
Manual 35162 EPG Governors with Single Phase Droop RoHS Compliant
Woodward 13
Installation Checks
Checks for All Applications
The following steps check only the speed control and actuator. They must work correctly before
paralleling the generator. Since most faults appear when the prime mover is first run, this step by step
approach eliminates most problems before they occur. Also, the main part of Chapter 5, Troubleshooting,
covers these checks.
The generator must not be paralleled during these tests. If a Ramp Generator is used, then temporarily
remove the wire at speed control terminal 8, which goes to the ramp generator. Leave the idle-rated
switch wiring connected. Perform the checks in the order indicated. Terminal numbers in this chapter refer
to the speed control.
1. Make sure all electrical connections are correctly made and terminal screws tightened; the magnetic
pickup is properly installed and jam nut tightened; the actuator and linkage are securely fastened.
2. Do not start the prime mover now. Turn on governor power. If the fuse or breaker opens as soon as
power is applied, the battery polarity (terminals 1 and 2) is probably reversed. The actuator shaft can
jump when power is turned on, but must quickly come back to the minimum-fuel position. Check the
battery voltage at terminal 1 (+) and 2 (–). It must be from 10 to 16 Vdc for EPG Model 1712 control
and from 20 to 32 Vdc for Model 1724.
3. Disconnect any wiring or jumper on terminal 7. Measure voltage from 2 (–) to 7 (+). The voltage must
be 7.2 ±1 volt. If voltage is correct, then re-install the wiring to terminal 7.
4. If idle speed is desired, connect a 50 kpotentiometer or fixed resistor to terminals 7 and 8 as
shown in the typical wiring diagram. To calculate the value of a fixed resistor:
5. Put the idle-rated switch in the rated position. Measure the voltage from terminal 7 (+) to 2 (–). Put
the idle-rated switch in the idle position. The voltage must increase. If it does not increase, check the
speed trim pot, if used, and idle-rated switch wiring.
6. If a signal generator with an isolated output is available, the failsafe and actuator travel can be
checked. Rated and idle speeds can be preset. If a signal generator is not available, skip to Step 7.
Turn governor power off. Remove the magnetic pickup wires from terminals 5 and 6. Connect the
signal generator to terminals 5 and 6. Set the output between 2 and 10 Vrms. The waveform can be
sine, square, or triangular. Calculate the MPU frequency for idle and rated speeds. See part number
selection in Chapter 1.
6.1 Check Failsafe and Actuator Travel
Set the signal generator frequency to about half idle speed. Set the idle-rated switch to rated.
Turn the signal generator and governor power on. The linkage must be at the maximum-fuel
position. Except for Detroit Diesel engines make sure linkage travel is limited by the prime
mover fuel control, not by the actuator stop. Turn the signal generator off and remove the
connections at terminals 5 and 6. The linkage should move to the minimum-fuel position. Make
sure linkage travel is limited by the prime mover’s fuel control, not by the actuator stop.
6.2 Preset Rated Speed
Set the signal generator for MPU frequency at rated speed and connect it to terminals 5 and 6.
Put the idle-rated switch in the rated position. Set the speed trim pot, if connected, to mid
position. Observe the linkage position.
If the linkage is at the maximum-fuel position:
Slowly turn the rated speed pot ccw until the linkage just begins to move to the minimum-fuel
position.