York V* Series Quick start guide

TECHNICAL GUIDE
MAXA-MI$ER®
V* Series
Unitized Energy Recovery
Ventilators
ERV Unit with a Champion® Series Packaged Unit
ERV Unit with Predator® Packaged Unit
ERV Unit with Sunline® Packaged Unit
Energy recovery COMPONENT rated in
accordance with ARI Standard 1060-2000 and
certified to ARI. Actual performance in packaged
equipment may vary.
®
246681-YTG-B-0607
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
ETL Certified per UL 1995 and CSA 22.2
DESCRIPTION
• Reduces cooling load at design temperatures up to 4 tons per
1000 cfm of outside air.
• Reduces heating load up to 2.5 Tons Btuh per 1000 CFM of out-
side air.
• Dry energy transfer. Moisture in supply (intake) air stream is
transferred to exhaust air stream in a vapor state, eliminating
condensate plumbing from the UERV.
• Attaches directly to the York rooftop units. All mounting equip-
ment is provided.
• Separate fused power supply.
• Filters / mist eliminators are provided on the entering air open-
ings.
• Adjustable support legs are provided.
• Two modes of operation (Pivoting Wheel Models only)
• Recovery mode during normal energy recovery operation.
• Trueeconomizermodewhenoutsidesensorcallsfor
economizer operation (3 - 12.5 ton packaged units
equipped with economizers). U. S. Patent 5,548,970.
• Pivoting wheel models used with packaged unit with econo-
mizer. Sequence of operation controlled by economizer. (select
models only)
• Balancing dampers provided on VR, VH and VU Modules.
(Except Millennium or VR74 and VR122)
• Centrifugal blowers (both intake and exhaust for high static
capability and low sound levels).
• Heavy gauge galvanized steel cabinets corrosion protected with
powder paint process that match York units.
• Fully insulated cabinet.
• ARI certified internal enthalpy wheel is provided.
• Internal enthalpy wheel made of polymeric material with silica
gel impregnated into the material. The enthalpy wheel has a
five year limited warranty.
• Internal enthalpy wheels are easily cleanable. Large wheels (25
inch diameter and above) are split into easily removable pie
segments. Smaller wheels can be removed from the ERV.
• Continuous operation down to 10 ºF (-12 ºC) without defrost at
indoor relative humidity up to 40%. For temperatures below 10
ºF (-12 ºC), Optional Low Ambient Control Kit is required. Kit
includes temperature sensor to control the ERV before frost
build up can occur on recovery wheel.
Note: MAXA-MI$ER®UERV’s are designed for use with
rooftops using 14” high or greater roof curbs.

246681-YTG-B-0607
2Unitary Products Group
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
YORK UERV MODEL NOMENCLATURE . . . . . . . . . . . 3
APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
PRINCIPLE OF OPERATION . . . . . . . . . . . . . . . . . . . . .4
ARI STANDARD 1060-2000 FOR AIR-TO-AIR ENERGY
RECOVERY VENTILATION EQUIPMENT . . . . . . . . . . .4
ENERGY RECOVERY WHEEL . . . . . . . . . . . . . . . . . . . .4
CROSS LEAKAGE IN UERV’S (PURGE SECTORS) . . .5
OPTIONAL ACCESSORIES - FIELD INSTALLED . . . . 5
OPTIONAL ACCESSORIES - FACTORY INSTALLED 6
HOW TO SELECT THE PROPER AIR CONDITIONING
UNIT AND UNITARY ENERGY RECOVERY
VENTILATOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . 26
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
APPROVALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
OPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
SEQUENCE OF OPERATION: . . . . . . . . . . . . . . . . . . 27
UERV TROUBLESHOOTING GUIDE . . . . . . . . . . . . . 28
UERV BELOW 600 CFM WITH STATIONARY WHEEL
(NO ECONOMIZER) . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
UERV ABOVE 600 CFM WITH STATIONARY WHEEL
(NO ECONOMIZER) . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
UERV ABOVE 600 CFM WITH PIVOTING WHEEL (USED
WITH ECONOMIZER) . . . . . . . . . . . . . . . . . . . . . . . . . . 29
LIST OF FIGURES
Fig. # Pg. #
1 UNITIZED ENERGY RECOVERY VENTILATOR . . . .4
2 ENERGY RECOVERY WHEEL . . . . . . . . . . . . . . . . . .4
3 “P” SERIES PIVOTING WHEEL FOR UNITS
W/ECONOMIZERS . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
4 UERV DIMENSIONAL DATA - 018 THROUGH 060. .17
5 UERV DIMENSIONAL DATA - 036 THROUGH 072. .17
6 UERV DIMENSIONAL DATA - 078 THROUGH 150. .18
7 UERV DIMENSIONAL DATA - 180 THROUGH 300. .18
8 MILLENNIUM UNIT VR074 AND VR122 . . . . . . . . . .19
9 STAND ALONE UERV’S FOR SIDE BY SIDE DUCT
ARRANGEMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . .21
10 STAND ALONE UERV’S FOR OVER AND UNDER
DUCT ARRANGEMENTS . . . . . . . . . . . . . . . . . . . . . .22
11 HORIZONTAL SPLIT SYSTEM UERV’S FOR VH006
AND VH011 SERIES . . . . . . . . . . . . . . . . . . . . . . . . .23
12 UPFLOW SPLIT SYSTEM UERV’S . . . . . . . . . . . . . .24
LIST OF TABLES
Tbl. # Pg. #
1 UERV OUTSIDE AIR CFM SELECTION BY CFM . . . . 5
2 PERFORMANCE - 1 1/2 THROUGH 12 1/2 TON
UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 PERFORMANCE - 15 THROUGH 25 TON UNITS . . . 8
4 PERFORMANCE - PIVOTING WHEEL MODELS . . . . 9
5 SPECIFICATIONS AND ELECTRICAL DATA - 300
THROUGH 550 CFM ERV’S . . . . . . . . . . . . . . . . . . . 10
6 SPECIFICATIONS AND ELECTRICAL DATA - 600
THROUGH 1700 CFM ERV’S . . . . . . . . . . . . . . . . . . 11
7 SPECIFICATIONS AND ELECTRICAL DATA - 1500
THROUGH 2800 CFM ERV’S . . . . . . . . . . . . . . . . . . 12
8 SPECIFICATIONS AND ELECTRICAL DATA - 2800
THROUGH 3600 CFM ERV’S . . . . . . . . . . . . . . . . . . 13
9 SPECIFICATIONS AND ELECTRICAL DATA - 3400
THROUGH 5600 CFM ERV’S . . . . . . . . . . . . . . . . . . 14
10 SPECIFICATIONS AND ELECTRICAL DATA - 5500
THROUGH 6200 CFM ERV’S . . . . . . . . . . . . . . . . . . 15
11 SPECIFICATIONS AND ELECTRICAL DATA - 6000
THROUGH 13000 CFM UERV’S . . . . . . . . . . . . . . . . 16
12 BLOWER PERFORMANCE CHART - VR074 . . . . . . 20
13 BLOWER PERFORMANCE CHART - VR122 . . . . . . 20
14 YORK HORIZONTAL AND UPFLOW SPLIT SYSTEM
UERV MODELS 300 - 500 CFM . . . . . . . . . . . . . . . . . 25
15 YORK HORIZONTAL AND UPFLOW SPLIT SYSTEM
UERV MODELS 600 - 1,000 CFM . . . . . . . . . . . . . . . 25

Unitary Products Group 3
246681-YTG-B-0607
YORK UERV MODEL NOMENCLATURE
* CFM is ERV wheel rating. This may vary depending on unit cabinet pressure drop.
** These CFM ranges are dependant upon blower motor selection.
*** Only options available for VR074 & VR122.
Digit Example
Model # Model Description Options
1 V Product Category V = Ventilator
2 R Wheel Type
R= Rooftop Stationary
H= Horizontal
O= Stand Alone Over and Under, Stationary
S= Stand Alone Side by Side
P= Rooftop Pivoting (036-060 & 078-150 only)
U= Upflow
3, 4 & 5 028 CFM*
006= 300 to 550
011= 600 to 1000
020= 1100 to 1700
028= 2200 to 2800** 1500 to 2200**
036= 2800 to 3600
046= 3400 to 4600
062= 5500 to 6200** 4800 to 5600**
074= 6000 to 8000
122= 8000 to 13000
6, 7 & 8 A12
York Rooftop
Cabinet
A05= D*NA/NH/NP 018-060
B05= D*EB/EH/EM 018-060 & B*HA/HH/HP 018-060
A06= DM/DF/DH 036-072 & BQ 036-060
A12= DM/DF/DH/DJ 078-150 & BP078-150
A15= DM/DH 180 & BP 180
A25= DM/DH 240-300, DJ180-300, DR180-300 & BQ 240
A40=
B12=
Stand Alone N00= None
York Furnace / Air
Handler Cabinet
Z02=P*DH/P*XD-V 10-037
Z03=P*UR/P*XU/PXU-V 8-037
X03=N*AH/N*VS B--G2FD 16-024S,030S,036S
Z04=P*HU/P*DU/P*DU-V/P*HU-L/P*DU-L 16-064,080
Z04=P*UR/P*XU/PXU-V 10-055
Y04=N*AH/N*VS B--G2FD 16-036S,042S,048S
Z05=P*HU/P*DU/P*DU-V/P*HU-L/P*DU-L 20-064,080,092
Z05=P*UR/P*XU/PXU-V 16-075
Z05=P*UR/P*XU/PXU-V 20-095
Y05=P*UR/P*XU/PXU-V 20112,130
X05=P*DH/P*XD-V 20-075
V05=N*AH/N*VS B--G2FD 14/20-048S,060S,061H
Z03=P*HU/P*DU/P*DU-V/P*HU/P*DU-L 12-032, 048, 060
Y03=P*DH/P*XD-V 12-055,075
W03=G*C 12-050,075
Z04=P*HU/P*DU/P*DU-V/P*HU-L/P*DU-L 12-080
Z04=P*UR/P*XU/PXU-V 12-075
X04=G*C 16-075,100
Z05=P*HU/P*DU/P*DU-V/P*HU-L/P*DU-L 16-092
Z05=P*UR/P*XU/PXU-V 14-095
Y05=P*HU/P*DU/P*DU-V/P*HU-L/P*DU-L 20-104
X05=P*DH/P*XD-V 16-075
W05=P*DH/P*XD-V 20-112
U05=G*C 20-100,125,150
9 H Blower Speed H = High Speed**
M = Mediu Speed** V = Variable Speed (VR074 only)
L = Constant Volume (VR122)
10 4 Voltage 1= 110v-1ph
2= 208/230v-3ph
4= 460v-3ph
5= 575v-3ph
8= 460v-1ph
9= 208/320v-1ph
11 W Duct Type A= no selection on Rooftop Units W= Wall Sleeve (Upflow Only) D = Ducted System
12 & 13 L2 Additional Options
AA= No Option
L1= Low Ambient Kit (LAK) *
L2= LAK & Motorized Outside Air (MOA) *
L3= LAK, MOA & Stop-Start-Job (SSJ) (not used on P models) *
L4= LAK, MOA, SSJ & Pressure Sensor (PS) (not used on P)
L5= LAK & SSJ (not used on P models) *
L6= LAK, SSJ & PS (not used on P models)
L7= LAK & PS
L8= LAK, MOA and PS
M1= Motorized Outside Air (MOA) *
M2= MOA, and Stop Start-Jog (SSJ) (not used on P models) *
M3= MOA, SSJ and Pressure Sensor (PS) (not used on P models)
M4= MOA and PS
S1= Stop-Start-Job (SSJ) (not used on P models) *
S2= SSJ and Pressure Sensor (PS) (not used on P models)
P1= Pressure Sensor (PS)
14 1 Product Generation 1= 1st Generation

246681-YTG-B-0607
4Unitary Products Group
APPLICATIONS
Unitized Energy Recovery Ventilators (UERV) are used with
the York rooftop packaged units. The internal wheel provides
sensible and latent energy exchange between the entering
and exhaust air streams of a building. This allows a substan-
tial amount of the energy, which is normally lost in the
exhaust air stream to be returned into the entering air. Ideal
applications are areas that have cold or hot temperatures, or
areas that have high humidity or very low humidity (recover
exhaust air from buildings that have humidifiers to add
humidity). Application software is available to provide the
energy and dollar savings for all areas of the United States
and Canada.
PRINCIPLE OF OPERATION
The UERV enthalpy wheel contains parallel layers of a poly-
meric material that are impregnated with silica gel (desic-
cant). The wheel is located in the entering (intake) air and
exhaust air streams of the ventilation equipment. As the
wheel rotates through each air stream, the wheel surface
adsorbs sensible and latent energy. In the heating mode, the
wheel rotates to provide a constant transfer of heat from the
exhaust air stream to the colder intake air stream. During the
cooling season, the process is reversed. On units equipped
with an economizer (3 - 12.5 tons), the wheel pivots out of the
air stream to allow economizer to operate normally for "free
cooling" when outdoor temperature and humidity is accept-
able. During economizer operation, the UERV exhaust
blower continues to run, providing power exhaust for the sys-
tem. The intake blower is de-energized during economizer
operation.
ARI STANDARD 1060-2000 FOR AIR-TO-AIR
ENERGY RECOVERY VENTILATION EQUIPMENT
The Air-Conditioning and Refrigeration Institute (ARI) issued
Standard 1060-2000 to certify air-to-air energy recovery ven-
tilators. This standard deals specifically with the ratings of the
Energy Recovery Wheel that is incorporated into the Energy
Recovery Ventilator (ERV). All of the York ERV's have an ARI
certified energy recovery wheel. The data shown in the spec-
ification charts is the ARI certified ratings for the wheel.
Actual performance in the ERV may vary.
Critical Terms for Standard 1060 are as follows:
1. Effectiveness. The measured energy recovery effec-
tiveness not adjusted to account for that portion of the
psychrometric change in the leaving supply air (Station
2) that is the result of leakage of entering exhaust air
(Station 3) rather than exchange of heat or moisture
between the air streams.
2. Net Effectiveness. The measured recovery effective-
ness adjusted to account for that portion of the psycho-
metric change in the leaving supply air (Station 2) that is
the result of leakage of the entering exhaust air (Station
3) rather than exchange of heat or moisture between the
air streams.
3. Exhaust Air Transfer Ratio (EATR). The tracer gas
concentration difference between the leaving supply air
(Station 2) and entering supply (outdoor) air stream (Sta-
tion 1) divided by the tracer gas concentration in the
entering exhaust (return) air (Station 3) at the 100%
rated air-flow, expressed as a percentage.
4. Outdoor Air Correction Factor (OACF). The entering
supply (outdoor) airflow (Station 1) divided by the mea-
sured (gross) leaving supply airflow (Station 2).
ENERGY RECOVERY WHEEL
The heart of the Energy Recovery Ventilator is the Energy
Recovery Wheel (defined by ARI as a rotary heat exchanger).
The wheel has a patented design of parallel layers of
wrapped polymeric material that is impregnated with a silica
gel (desiccant). This unique design makes it the only truly
cleanable wheel on the market today. The small wheels (30
inch diameter and smaller) are slide out cassettes, and the
larger wheels have pie segments that are removable for
cleaning.
FIGURE 1 - UNITIZED ENERGY RECOVERY
VENTILATOR
FIGURE 2 - ENERGY RECOVERY WHEEL

Unitary Products Group 5
246681-YTG-B-0607
CROSS LEAKAGE IN UERV’S (PURGE SECTORS)
The issue of cross leakage in rotary wheel based UERV's
used in space conditioning applications is often misunder-
stood. As a result, many systems are installed with purge
sectors and the additional fan capacity required to allow
these sectors to function when in fact they are unnecessary.
A better understanding of the rational for the purge sector,
and its history, allows us to dispense with the purge sector, its
added first cost and continuing cost of operation.
A purge sector minimizes the carry over cross leakage from
the exhaust into the supply (outside air) air stream by shunt-
ing a portion of the supply air back into the exhaust air stream
across the seal separating the exhaust and supply. This is
required in industrial applications where the exhaust carries
contaminants. This typically results in air volume being 15%
to 20% higher to get the desired air intake, and the cost asso-
ciated with it.
In space conditioning applications, where the ventilation is
operating to maintain acceptable indoor air quality, there are
no contaminants in concentrations large enough to cause
concern. Cross leakage in the UERV system results in a
small amount of the exhaust air, typically less than 5% in bal-
anced airflow, returning to the space. This is not contami-
nated air, as some would suggest. It is however air that
effectively never left the space. The operation cost of moving
this air is far less than that required for a purge sector. Do not
use the York UERV's in applications that have concentrations
of contaminants.
OPTIONAL ACCESSORIES - FIELD
INSTALLED
UERV Equipment Support - 8 inch (203 mm) high base for
support of the exhaust and intake end of the UERV. Must be
ordered separately from the UERV.
Equipment Support
UERV Part No.
VR006 1ES0401
VR/P011 1ES0402
VR/P020 1ES0402
VR/P028 1ES0402
Equipment Support
UERV Part No.
VR036 1ES0403
VR046 1ES0403
VR062 1ES0404
VR074
VR122
Roof Curb - A 14 or 24 inch (355 or 610 mm) roof curb is
required to match supply and exhaust openings of the UERV
with the rooftop units. York provides a full line of roof curbs to
match the specified unit. See specification pages for required
curb. Must be ordered separately from UERV.
Stand Alone Balancing Damper - Balancing dampers are
used with VO and VS models when ERV is connected to the
rooftop unit, not to ductwork on the roof.
TABLE 1: UERV OUTSIDE AIR CFM SELECTION BY CFM
Unit-Tons 300-550 600-1000 1100-1700 1500-2800 2800-3600 3400-4600 4800-5600 5500-6200 6000-8000 8000-13000
Rooftop
1.5 - 6 1.5 - 6 Stand Alone type ERV’s are available for all tonnage sizes.
7.5 - 12.5 7.5 - 12.5 7.5 - 12.5
15 - 25 15 - 25 15 - 25 15 - 25 15 - 25
30 - 50 30 - 50
Upflow 1.5 - 5 1.5 - 5
Horizontal 1.5 - 5 1.5 - 5 Stand Alone ERV’s are available for equipment room applications.

246681-YTG-B-0607
6Unitary Products Group
* These balancing dampers work best with”VO” stand alones.
** These balancing dampers work best with”VS” stand alones.
OPTIONAL ACCESSORIES - FACTORY
INSTALLED
Low Ambient Control Kit - Prevents frost formation on
energy wheel heat transfer surfaces by terminating the intake
blower operation when discharge air temperature falls below
a field selectable temperature setting. Intake blower opera-
tion resumes operation after temperature rises above the
adjustable temperature differential.
Pressure Sensor - Measurement device on the UERV to
determine airflow across the Wheel.
Motorized Intake Air Damper - Damper mounts in the out-
door air intake hood. It opens when the UERV is energized
and closes when de-energized.
Stop-Start-Jog - Function that rotates the Enthalpy Wheel
(non-pivoting models) on a preset timer to prevent contami-
nation of the wheel during economizer operation.
ERV Option Codes (ex.: VR028A12H4AL3 would be an R28
series high speed 460 volt UERV with a Low Ambient kit,
Motorized Outside Air, and Stop-Start-Jog kit.)
L1 - Low Ambient Kit (LAK) *
L2 - LAK & Motorized. Outside Air (MOA) *
L3 - LAK, MOA, & Stop-Start-Jog (SSJ) *
L4 - LAK, MOA, SSJ, & Pressure Sensor (PS)
L5 - LAK and SSJ *
L6 - LAK, SSJ, and PS
L7 - LAK and PS
L8 - LAK, MOA, and PS
M1 - Motorized Outside Air (MOA) *
M2 - MOA and Stop-Start-Jog (SSJ) *
M3 - MOA, SSJ, and Pressure Sensor (PS)
M4 - MOA and PS
S1 - Stop-Start-Jog (SSJ) *
S2 - SSJ and Pressure Sensor (PS)
P1 - Pressure Sensor (PS)
NOTE: * denotes only options available for VR074 & VR122.
HOW TO SELECT THE PROPER AIR
CONDITIONING UNIT AND UNITARY ENERGY
RECOVERY VENTILATOR
1. Determine the air conditioning load requirements with
the required amount of outside air without an UERV.
2. Select the proper UERV for the outside air CFM require-
ments and calculate the tonnage reduction through the
York UERV software program.
3. Select the air conditioning unit required by reducing the
load determined in step 1 by the reduction in step 2.
(Example: If the load in Step 1 was 10 tons, and the
reduction in Step 2 was 2.5 tons, select a 7.5 ton unit.)
4. Select the proper UERV based on the select unit. The
York part numbering scheme is as follows:
RSI Model York
Model Description Used With
80-950-23 1DB0402 * Balancing Damper, “VO and VS” D*NA/NH/N; 018-060
80-950-24 1DB0401 * Balancing Damper, “VO and VS” D*EB/EH/EM/B*HA/HH 018-060
80-950-13 1DB0403 * Balancing Damper, “VO and VS” DM/DF/DH 036-072 & BQ 036-060
80-950-29 1DB0404 * Balancing Damper, “VO and VS” DM/DF/DH 078-150 & BP 078-150
80-950-19 1DB0405 ** Balancing Damper, “VO and VS” DM/DH 180 & BP 180
80-950-18 1DB0406 ** Balancing Damper, “VO and VS” DM/DH 240-300, DJ/DR 180-300 & BQ 240
Ventilator
Wheel Type
CFM = 2800
York Unit Cabinet Size
Blower Speed (H for High, M for Medium)
Voltage
Duct Type (A, D or W)
Option Code (see list above)
Generation
VR028 A12 H 4 A L3 1

Unitary Products Group 7
246681-YTG-B-0607
Note 1: Complete York ERV model number includes the electrical information. Example DM 060
needing 500 CFM outside of air at 230 volts/3 phase. Model would be a VR006A06H2AAA1.
TABLE 2: PERFORMANCE - 1 1/2 THROUGH 12 1/2 TON UNITS
“R” Series Stationary Wheel for Units without Economizers
York
Packaged Unit
Model No.
Unit
Size
(Tons)
ERV CFM
Range Matching ERV
Model Voltage &
Phase Voltage
Code
Nominal ARI Data (Total
CFM Net Effectiveness
Heating Cooling
D*EB 018-060
D*EH 018-060
D*EM 036-060
B*HA 018-060
B*HH 018-060
B*HP 024-048
1.5 - 5 300-550 VR006B05H
110v-1ph 1
500 65% 64%
208/230v-1ph 9
208/240v-3ph 2
460v-3ph 4
D*NH 018-060
D*NA 018-060
D*NP 024-048
D*NZ 024-060
1.5 - 5 300-550 VR006A05H
110v-1ph 1
500 65% 64%
208/230v-1ph 9
208/240v-3ph 2
460v-3ph 4
DM 036-072
DF 036-072
DH 036-060
BQ 036-060
3 - 6
300-550 VR006A06H
110v-1ph 1
500 65% 64%
208/230v-1ph 9
208/240v-3ph 2
460v-3ph 4
600-1000 VR011A06H
208/230v-1ph 9
900 73% 72%
208/230v-3ph 2
460v-3ph 4
575v-3ph 5
DM 090-102
DF 090-102
DH 078-102
BP 090
7.5 - 8.5
600-1000 VR011B12H 208/230v-3ph 2 900 73% 72%460v-3ph 4
575v-3ph 5
1100-1700 VR020B12H 208/230v-3ph 2 1600 65% 64%460v-3ph 4
575v-3ph 5
DM 078
DM 120-150
DF 078
DF120
DH 120-150
DJ 150
DR 090-150
BP 078
BP 120-150
7.5 -
12.5
600-1000 VR011A12H 208/230v-3ph 2 900 73% 72%460v-3ph 4
575v-3ph 5
1100-1700 VR020A12H 208/230v-3ph 2 1600 65% 64%460v-3ph 4
575v-3ph 5
1500-2200 VR028A12M 208/230v-3ph 2 1950 71% 70%460v-3ph 4
575v-3ph 5
2200-2800 VR028A12H 208/230v-3ph 2 2600 65% 63%460v-3ph 4
575v-3ph 5

246681-YTG-B-0607
8Unitary Products Group
Note 1: Complete York ERV model number includes the electrical information. Example: DM180 needing 2800 CFM
outside of air at 230 volts/3 phase. Model would be a VR028A15H2AAA1.
Note 2: For VR074 and VR122 units used with an economizer must have the Start-Stop-Jog (SSJ) option.
TABLE 3: PERFORMANCE - 15 THROUGH 25 TON UNITS
Use this table to determine ventilation and size requirements. Table shows York packaged units and matching ERV model,
Air Flow Range, and ARI rated Net Effectiveness at 100% of rated CFM.
“R” Series Stationary Wheel for Units without Economizers
York
Packaged Unit
Model No.
Unit
Size
(Tons)
ERV CFM
Range Matching ERV
Model Voltage &
Phase Voltage
Code
Nominal ARI Data (Total
CFM Net Effectiveness
Heating Cooling
DM 180
DH 180
BP 180 15
1500-2200 VR028A15M 208/230v-3ph 2 1950 71% 70%460v-3ph 4
575v-3ph 5
2200-2800 VR028A15H 208/230v-3ph 2 2600 65% 63%460v-3ph 4
575v-3ph 5
2800-3600 VR036A15H 208/230v-3ph 2 3100 65% 63%460v-3ph 4
575v-3ph 5
3400-4600 VR046A15H 208/230v-3ph 2 3900 65% 63%460v-3ph 4
575v-3ph 5
4800-5600 VR062A15M 208/230v-3ph 2 4125 71% 70%460v-3ph 4
575v-3ph 5
5500-6200 VR062A15H 208/230v-3ph 2 5500 65% 63%460v-3ph 4
575v-3ph 5
DM 240
DM 300
DH 240
BP 240
BQ 240
DJ 180
DJ 210
DJ 240
DJ 300
DR 180
DR 240
DR 300
15 - 25
2200-2800 VR028A25H 208/230v-3ph 2 2600 65% 63%460v-3ph 4
575v-3ph 5
2800-3600 VR036A25H 208/230v-3ph 2 3100 65% 63%460v-3ph 4
575v-3ph 5
3400-4600 VR046A25H 208/230v-3ph 2 3900 65% 63%460v-3ph 4
575v-3ph 5
4800-5600 VR062A25M 208/230v-3ph 2 4125 71% 70%460v-3ph 4
575v-3ph 5
5500-6200 VR062A25H 208/230v-3ph 4 5500 65% 63%460v-3ph 5
575v-3ph 2
(See note 2) (See
note 2)
6000-8000 VR074A40* 208/230v-3ph 2 6600 65% 63%460v-3ph 4
575v-3ph 5
8000-13000 VR122A40* 208/230v-3ph 2 10800 65% 63%460v-3ph 4
575v-3ph 5

Unitary Products Group 9
246681-YTG-B-0607
Note 1: Complete York ERV model number includes the electrical information. Example DM 060
needing 800 CFM outside of air at 230 volts/3 phase. Model would be a VP011A06H2AAA1.
2: Predator models D/B*078-150, with ERV must use “slab” type economizers and downflow position.
TABLE 4: PERFORMANCE - PIVOTING WHEEL MODELS
“P” Series Pivoting Wheel for Units with Economizers
York
Packaged Unit
Model No.
Unit
Size
(Tons)
ERV
CFM
Range
Max.
CFM
Power
Exhaust
Matching
ERV
Model
Voltage &
Phase Voltage
Code
Nominal ARI Data (Total
CFM Net Effectiveness
Heating Cooling
DM 036-072
DF 036-072
DH 036-060
BQ 036-060
3 - 6 600-
1000 1900 VP011A06H
208/230v-1ph 9
900 73% 72%
208/240v-3ph 2
460v-3ph 4
575v-3ph 5
DM 090-102
DF 090-102
DH 078-102
BP 090
(See note 2)
7.5 - 8.5
600-
1000 1900 VP011B12H 208/230v-3ph 2 900 73% 72%460v-3ph 4
575v-3ph 5
1100-
1700 3000 VP020B12H 208/230v-3ph 2 1600 65% 64%460v-3ph 4
575v-3ph 5
DM 078
DM 120-150
DF 078
DF120
DH 120-150
DJ 150
DR 090-150
BP 078
BP 120-150
(See note 2)
7.5 -
12.5
600-
1000 1900 VP011A12H 208/230v-3ph 2 900 73% 72%460v-3ph 4
575v-3ph 5
1100-
1700 3000 VP020A12H 208/230v-3ph 2 1600 65% 64%460v-3ph 4
575v-3ph 5
1500-
2200 3450 VP028A12M 208/230v-3ph 2 1950 71% 70%460v-3ph 4
575v-3ph 5
2200-
2800 4200 VP028A12H 208/230v-3ph 2 2600 65% 63%460v-3ph 4
575v-3ph 5
FIGURE 3 - “P” SERIES PIVOTING WHEEL FOR UNITS W/ECONOMIZERS
Enthalpy Wheel
(with removable pie
segments)
Exhaust
Air Blower
(
ener
g
ized
)
Outsid
e
Air Blower
(energized)
Exhaust
Air Blower
Fresh Air Damper
(opens during economizer
operation)
Unit & UERV Disconnect
(provided correct wire size used
for both units and
local code approval)
Enthalpy Wheel
Pivoted out of Intake and
Discharge Air Stream

246681-YTG-B-0607
10 Unitary Products Group
TABLE 5: SPECIFICATIONS AND ELECTRICAL DATA - 300 THROUGH 550 CFM ERV’S
208/230v/460-1ph
Motor - hp
Wheel Size (dia x width) -in
Motor Speed -rpm
Motor Speed(s)
Bearing Type
Full Load Amps
Service Factor
Motor - hp
Wheel Size (dia x width) -in
Motor Speed -rpm
Motor Speed(s)
Bearing Type
Full Load Amps-Stationary
Full Load Amps-Pivoting
Service Factor
Potential Volts
Motor Speed -rpm
Full Load Amps
MCA
OCPD
Wheel Depth
Wheel Diameter -in
Construction
Nominal Airflow CFM
EATR - -0.50 H2O
EATR - 0.00 H2O
EATR - +0.50 H2O
OACF - -0.50 H2O
OACF - 0.00 H2O
OACF
- +
0
.
50
H
2
O
Latent
100% Airflow Heating 60%
75% Airflow Heating 65%
100% Airflow Cooling 60%
75% Airflow Cooling 65%
100% Airflow Heating 60%
75% Airflow Heating 65%
100% Airflow Cooling 60%
75% Airflow Cooling 65%
Curb A/C Unit Curb Height - in
Shipping Weight - lbs.
Net Weight - lbs.
Note 1: A stepdown transformer is provided to stepdown high voltage primary to 115 volt secondary.
10
1.59%
9.90%
500 @ .6Δ
2
1.02%
0.20%
0.00%
Exhaust Air Blower Sleeve
1.1
Wheel Electrical
Data
115
1050
5.5 x 6.3
2
0.25 / PSC
1780
Specifications and Electrical Data - 300 through 550 CFM ERV's
Fresh Air Blower
VR006 - Rooftop Stationary
0.2 / PSC
3.8
2
5.5 x 6.3
208/230v/460-3phLine Voltage - 60hz
1780
1.1
115v-1ph
3.8
NA
0.6
Sleeve
Weights
Total Electrical
Net
Effectiveness
Total
Effectiveness
Thermal Ratings @ 0" Pressure Diff.
Enthalpy Wheel
ARI Airflow Data
Wheel Data
73%
8.7
1.33%
68%
73%
68%
Sensible Total
65%
73%
155
14
198
69%
64%
69%
65%
70%
Model Numbers
64%
68%
73%
68%
70%
One Piece / Polymeric
19.3
VH006 - Horizontal Split System
VU006 - Upflow Split System
2: On Horizontal and upflow UERVs, the transformer is provided for field installation.
VS006 - S/S Stand Alone Stationary
VO006 - O/U Stand Alone Stationary

Unitary Products Group 11
246681-YTG-B-0607
TABLE 6: SPECIFICATIONS AND ELECTRICAL DATA - 600 THROUGH 1700 CFM ERV’S
208/ 230v-
1ph
208/ 230v-
3ph
460v-
1ph
460v-
3ph
208/ 230v-
3ph 460v-3ph 575v-3ph
Motor - hp
Wheel Size (dia x width) -in
Motor Speed -rpm
Motor Speed(s)
Bearing Type
Full Load Amps 3.8 1.9 1.4
Service Factor
Motor - hp Stationary
Motor - hp Pivoting
Wheel Size (dia x width) -in
Motor Speed -rpm
Motor Speed(s)
Bearing Type
Full Load Amps-Stationary 3.4 3.4 1.5 1.5 3.8 1.9 1.4
Full Load Amps-Pivoting 3.4 3.4 1.5 1.5 5.6 2.8 2.0
Service Factor
Potential Volts
Motor Speed -rpm
Full Load Amps
MCA - Stationary 8.25 8.25 4.4 4.4 9.15 4.9 3.8
OCPD - Stationary 10 10 6 6 12 6 5
MCA - Pivoting 8.25 8.25 4.4 4.4 11.4 6 4.5
OCPD - Pivoting 10 10 6 6 15 8 6
Wheel Depth - in
Wheel Diameter - in
Construction / Media
Nominal Airflow CFM
EATR - -1.00 H2O
EATR - 0.00 H2O
EATR - +1.00 H2O
OACF - -1.00 H2O
OACF - 0.00 H2O
OACF
-+
1.00 H
2O
Sensible Latent Sensible Latent Total
100% Airflow Heating 76% 68% 68% 61% 65%
75% Airflow Heating 81% 73% 72% 67% 71%
100% Airflow Cooling 76% 68% 68% 61% 64%
75% Airflow Cooling 81% 73% 72% 67% 70%
100% Airflow Heating 76% 68% 68% 61% 65%
75% Airflow Heating 81% 73% 72% 67% 71%
100% Airflow Cooling 76% 68% 68% 61% 64%
75% Airflow Cooling 81% 73% 72% 67% 70%
Curb A/C Unit Curb Hgt - in
Shipping Weight - lbs.
Net Weight - lbs.
Net
Effective-
ness
Thermal Ratings @ 0" Pressure Diff.
Total
Effective-
ness
Total
73%
72%
76%
78%
0.00%
Ball
Enthalpy
Wheel ARI
Rating Data 0.97%
Sleeve
Wheel
Electrical
Data
208 / 230 208 / 230
1050
Wheel Data
900 @ 1.0Δ
0.00%
Adjustable Sheave
14 on A06 24
One Piece / Polymeric
1.19%
1.34%
9.30%
0.70%
1.16%
72%
73%
1.29%
76%
78%
Fresh Air
Blower
1.0 / Belt
VP020 - Rooftop Pivoting
9 x 9
1725
VR020 - Rooftop Stationary
Total
Electrical
3.4
1
1
3
Exhaust Air
Blower
Weights 318 425
245 345
0.40%
.5 / PSC
10 x 6 AT
1120 / 960 / 850
1.0 / Belt
9 x 9
1725
1600 @ .95Δ
7.80%
3
One Piece / Polymeric
VP011 - Rooftop Pivoting
0.6
.5 / PSC
1050
10 x 6 AT
1120 / 960 / 850
3
Ball
0.6
Model Numbers
Line Voltage - 60hz
.5 / PSC
Sleeve
1.5 / Belt
VR011 - Rooftop Stationary
25.3 30.346
0.97%
1.15
1.15
3
Adjustable Sheave
VH011 - Horizontal Split System
VU011 - Upflow Split System
Note 1: On Horizontal and upflow UERVs, the transformer is field installed.
VO011 - O/U Stand Alone
VS011 - S/S Stand Alone
VO020 - O/U Stand Alone
VS020 - S/S Stand Alone
Note 2: Pivoting electrical data applies to VP models only.

246681-YTG-B-0607
12 Unitary Products Group
TABLE 7: SPECIFICATIONS AND ELECTRICAL DATA - 1500 THROUGH 2800 CFM ERV’S
* Electric data is for (A12) DM/DF/DH/DJ 078-150 and BP 078-150 only.
** Electric data is for (A15 and A25) DM/DH/DJ/DR 180-300 and BQ 240 only.
Note: Pivoting electrical data applies to VP models only.
Model Numbers * VR028 - Rooftop Stationary
* VP028 - Rooftop Pivoting
VO028 - O/U Stand Alone
** VR028 - Rooftop Stationary
VS028 - S/S Stand Alone
Line Voltage - 60hz 208/230v-3ph 460v-3ph 575v-3ph 208/230v-3ph 460v-3ph 575v-3ph
Fresh Air
Blower
Motor - hp / type 1.5 / Belt 2 / Belt
Wheel Size (dia x width) - in 10 x 10 10 x 10
Motor Speed - rpm 1725 1725
Motor Speed(s) Adjustable Sheave Adjustable Sheave
Bearing Type Ball Ball
Full Load Amps 5.6 2.8 2 6.6 3.3 2.4
Service Factor 1.15 1.15
Exhaust Air
Blower
Motor - hp Stationary 1.5 / Belt 2 / Belt
Motor - hp Pivoting 3 / Belt -
Wheel Size (dia x width) - in 10 x 10 10 x 10
Motor Speed - rpm 1725 1725
Motor Speed(s) Adjustable Sheave Adjustable Sheave
Bearing Type Ball Ball
Full Load Amps-Stationary 5.6 2.8 2 6.6 3.3 2.4
Full Load Amps-Pivoting 9 4.4 3.6 - - -
Service Factor 1.15 1.15
Wheel
Electrical
Data
Motor - hp (1 phase) 0.17 0.17
Potential Volts 200-208 / 230 200-208 / 230
Motor Speed - rpm 1725 1725
Full Load Amps 1.1 1.1
Total
Electrical
MCA - Stationary 13.7 7.4 5.6 16 8.6 6.6
OCPD - Stationary 20 10 7 20 10 7
MCA - Pivoting 18 9.4 7.6 - - -
OCPD - Pivoting 25 12 10 - - -
Wheel
Data Wheel Depth x Diameter - in 3 x 37.759 3 x 37.759
Construction / Media Type Segmented Pies / Polymeric Segmented Pies / Polymeric
Enthalpy
Wheel ARI
Rating Data
Nominal Airflow CFM 2600 @ .95Δ2600 @ .95Δ
EATR - -1.00 H2O 6.10% 6.10%
EATR - 0.00 H2O 0.40% 0.40%
EATR - +1.00 H2O 0.00% 0.00%
OACF - -1.00 H2O 0.99% 0.99%
OACF - 0.00 H2O 1.13% 1.13%
OACF - +1.00 H2O 1.23% 1.23%
Thermal Ratings @ 0” Pressure Diff. Sensible Latent Total Sensible Latent Total
Total
Effective-
ness
100% Airflow Heating 68% 60% 65% 68% 60% 65%
75% Airflow Heating 74% 67% 71% 74% 67% 71%
100% Airflow Cooling 68% 60% 63% 68% 60% 63%
75% Airflow Cooling 74% 67% 70% 74% 67% 70%
Net
Effective-
ness
100% Airflow Heating 68% 60% 65% 68% 60% 65%
75% Airflow Heating 74% 67% 71% 74% 67% 71%
100% Airflow Cooling 68% 60% 63% 68% 60% 63%
75% Airflow Cooling 74% 67% 70% 74% 67% 70%
Curb A/C Unit Curb Height - in 24 on A12, 14 on A15 & A25 24 on A12, 14 on A15 & A25
Weights Shipping Weight - lbs. 470 470
Net Weight - lbs. 395 395

Unitary Products Group 13
246681-YTG-B-0607
TABLE 8: SPECIFICATIONS AND ELECTRICAL DATA - 2800 THROUGH 3600 CFM ERV’S
Model Numbers VR036 - Rooftop Stationary
VS036 - S/S Stand Alone VO036 - O/U Stand Alone
Line Voltage - 60hz 208/230v-3ph 460v-3ph 575v-3ph 208/230v-3ph 460v-3ph 575v-3ph
Fresh Air
Blower
Motor - hp / type 3 / Belt 2 / Belt
Wheel Size (dia x width) - in 12 x 9 12 x 9
Motor Speed - rpm 1725 1725
Motor Speed(s) Adjustable Sheave Adjustable Sheave
Bearing Type Ball Ball
Full Load Amps 9.4 4.3 3.2 6.6 3.3 2.4
Service Factor 1.15 1.15
Exhaust Air
Blower
Motor - hp Stationary 3 / Belt 2 / Belt
Wheel Size (dia x width) - in 12 x 9 12 x 9
Motor Speed - rpm 1725 1725
Motor Speed(s) Adjustable Sheave Adjustable Sheave
Bearing Type Ball Ball
Full Load Amps-Stationary 9.4 4.3 3.2 6.6 3.3 2.4
Service Factor 1.15 1.15
Wheel
Electrical
Data
Motor - hp (1 phase) 0.50 0.50
Potential Volts 200-208 / 230 200-208 / 230
Motor Speed - rpm 1725 1725
Full Load Amps 2.7 2.7
Total
Electrical MCA - Stationary 22.4 10.9 8.4 16.1 18.6 6.6
OCPD - Stationary 30 15 9 20 12 9
Wheel
Data Wheel Depth x Diameter - in 3 x 41.825 3 x 41.825
Construction / Media Type Segmented Pies / Polymeric Segmented Pies / Polymeric
Enthalpy
Wheel ARI
Rating Data
Nominal Airflow CFM 3100 @ .9Δ3100 @ .9Δ
EATR - -1.00 H2O 4.90% 4.90%
EATR - 0.00 H2O 1.30% 1.30%
EATR - +1.00 H2O 0.30% 0.30%
OACF - -1.00 H2O 0.99% 0.99%
OACF - 0.00 H2O 1.07% 1.07%
OACF - +1.00 H2O 1.12% 1.12%
Thermal Ratings @ 0” Pressure Diff. Sensible Latent Total Sensible Latent Total
Total
Effective-
ness
100% Airflow Heating 68% 60% 65% 68% 60% 65%
75% Airflow Heating 74% 67% 71% 74% 67% 71%
100% Airflow Cooling 68% 60% 63% 68% 60% 63%
75% Airflow Cooling 74% 67% 70% 74% 67% 70%
Net
Effective-
ness
100% Airflow Heating 68% 60% 65% 68% 60% 65%
75% Airflow Heating 74% 67% 71% 74% 67% 71%
100% Airflow Cooling 68% 60% 63% 68% 60% 63%
75% Airflow Cooling 74% 67% 70% 74% 67% 70%
Curb A/C Unit Curb Height - in 24 24
Weights Shipping Weight - lbs. 571 571
Net Weight - lbs. 475 475

246681-YTG-B-0607
14 Unitary Products Group
TABLE 9: SPECIFICATIONS AND ELECTRICAL DATA - 3400 THROUGH 5600 CFM ERV’S
Model Numbers VR046 - Rooftop Stationary
VS046 - S/S Stand Alone VO046 - O/U Stand Alone
Line Voltage - 60hz 208/230v-3ph 460v-3ph 575v-3ph 208/230v-3ph 460v-3ph 575v-3ph
Fresh Air
Blower
Motor - hp / type 5 / Belt 3 / Belt
Wheel Size (dia x width) - in 12 x 12 12 x 12
Motor Speed - rpm 1725 1725
Motor Speed(s) Adjustable Sheave Adjustable Sheave
Bearing Type Ball Ball
Full Load Amps 14.8 7 5.1 9 4.4 3.4
Service Factor 1.15 1.15
Exhaust Air
Blower
Motor - hp Stationary 5 / Belt 3 / Belt
Wheel Size (dia x width) - in 12 x 12 12 x 12
Motor Speed - rpm 1725 1725
Motor Speed(s) Adjustable Sheave Adjustable Sheave
Bearing Type Ball Ball
Full Load Amps-Stationary 14.8 7 5.1 9 4.4 3.4
Service Factor 1.15 1.15
Wheel
Electrical
Data
Motor - hp (1 phase) 0.5 0.5
Potential Volts 200-208 / 230 200-208 / 230
Motor Speed - rpm 1150 1150
Full Load Amps 1.2 1.2
Total
Electrical MCA - Stationary 34.5 17 12 22 11 8.7
OCPD - Stationary 40 25 15 30 15 12
Wheel
Data Wheel Depth x Diameter - in 3 x 46.776 3 x 46.776
Construction / Media Type Segmented Pies / Polymeric Segmented Pies / Polymeric
Enthalpy
Wheel ARI
Rating Data
Nominal Airflow CFM 3900 @ .95Δ3900 @ .95Δ
EATR - -1.00 H2O 4.40% 4.40%
EATR - 0.00 H2O 1.10% 1.10%
EATR - +1.00 H2O 0.20% 0.20%
OACF - -1.00 H2O 0.99% 0.99%
OACF - 0.00 H2O 1.06% 1.06%
OACF - +1.00 H2O 1.11% 1.11%
Thermal Ratings @ 0” Pressure Diff. Sensible Latent Total Sensible Latent Total
Total
Effective-
ness
100% Airflow Heating 68% 60% 65% 68% 60% 65%
75% Airflow Heating 73% 67% 71% 73% 67% 71%
100% Airflow Cooling 68% 60% 63% 68% 60% 63%
75% Airflow Cooling 73% 67% 70% 73% 67% 70%
Net
Effective-
ness
100% Airflow Heating 68% 60% 65% 68% 60% 65%
75% Airflow Heating 73% 67% 71% 73% 67% 71%
100% Airflow Cooling 68% 60% 63% 68% 60% 63%
75% Airflow Cooling 73% 67% 70% 73% 67% 70%
Curb A/C Unit Curb Height - in 24 24
Weights Shipping Weight - lbs. 920 920
Net Weight - lbs. 805 805

Unitary Products Group 15
246681-YTG-B-0607
TABLE 10: SPECIFICATIONS AND ELECTRICAL DATA - 5500 THROUGH 6200 CFM ERV’S
Model Numbers VO062 - O/U Stand Alone VR062 - Rooftop Stationary
VS062 - S/S Stand Alone
Line Voltage - 60hz 208/230v-3ph 460v-3ph 575v-3ph 208/230v-3ph 460v-3ph 575v-3ph
Fresh Air
Blower
Motor - hp / type 5 / Belt 5 / Belt
Wheel Size (dia x width) - in 12 x 12 12 x 12
Motor Speed - rpm 1725 1725
Motor Speed(s) Adjustable Sheave Adjustable Sheave
Bearing Type Ball Ball
Full Load Amps 15 7.4 5.9 15 7 5.8
Service Factor 1.15 1.15
Exhaust Air
Blower
Motor - hp Stationary 5 / Belt 5 / Belt
Wheel Size (dia x width) - in 12 x 12 12 x 12
Motor Speed - rpm 1725 1725
Motor Speed(s) Adjustable Sheave Adjustable Sheave
Bearing Type Ball Ball
Full Load Amps-Stationary 14.8 7 5.1 14.8 7 5.1
Service Factor 1.15 1.15
Wheel
Electrical
Data
Motor - hp (1 phase) 0.5 0.5
Potential Volts 200-208 / 230 200-208 / 230
Motor Speed - rpm 1075 1075
Full Load Amps 1.2 2.7
Total
Electrical MCA - Stationary 36.8 17.5 13.6 34.5 17 12.7
OCPD - Stationary 50 25 20 40 25 15
Wheel
Data Wheel Depth x Diameter - in 3 x 52.026 3 x 52.026
Construction / Media Type Segmented Pies / Polymeric Segmented Pies / Polymeric
Enthalpy
Wheel ARI
Rating Data
Nominal Airflow CFM 5500 @ .95Δ5500 @ .95Δ
EATR - -1.00 H2O 4.00% 4.00%
EATR - 0.00 H2O 1.00% 1.00%
EATR - +1.00 H2O 0.20% 0.20%
OACF - -1.00 H2O 0.99% 0.99%
OACF - 0.00 H2O 1.06% 1.06%
OACF - +1.00 H2O 1.10% 1.10%
Thermal Ratings @ 0” Pressure Diff. Sensible Latent Total Sensible Latent Total
Total
Effective-
ness
100% Airflow Heating 68% 60% 65% 68% 60% 65%
75% Airflow Heating 73% 67% 71% 73% 67% 71%
100% Airflow Cooling 68% 60% 63% 68% 60% 63%
75% Airflow Cooling 73% 67% 70% 73% 67% 70%
Net
Effective-
ness
100% Airflow Heating 68% 60% 65% 68% 60% 65%
75% Airflow Heating 73% 67% 71% 73% 67% 71%
100% Airflow Cooling 68% 60% 63% 68% 60% 63%
75% Airflow Cooling 73% 67% 70% 73% 67% 70%
Curb A/C Unit Curb Height - in 24 24
Weights Shipping Weight - lbs. 1250 1250
Net Weight - lbs. 1075 1075

246681-YTG-B-0607
16 Unitary Products Group
TABLE 11: SPECIFICATIONS AND ELECTRICAL DATA - 6000 THROUGH 13000 CFM UERV’S
UERV Series VR074 VR122
Line Voltage - 60hz 208/230v-3ph 460v-3ph 575v-3ph 208/230v-3ph 460v-3ph 575v-3ph
Exhaust Air
Blower
Motor - hp (2) 5 / Belt (2) 7.5 / Belt
Wheel Size (dia x width) - in (2) 12 x 12 (2) 15 x 15
Motor Speed - rpm 1725 1725
Motor Speed(s) Adjustable Sheave Adjustable Sheave
Bearing Type Ball Ball
Full Load Amps 14.8 7 5 22.4 9.7 7.8
OCPD 20 9 7 30 15 10
Service Factor 1.15 1.15
Wheel
Electrical
Data
Motor - hp (3 phase) 0.25 0.25 0.33 0.25 0.25 0.33
Motor Speed - rpm 1725 1725
Full Load Amps 1.6 0.8 1.4 1.6 0.8 1.4
OCPD 322322
Total
Electrical MCA 34.9 16.6 12.7 52 22.6 19
OCPD 50 20 15 70 30 25
Wheel
Data Wheel Depth x Diameter - in 3 x 58 3 x 74
Construction / Media Type Segmented Pies / Polymeric Segmented Pies / Polymeric
Enthalpy
Wheel
Airflow Data
Nominal Airflow CFM 6600 @ .95Δ10800 @ .95Δ
EATR - -1.00 H2O 4.60% 3.40%
EATR - 0.00 H2O 1.90% 1.20%
EATR - +1.00 H2O 0.90% 0.40%
OACF - -1.00 H2O 0.99% 0.99%
OACF - 0.00 H2O 1.05% 1.04%
OACF - +1.00 H2O 1.09% 1.07%
Thermal Ratings @ 0” Pressure Diff. Sensible Latent Total Sensible Latent Total
Total
Effective-
ness
100% Airflow Heating 68% 60% 65% 68% 60% 65%
75% Airflow Heating 73% 67% 71% 73% 67% 71%
100% Airflow Cooling 68% 60% 63% 68% 60% 63%
75% Airflow Cooling 73% 67% 70% 73% 67% 70%
Net
Effective-
ness
100% Airflow Heating 68% 60% 65% 68% 60% 65%
75% Airflow Heating 73% 67% 71% 73% 67% 71%
100% Airflow Cooling 68% 60% 63% 68% 60% 63%
75% Airflow Cooling 73% 67% 70% 73% 67% 70%
Curb A/C Unit Curb Height - in 14 14
Weights Shipping Weight - lbs. 2800 3000
Net Weight - lbs. 2600 2800

Unitary Products Group 17
246681-YTG-B-0607
FIGURE 4 - UERV DIMENSIONAL DATA - 018 THROUGH 060
ERV Model York Model
A
B C D CFM
D*NA/NH/NP/NZ
018-060
24.75
(629)
24.63
(624)
34.83
(885)
8
(203) 300-550
D*NA/NH/NP/NZ 018-060
34.83
(885)
8
(203)
24.75
(629)
24.63
(624)
14" High Curbs Required on VR006-1RC0463
D*EB/EH/EM 018-060
300-550
D*EB/EH/EM, B*HA/HH/HP
018-060
Optional Eqpt
Support
Exhaust Blowe
r
Outdoor Air
Intake Blower
Enthalpy
Wheel
A
B
C
D
VR006B05H
VR006A05H
B*HA/HH/HP 018-060
FIGURE 5 - UERV DIMENSIONAL DATA - 036 THROUGH 072
14" High Curbs Required
ERV Model York Size A B C D CFM
48.75
(1238)
8
(203)
300-550036-072 24.75
(629)
37.96
(964)
8
(203)
DM/DF/DH 036-072
BQ 036-060
24.63
(624)
600-1100036-072 32.13
(816)
33.5
(851)
C
D
A
Exhaust Blowe
r
B
Enthalpy Wheel
Intake Air Blower
VR006A06H
VR011A06H
48.75
(1238)
8
(203) 600-1100036-072 32.13
(816)
33.5
(851)
VP011A06H
-1RC0434

246681-YTG-B-0607
18 Unitary Products Group
FIGURE 6 - UERV DIMENSIONAL DATA - 078 THROUGH 150
Model Number York Size
A
BC DCFM
20.32
(516)
11
(279)
32.13
(816)
33.5
(851)
44.75
(1137)
60.38
(1533)
600-1000
1100-1700
14" High Curbs Required on "VR011" & "VP011" - 1RC0471
DM/DF/DH/DJ 078-150
BP 078-150
078-102
078-102
090-150
24" High Curbs Required on "VR028" & "VP028" - 1RC0476
37.25
(946)
24" High Curbs Required on "VR020" & "VP020" - 1RC0476
37.5
(953)
090-150
C
D
A
B
Optional Eqpt
Support
Exhaust Blower
Outdoor Air
Intake Blower
Enthalpy Wheel
VR011B12H
VP011B12H
VR020B12H
VP020B12H
VR011A12H
VP011A12H
VR020A12H
VP020A12H
43.56
(1106)
42.63
(1083)
1500-2200090-150 42.63
(1083)
64.25
(1631)
18.32
(466)
090-150 2200-2800
43.56
(1106)
64 25
(1631)
18.32
(466)
VR028A12M
VP028A12M
VR028A12H
VP028A12H
20.32
(516)
11
(279)
32.13
(816)
33.5
(851)
44.75
(1137)
60.38
(1533)
600-1000
1100-1700
37.25
(946)
37.5
(953)
FIGURE 7 - UERV DIMENSIONAL DATA - 180 THROUGH 300
Model Number Unit Size A B C D CFM
1500-2200
180-300
180
180-300
180
180-300
180
180-300
180
180-300
24" High Curbs Required on "VR036" - 1RC0477 or 1RC0478
14" Roofcurbs Required on "VR028" - 1RC0436 - 437
52.68
(1338)
57.38
(1457)
DM 180-300
DH 180-240
DJ 180-300
DR 180-300
BP 180
BP 240
BQ 240
46.68
(1186)
57.38
(1457)
60.00
(1524)
30.50
(775) 2800-3600
24" High Curbs Required on "VR062" - 1RC0477 or 1RC0478
3400-4600
4800-5600
5500-6200
58.88
(1496)
57.38
(1457)
57.38
(1457)
22.50
(572) 2200-2800
52.13
(1327)
24" High Curbs Required on "VR046" - 1RC0477 or 1RC0478
180 42.63
(1083)
D
A
Exhaust
Blower
Outdoor Air Intake
Blower
Enthalpy
Wheel
B
C
VR028A15M
VR028A15H
VR028A25M
VR036A15H
VR036A25H
VR046A15H
VR046A25H
VR062A15M
VR062A25M
VR062A15H
VR062A25H
58.88
(1496)
43.56
(1106)
60.00
(1524)
60.00
(1524)
60.00
(1524)
30.50
(775)
30.50
(775)
30.50
(775)
NOTE: Refer to Unit Price Pages for exact unit, ERV and curb matchup.

Unitary Products Group 19
246681-YTG-B-0607
- Designed to meet Millennium unit specifications
- 14’ High Curbs Required
- Rooftop unit blower exceeds the capacity of the ERV Exhaust Blowers
- See blower performance charts for airflow at various external static pressures.
FIGURE 8 - MILLENNIUM UNIT VR074 AND VR122
74.75
24.59
61.23
82.13
20.92
Model Number CFM Description
VR074A40L 6000 - 8000 Constant volume
VR074A40V 6000 - 8000 Variable Air Vaolume
VR122A40L 8000 - 13000 Constant Volume
VR122A40V 8000 - 13000 Variable Air Volume

246681-YTG-B-0607
20 Unitary Products Group
Notes:
1. Drive losses included in the above table
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
Notes:
1. Drive losses included in the above table
2. Performance can vary depending on ambient conditions
3. Blower RPMs are for reference only
TABLE 12: BLOWER PERFORMANCE CHART - VR074
Exhaust
Blower RPM for VR074, (2) 5HP, Barometric Hood
External Static Pressure (in water)
00.511.52
CFM
6000 910 1060 1200 1300 1400
6500 955 1095 1225 1360 1430
7000 1000 1130 1260 1380 1475
7500 1040 1170 1290 1400 1500
8000 1080 1200 1315 1425 1530
RPM Range
Low 910-1320 Standard Unit
High 1325-1565 Optional Kit (01-KIT-RH58)
TABLE 13: BLOWER PERFORMANCE CHART - VR122
Exhaust
Blower RPM for VR122, 7.5HP, Barometric Hood
External Static Pressure (in water)
00.511.52
CFM
8000 775 900 1030 1125 1200
9000 825 945 1055 1150 1240
10000 875 985 1090 1190 1280
11000 925 1030 1125 1215 1310
12000 970 1070 1165 1250 1355
13000 1015 1110 1200 1280 1360
RPM Range
Low 775-1000 Standard Unit
Med 1000-1200 Optional Kit (0-KIT-RM74)
High 1175-1375 Optional Kit (01-KIT-RH74)
Table of contents
Other York Fan manuals

York
York YEFB Series User manual

York
York YH0A Manual

York
York Predator ZF150 User manual

York
York CC10 User manual

York
York ZB Series User manual

York
York PW Series Troubleshooting guide

York
York ZT078-102 User manual

York
York CI Series User manual

York
York YECFC Instruction manual

York
York MFSI User manual
Popular Fan manuals by other brands

Radfan
Radfan Classic Small instructions

MacroAir Technologies
MacroAir Technologies AVD 370/2 installation manual

Eberg
Eberg BRIS instruction manual

PAX
PAX Mistral iV12t Installation and operating instructions

Dantherm
Dantherm HCV 4 installation manual

Chore-Time
Chore-Time 50576 Installation and Operators Instruction Manual