20
Display Error type Description Case #
L-20 Flame error Flame detected after
closing the gas valve
15
L-21 Flame error Flame detected after
closing the gas valve
16
L-22 Flame error Flame failure during
burning
5
L-25 Sensor error Heat exchange sensor
failure
4
L-26 Sensor error Flue sensor failure 4
L-27 to 31 Internal error Internal error 13
L-32 Sensor error Heat exchange sensor
failure
4
L-33 to 38 Internal error Internal error 13
L-42 Flue temperature
error
Too many flue temperature
errors
3
L-43 Overheating Heat exchange sensor is
overheated too often
3
9.2 Temporary errors
The table below describes the temporary errors that can
occur. These will disappear automatically after the cause
has been resolved.
Display Error type Description Case #
E-00 to 04 Internal error Internal error 13
E-05 Overheating Heat exchange sensor is
overheated
3
E-06 to 13 Internal error Internal error
Flame detected when there
shouldn’t be one
13
E-14 Flame error 16
E-15 to 20 Internal error Internal error 13
E-21 and 22 Heat exchanger
sensor error
Heat exchanger sensor not
detected
4
E-23 and 24 Flue sensor error Flue sensor not detected 4
E-27 and 28 Heat exchanger
sensor error
Heat exchanger sensor
short-circuit
4
E-30 and 31 Flue sensor error Flue sensor short-circuit 4
E-34 Reset button
error
Too many reset actions in a
short timespan
9
E-36 Overheating Heat exchange sensor is
overheated
3
E-38 and 39 Heat exchanger
sensor error
Heat exchanger sensor not
detected
4
E-47 and 48 Heat exchanger
sensor error
Heat exchange sensor
short-circuit
4
E-49 to 64 Internal error Internal error 13
E-65 Voltage too low Supply voltage is too low
for over 1 minute
E-66 Voltage too high Supply voltage is too high
for over 1 minute
E-67 Pressure switch
error
Too many pressure switch
errors
11
E-68 Flue temperature
error
Flue sensor is overheated 3
E-69 Configuration
error
Heater configuration error 19
9.3 Warnings
The table below describes the temporary warnings that
can occur. The heater may still be working, or stops until
the cause has been resolved.
Display Error type Description Case #
A-02 Configuration
error
Heater configuration error 19
A-07 Overheating Heat exchange sensor is
almost overheated
3
A-08 Overheating Flue sensor is almost
overheated
3
9.4 Instructions
After identifying the problem, use the Case number to find
the possible cause in this paragraph.
Case 1: Flame lasts only 5 seconds after ignition.
• The flame is not detected:
–Check the ignition/ionisation cable and the
electrode. The cable should have a resistance
of 1 kΩ.
• The air heater is not earthed properly.
• The circuit board is defective.
Case 2: No flame after ignition.
• There is not enough gas pressure.
• The gas mixture is too poor:
–Adjust the gas valve (see §8.1).
• The gas valve does not open:
–During ignition, check for a 230 V voltage on
the valve.
• Check if the ignition electrode sparks. If not:
–Check the cable and electrode and replace
them when damaged.
–Check the burner control unit and replace it
when it does not give a spark output.
Case 3: Heat exchange sensor or flue sensor is overheated.
• Check if the connectors J12 and J6 are plugged in
correctly and if the connection J12[1-4] (optional
overheating protection) is closed.
• Check if the system fan supplies enough air.
• Check the settings of the gas valve. The heater may
be overfired. If so:
–Adjust the burner pressure.
Case 4: Heat exchange sensor or flue sensor not detected,
or short circuit.
NOTICE L-25 refers to the heat exchange sensor. L-26
refers to the flue sensor, if applicable.