The RecoverX is a VAPOR ONLY
recovery unit. It will not tolerate liquid.
Use your RecoverX to pull vapor refriger-
ant directly out of the system and transfer
it into your recovery cylinder.
Vapor recovery can be done by connect-
ing to the low pressure system suction
service port (Vapor port) side of the sys-
tem. See diagram on following page.
Follow the steps below:
1) Ensure the recovery unit Power
Switch is off (○) and power to the
system to be serviced is off.
2) Connect the recovery unit, manifold
set, the system to be serviced, and the
recovery tank as shown on page 5.
3) Open the valves on the recovery
cylinder.
4) Turn the Bypass Valve to “OPEN.”
5) Turn the Power Switch on (׀) .
6) Turn the Bypass Valve clockwise to
“CLOSED.”
7) Slowly open the low pressure valve
on the manifold set, regulating the
suction pressure at no more than 40
psi. This will prevent the compres-
sor from stalling.
8) Monitor the manifold low-pressure
gauge. Once the pressure has reached
the required vacuum level, recovery
is complete.
9) Turn the Power Switch off (○).
10) Wait five (5) minutes to ensure the
pressure does not rise.
11) If the pressure rises above the re-
quired vacuum level, continue the
recovery at Step 4.
12) If the pressure remains below the
required level, close the low-pressure
valve on the manifold set and the
recovery tank valves. Disconnect the
hoses.
13) Because oil can be removed from the
HVAC system during recovery, the
Oil Drain port should be drained after
every usage. By draining this oil into
a measuring device, it can be deter-
mined how much refrigerant oil was
removed from the HVAC system.
See the “Oil Level Check” procedure
on page 7.
Operating Guide
Restart Procedure
Liquid refrigerant will flush the oil from the
compressor sump and cause the compressor
to seize or could damage the compressor
valve plates.
The RecoverX is designed for recovery of
vapor refrigerant only. It can also be used
for the traditional push-pull method of
recovering liquid refrigerant.
CAUTION: This unit IS NOT designed for the direct recovery of liquid refrigerant.
If the recovery unit was stopped during
operation, it may be necessary to balance
the internal pressures before the unit will
start.
• Turn Power Switch off (○).
• Stop refrigerant flow to the suction
port on the unit.
• Open “Bypass Valve”.
• Wait 30 seconds.
• Restart the recovery unit.
• Close “Bypass Valve”.
• Resume normal vapor recovery.
4
Troubleshooting Guide
Problem Possible Cause Solution
Compressor will not
start
• Power cord not plugged in • Plug in to energized 110V receptacle
• 110V receptacle not energized • Check 110V receptacle for power
• High Pressure Switch not reset • Reduce discharge pressure and reset.
• If switch will not reset, check dis-
charge for restrictions or schrader
core not fully depressed.
• Circuit Breaker is tripped • Reset circuit breaker
• Defective system switch • Replace switch
Unit starts but stops
after a short period
• Restriction on the discharge port • Open valve on recovery tank
• Ensure schrader core on discharge
port is fully depressed
• Check for other restrictions
• High differential pressure across
compressor
• Turn Bypass Valve to “OPEN.”
• Liquid refrigerant present in the
sump of the compressor
• Remove liquid refrigerant from
sump of compressor.
• Compressor oil level is too low
or too high.
• Check oil level and add or drain if
necessary
Unit will not perform
liquid push-pull
recovery
• System to be serviced does not
allow liquid recovery
• Use Vapor Recovery method
Compressor starts but
trips the circuit breaker
upon start up
UL Certified Rates to ARI Standard 740-98
Other Refrigerants:
YELLOW JACKET RecoverX is approved for use with the following refrigerants which
has not been certified for a particular recovery rate.
R-12, R-134a, R-401C, R-406A, R-500, R-401A, R-409A, R-401B, R-412A, R-411A, R
-407D, R-22, R-411B, R-502, R-407C, R-402B, R-408A, R-509.
R12 R134a R22 R500 R502
Vapor lbs./min .24 .20 .29 .24 .24
Liquid lbs./min N/A N/A N/A N/A N/A
Push-Pull lbs./min 10.4 9.3 8.8 9.6 7.6
Vacuum Level 15 in. Hg 15 in. Hg 15 in. Hg 15 in. Hg 15 in. Hg
9