Position Transmitter Zero / End (PTM ZERO / ENd)................................................................. 95
9.10.3 HART Feedback Direction (HT NORM / REVS)........................................................................ 96
9.10.4 Back Calculation (bACKCAL oFF / on)...................................................................................... 97
9.11 Device Configuration (dEV CFG)....................................................................................................... 98
9.11.1 Action Setting (ACT REVS / dIR)............................................................................................... 98
9.11.2 Linear Lever Type (LEVT STd / AdT)........................................................................................ 98
9.11.3 Linear Interpolation (ITP oFF / on)............................................................................................. 99
9.11.4 Lock of Parameters (Write Protect, W UNLOCK / LOCK)......................................................... 99
9.11.5 Actual Position View Mode (View Mode, VI NORM / REVS) .................................................. 100

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 5
9.11.6 Polling address setting (POL AddR)........................................................................................ 100
9.11.7 Factory Reset (dEFAULT oFF / on)......................................................................................... 101
9.11.8 Positioner Self-Test (SELFTEST)............................................................................................ 102
9.12 Diagnosis Mode (dIAGNd)............................................................................................................... 103
9.12.1 Default Alarm Settings............................................................................................................. 104
9.12.2 Process Status (PS) ................................................................................................................ 105
9.12.3 Device Status (dS)................................................................................................................... 106
9.12.4 View Monitoring Counts (VI CNTS)......................................................................................... 107
9.12.5 Diagnostic Limit Configuration (LIMT CFG)............................................................................. 108
9.12.6 Reset Alarm Status (RST ALRM oFF / on).............................................................................. 109
9.12.7 View Event Log (EVT LOG)..................................................................................................... 110
9.12.8 Partial Stroke Test Record (View PST Result Record, PST RSLT)........................................ 111
9.12.9 PST Configuration (PST CFG) ................................................................................................ 112
9.12.10 Run PST (PST NOW).............................................................................................................. 113
9.12.11 Periodic PST Test (PST Schedule, PST SCHd oFF / on)....................................................... 114
9.13 Position information (INFO) ............................................................................................................. 114
9.14 Error codes during automatic calibration......................................................................................... 116
9.15 Status and Alarm Code.................................................................................................................... 117
11 Main Software Map .................................................................................................................................119

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 6
1 Introduction
1.1 General Information for the users
Thank you for purchasing Rotork YTC Limited products. Each product has been fully inspected after
its production to offer you the highest quality and reliable performance. Please read the product
manual carefully prior to installing and commissioning the product.
➢Installation, commissioning, and maintenance of the product may only be performed by trained
specialist personnel who have been authorized by the plant operator accordingly.
➢The manual should be provided to the end-user.
➢Factory Mutual approved Intrinsically Safe and Non-Incendive units must be Installed Per
drwg SKC_18601_150326.pdf
➢CSA approved Intrinsically Safe and Non-Incendive units must be Installed Per drwg SKC-
8465.pdf
➢The manual can be altered or revised without any prior notice. Any changes in product’s
specification, design, and/or any components may not be printed immediately but until the
following revision of the manual.
➢When the manual refers to “Valve Zero / Zero” means the final valve position upon pneumatic
pressure has been fully exhausted from positioner’s OUT1 port. For example, the valve zero
position may differ between linear direct and reverse actions. (DA/RA)
➢The manual should not be duplicated or reproduced for any purpose without prior approval from
Rotork YTC Limited, Gimpo-si, South Korea.
➢In case of any other problems that are not stated in this manual, please make immediate contact
to Rotork YTC Limited.
➢Positioner is an accessory of the control valve, so please make sure to read the applicable
instruction manual of the control valve prior to installation and operation.
1.2 Manufacturer Warranty
➢For the safety, it is important to follow the instructions in the manual. Manufacturer will not be
responsible for any damages caused by user’s negligence.
➢Any modifications or repairs to the product may only be performed if expressed in this manual.
Injuries and physical damages caused by customer’s modifying or repairing the product without a
prior consultation with Rotork YTC Limited will not be compensated. If any alterations or
modifications are necessary, please contact Rotork YTC Limited directly.
➢The warranty period of the product is (18) months from the date of shipment unless stated
otherwise. Date of shipment can be checked by providing the LOT NO. or SERIAL NO. to us.

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 7
➢Manufacturer warranty will not cover products that have been subjected to abuse, accidents,
alterations, modifications, tampering, negligence, misuse, faulty installation, lack of reasonable
care, repair or service in any way that is not contemplated in the documentation for the product,
or if the model or serial number has been altered, tampered with, defaced or removed; damages
that occurs in shipment, due to act of God, failure due to power surge, or cosmetic damage.
Improper or incorrectly performed maintenance will void this limited warranty.
➢For detailed warranty information, please contact the corresponding local Rotork YTC Limited
office or main office in South Korea.
1.3 Explosion Proof Warning (Only for Intrinsic safety type positioners)
Please ensure the unit is being used and installed in conformity with local, regional, and national
explosion proof within the proper safety barrier environment.
➢Refer to “2.6 Certifications”
➢Explosion proof type of cables and gaskets should be used, when explosion gases are present at
the installation site.
➢Positioner has 2 ports for power connection. Explosion proof type wires and packing should be
used. Blind plug is required when any port is not being used.
➢Ring terminal with surface area of more than 1.25 mm2 with M4 spring washer should be used to
connect the power.
➢For external ground terminal, ring terminal with surface area of more than 5.5 mm2 should be used.
➢Wiring in these applications shall utilize appropriate methods for Class I, Division 2 / Zone 2
➢Substitution of components may impair intrinsic safety.
➢WARNING –EXPLOSION HAZARD –Substitution of components may impair suitability for
Class I, Division 2.
➢“AVERTISSEMENT –RISQUE D'EXPLOSION –Remplacement des composants peut nuire à la
conformité de Classe I, Division 2”
➢EXPLOSION HAZARD. Do not connect or disconnect wiring unless all sources of power have
been removed or the area is known to be non-hazardous.
(French) RISQUE D'EXPLOSION. Ne pas raccorder ou débrancher le câblage à moins Toutes
les sources d'énergie ont été enlevées ou la zone est connue pour être non dangereux.
➢The enclosure of models YT-3300, YT-3301, and YT-3303 contains aluminum, which is
considered to constitute a potential risk of ignition when subjected to impact or friction. Care
must be used during installation in locating this equipment to prevent impact or friction
➢Some of the enclosure parts are made of non-metallic materials. To prevent the risk of
Electrostatic sparking, clean the enclosure only with a damp cloth.
➢The product must be installed in such a manner as to minimize the risk of impact or friction with
other metal surfaces.

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 8
➢For Intrinsically Safe installations, the product must be connected to suitably rated intrinsically
safe equipment, and must be installed in accordance with applicable intrinsically safe installation
standards.
➢Special conditions for safe use of sign “X” of ATEX / IECEx :
The ambient temperature range deviates from the standard temperature range and amounts to:
Temperature class T5 / T100°C: -40°C to +60°C
Temperature class T6 / T85°C: -40°C to +40°C
Equipment must be protected from high risk of mechanical impact hazard and high electrostatic
charge hazards.
➢FM & CSA only : Tapped Exhaust option is used when it is required to vent away Group D,
Div/Group IIA, Zone gases to a safe area. Using gases other than air must be compatible with
the YT-3300 series wetted parts.

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 9
2 Product Description
2.1 General
YT-3300 / 3350 / 3303 / 3301 / 3302 series Smart Valve Positioner accurately controls valve stroke in
response to an input signal of 4 ~ 20 mA from the controller. Built-in micro-processor optimizes the
positioner’s performance and provides unique functions such as Auto-Calibration, PID Control, and
HART Protocol Communications.
2.2 Main Features and Functions
➢LCD display enables users to monitor the positioner status.
➢User will easily understand the method of using 4 buttons because it work same in all versions of
firmware interfaces.
➢When unexpected situation like momentary blackout happens, our positioner boot-time only take
0.5 second and this can minimize the travel of valve which consequentially increase the safety of
system.
➢Positioner operates normally even there are sudden changes in supply pressure and / or high
vibration environment.
➢YT-3301 / 3302 remote positioner is stronger on high temperature and vibration environment
because it is separated into remote sensor and positioner.
➢The method of Auto Calibration is very simple.
➢As an advantage of having very low air consumption, It could greatly reduce operating costs in
large-scale plants.
➢It is compatible with most of controllers.
➢Orifices can be installed even in the field to minimize the hunting occurrence and optimize
operating conditions.
➢Various information about positioner can be processed by HART communication. (HART option)
➢"EDD and FDI files required for HART communication can be downloaded from our website
(www.ytc.co.kr) or FieldComm Group (www.fieldcommgroup.org). When using the FieldComm
Group website, please search for the Product Name on YT-3XXX."
➢Valve system becomes more stable by outputting analog feedback signal.
➢Different valve characteristics can be adjusted – Linear, Quick Open, Equal Percentage, and User
Set which user can make 5 or 18 points characterizations.
➢Tight Shut – Close and Shut - Open can be set.
➢PID parameters can be adjusted in the field without any additional communicator.
➢A/M switch can be used to direct supply air to the actuator or to manually operate the positioner
or valve without any signal.
➢Split range 4 ~ 12 mA or 12 ~ 20 mA can be set.
➢Operating temperature for remote sensor of YT-3301 / 3302 is -40 ~ 120 °C.
Operating temperature for positioners is -30 ~ 85 °C or -40 ~ 85 °C (Please check certified
explosion proof temperature)

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 10
➢Hand calibration function can set Zero point or End point manually.
➢It has IP66, Type 4X(FM) protection grade.
➢Polyester powder coating resists the corrosion process. (except YT-3350).
➢Maintenance of the positioner is easy because of modularized inner structure.
➢SIL2 certified.(For more information, see SIL Safety Instruction on homepage)
➢Suitable for use with methane or natural gas supply pressure medium for FM/CSA (only A & AG
of Explosion proof of Product code)
➢The AG option in the product code has the tapped exhaust ports to carry the gas vented from the
positioner to a safe location when the positioner is installed indoors to use methane or natural gas
as a process medium.
2.3 Label Description
•MODEL : Indicates the model number and additional options.
•EXPLOSION PROOF : Indicates certified explosion proof grade.
•INGRESS PROTECTION : Indicates enclosure protection grade.
•INPUT SIGNAL : Indicates input signal range.
•OPERATING TEMP. : Indicates the allowable operating temperature.
•SUPPLY PRESSURE : Indicates the supply pressure range.
•SERIAL NUMBER : Indicates unique serial number.
•MONTH.YEAR : Indicates manufactured month and year.
•INTRINSIC SAFETY / NONINCENDIVE : Indicates intrinsic safety explosion proof grade.
•AMBIENT TEMP. : Indicates the allowable ambient temperature for explosion proof.
•Ui, Ii, Pi, Ci, Li : Indicates the allowable electrical data in the certificate.
ATEX: Ui = 28 V, Ii = 93 mA, Pi = 651 mW, Ci = 0.6 nF, Li = 10 μH
FM: Ui = 28 V, Ii = 93 mA, Pi = 651 mW, Ci = 0.55 nF, Li = 12 μH
You can also see the details in the certificate.
Fig. L-1: YT-3300 / 3303 / 3301 / 3302 Non-explosion proof

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 11
Fig. L-2: YT-3300 / 3303 / 3301 / 3302 Non-explosion proof (EAC)
Fig. L-3: YT-3300 / 3303/ 3301 / 3302 Intrinsic safety type (UKEX, ATEX, IECEx, KCs, NEPSI, PESO)
(PESO applies only to YT-3300)
Fig. L-4: YT-3300 / 3303 / 3302 Intrinsic safety type (FM, CSA)

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 12
Fig. L-5: YT-3301 Intrinsic safety type (FM, CSA)
Fig. L-6: YT-3300 / 3303 / 3301 / 3302 Intrinsic safety type (EAC)
Fig. L-7: YT-3300 / 3303 / 3301 / 3302 Intrinsic safety type (INMETRO)

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 13
Fig. L-8: YT-3300 Intrinsic safety type (CCC)
Fig. L-9: YT-3303 Intrinsic safety type (CCC)
Fig. L-10: YT-3301 Intrinsic safety type (CCC)

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 14
Fig. L-11: YT-3302 Intrinsic safety type (CCC)
Fig. L-12: YT-3350 Non-explosion proof
Fig. L-13: YT-3350 Intrinsic safety type (UKEX, ATEX, IECEx, KCs, NEPSI)

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 15
Fig. L-14: YT-3350 Intrinsic safety type (FM, CSA)
Fig. L-15: YT-3350 Intrinsic safety type (EAC)
Fig. L-16: YT-3350 Intrinsic safety type (INMETRO)

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 16
Fig. L-17: YT-3350 Intrinsic safety type (CCC)
2.4 Product Code
2.4.1 YT-3300 / 3350 series follows suffix symbols as follows.
YT-3300 / 3350 1 2 3 4 5 6 7 8
1 Motion Type
L :
R :
Linear (Positioner is attached the right yoke of actuator.)
Rotary
2 Acting type
S :
D :
Single
Double
3 Explosion Proof
1) N :
i :
11) A :
12) AG :
E :
Z :
Non-Explosion
ATEX, IECEx, KCs, NEPSI, INMETRO 2), UKEX, , PESO 10) :
Ex ia IIC T5/T6 Gb, Ex iaD IIIC T100°C/T85°C Db, IP66
FM, CSA :
Class I, Division 1&2 Groups ABCD T5/T6
Class II, Division 1&2 Groups EFG T100°C/T85°C; Class III
Class I, Zone 0, AEx ia IIC T5/T6(FM)
Ex ia IIC T5/T6 Ga; Ex tb IIIC T100°C/T85°C Db
FM, CSA + Tapped Exhaust
Intrinsic safety for EAC
Intrinsic safety for CCC

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 17
4 Lever Type
Linear
0 :
1 :
2 :
3 :
4 :
5 :
6 :
10 ~ 40 mm (Standard type)
20 ~ 100 mm (Standard type)
90 ~ 150 mm (Standard type)
16 ~ 30 mm (Adapter type)
16 ~ 60 mm (Adapter type)
16 ~ 100 mm (Adapter type)
90 ~ 150 mm (Adapter type)
Rotary
1 :
2 :
3 :
4 :
5 :
M6 x 34L
M6 x 63L
M8 x 34L
M8 x 63L
Namur
5 Conduit - Air
Connection Type
1 :
2 :
3 :
4 :
5 :
G 1/2 – Rc 1/4
G 1/2 – 1/4 NPT (YT-3350 is available for No. 2 ONLY)
G 1/2 – G 1/4
M20x1.5P – 1/4 NPT
1/2 NPT – 1/4 NPT
6 Communication
0 :
2 :
None
+ HART Communication
7 Option
0 :
1 :
2 :
3 :
4 :
5 :
None 8)
+ Position Transmitter 9)
+ Limit Switch(Mechanical Type, 2ea) 3)
+ Limit Switch(Inductive Proximity Type, 2ea) 4)
+ Position Transmitter and Limit Switch(Mechanical Type, 2ea) 5)
+ Position Transmitter and Limit Switch(Inductive Proximity Type,
2ea) 6)
8 Operating Temp.
(Non-explosion proof) 7)
S :
L :
A :
-30 ~ 85 °C (-22 ~ 185 °F, except EAC)
-40 ~ 85 °C (-40 ~ 185 °F)
-55 ~ 85 °C (-67 ~ 185 °F, only EAC)
1) In case of EAC non-explosion type, put “EAC” in a purchase order.
2) In case of INMETRO, put “INMETRO” in a purchase order.
3) 5) These options are only available for “S”, “L” in 8 operating temp.
4) 6) These options are only available for “S” in 8 operating temp.
7) This option is just the normal operating temperature of the product and is not related to explosion
proof temperature. See “2.6 Certificates” for explosion proof temperature.
8) 9) NCS type
3) 4) 5) 6) 11) 12) Potentiometer type
10) PESO applies only to YT-3300.

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 18
2.4.2 YT-3303 series follows suffix symbols as follows.
(YT-3303 has only a potentiometer type)
YT-3303 1 2 3 4 5 6 7 8
1 Motion Type
L :
R :
Linear (Positioner is attached the left yoke of actuator.)
Rotary
2 Acting type
S :
D :
Single
Double
3 Explosion Proof
N :
i :
A :
AG :
E :
Z :
Non-Explosion
ATEX, IECEx, KCs, NEPSI, INMETRO 1), UKEX :
Ex ia IIC T5/T6 Gb, Ex iaD IIIC T100°C/T85°C Db, IP66
FM, CSA :
Class I, Division 1&2 Groups ABCD T5/T6
Class II, Division 1&2 Groups EFG T100°C/T85°C; Class III
Class I, Zone 0, AEx ia IIC T5/T6(FM)
Ex ia IIC T5/T6 Ga; Ex tb IIIC T100°C/T85°C Db
FM, CSA + Tapped Exhaust
Intrinsic safety for EAC
Intrinsic safety for CCC
4 Lever Type
Linear
1 :
2 :
3 :
4 :
10 ~ 40 mm
20 ~ 70 mm
50 ~ 100 mm
100 ~ 150 mm
Rotary
1 :
2 :
3 :
4 :
5 :
M6 x 34L
M6 x 63L
M8 x 34L
M8 x 63L
Namur
5 Conduit –
Air Connection Type
1 :
2 :
3 :
4 :
5 :
G 1/2 – Rc 1/4
G 1/2 – 1/4 NPT
G 1/2 – G 1/4
M20x1.5P(Adapter type) – 1/4 NPT
1/2 NPT(Adapter type) – 1/4 NPT
6 Communication
0 :
2 :
None
+ HART Communication
7 Option
0 :
1 :
None
+ Position Transmitter

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 19
8 Operating Temp.
(Non-explosion proof) 2)
S :
L :
A :
-30 ~ 85 °C (-22 ~ 185 °F, except EAC)
-40 ~ 85 °C (-40 ~ 185 °F)
-55 ~ 85 °C (-67 ~ 185 °F, only EAC)
1) In case of INMETRO, put “INMETRO” in a purchase order sheet.
2) This option is just the normal operating temperature of the product and is not related to explosion proof
temperature. See “2.6 Certificates” for explosion proof temperature.
2.4.3 YT-3301 / 3302 series follows suffix symbols as follows.
(YT-3301 is MS Connector Type. YT-3302 is Junction Box Type. Both models have only a
potentiometer type.)
YT-3301 / 3302 1 2 3 4 5 6 7 8 9
1 Motion Type
L :
R :
Linear
Rotary
2 Acting type
S :
D :
Single
Double
3 Explosion Proof
N :
i :
A :
AG :
E :
Z :
Non-Explosion
ATEX, IECEx, KCs, NEPSI, INMETRO 1), UKEX :
Ex ia IIC T5/T6 Gb, Ex iaD IIIC T100°C/T85°C Db, IP66
FM & CSA :
Class I, Division 1&2 Groups ABCD T5/T6
Class II, Division 1&2 Groups EFG T100°C/T85°C; Class III
Class I, Zone 0, AEx ia IIC T5/T6(FM)
Ex ia IIC T5/T6 Ga; Ex tb IIIC T100°C/T85°C Db
FM, CSA + Tapped Exhaust
Intrinsic safety for EAC
Intrinsic safety for CCC
4 Lever Type
Linear
1 :
2 :
3 :
4 :
10 ~ 40 mm
20 ~ 70 mm
50 ~ 100 mm
100 ~ 150 mm
Rotary
5 :
Namur
5 Conduit –
Air Connection Type
1 :
2 :
3 :
4 :
5 :
G 1/2 – Rc 1/4
G 1/2 – 1/4 NPT
G 1/2 – G 1/4
M20x1.5P(Adapter type) – 1/4 NPT
1/2 NPT(Adapter type) – 1/4 NPT

Smart Positioner
YT-3300 / 3350 / 3303 / 3301 / 3302 series (New Software) Product Manual
Ver. 2.12 20
6 Communication
0 :
2 :
None
+ HART Communication
7 Option
0 :
1 :
None
+ Position Transmitter
8 Operating Temp.
(Non-explosion proof) 2)
S :
L :
A :
-30 ~ 85 °C (-22 ~ 185 °F, except EAC)
-40 ~ 85 °C (-40 ~ 185 °F)
-55 ~ 85 °C (-67 ~ 185 °F, only EAC)
9 Cable Length 3)
1 :
2 :
3 :
4 :
5m
10m
15m
20m
1) In case of INMETRO, put “INMETRO” in a purchase order sheet.
2) Maximum cable length is 20m.
3) This option is just the normal operating temperature of the product and is not related to explosion
proof temperature. See “2.6 Certificates” for explosion proof temperature.
This manual suits for next models
4
Table of contents
Other rotork Valve Positioner manuals

rotork
rotork YT-3300 Series User manual

rotork
rotork YT-3300 Series User manual

rotork
rotork YT-3700 User manual

rotork
rotork TMP-3000 User manual

rotork
rotork YT-3100 User manual

rotork
rotork YT-3700 User manual

rotork
rotork YT-1200 Series User manual

rotork
rotork YT-2600 Series User manual

rotork
rotork TMP-3000 User manual

rotork
rotork YT-3300 Series User manual