User Information
B01
B101
E61-136-00
•
Indication of the switching state via LED
•
2 start behaviors possible:
- Monitored manual start
- Automatic start
•
Up to PL e, SILCL 3, category 4
•
It is not allowed to open the device, tamper with the devi-
ce or bypass the safety devices.
•
All relevant safety regulations and standards are to be
observed.
•
The overall concept of the control system in which the
device is incorporated must be validated by the user.
•
Failure to observe the safety regulations can result in
death, serious injury and serious damage.
Correct Use The SR2C is a universal emergency stop safety switching device
with two safe relay outputs that can quickly and safely stop the
moving parts of a machine or system in case of danger.
Applications for the SR2C include single or dual-channel emer-
gency stop circuits and guard monitoring on machines and sys-
tems.
Features
•
2 safe, redundant relay outputs
•
Connection of:
•
- Emergency stop buttons
- Safety switches
- Non-contact safety switches
- OSSD-Outputs
•
Single and dual-channel operation possible
•
Feedback loop for monitoring downstream contactors or
expansion modules
•
Cyclical monitoring of the output contacts
Function
The emergency stop safety switching device SR2C is
designed for safe isolation of safety circuits according to
DIN EN 60204-1 and can be used up to safety category 4,
PL e according to EN ISO 13849-1.
The internal logical system closes the safety contacts when
the start button is pressed.
If the emergency stop circuit is opened, the positively
driven safety contacts are opened and safely switch the
machine off. It is ensured that a single fault does not lead
to a loss of the safety function and that every fault is detec-
ted by cyclical self-monitoring no later than when the sys-
tem is switched off and switched on again.
Electrical
Connection
•
When the 24V version is used, a control transformer
according to EN 61558-2-6 or a power supply unit with
electrical isolation from the mains must be connected.
•
External fusing of the safety contacts (4A slow-blow or
6A quick-action or 10A gG) must be provided.
•
A maximum length of the control lines of 1000 meters
with a line cross section of 0.75 mm
2
must not be excee-
ded.
•
The line cross section must not exceed 2.5 mm
2
.
•
If the device does not function after commissioning, it
must be returned to the manufacturer unopened. Ope-
ning the device will void the warranty.
Installation
As per DIN EN 60204-1, the device is intended for installa-
tion in control cabinets with a minimum degree of protection
of IP54. It is mounted on a 35-mm DIN rail according to
DIN EN 60715 TH35.
Safety Precautions
•
Installation and commissioning of the device must be
performed only by authorized personnel.
•
Observe the country-specific regulations when installing
the device.
•
The electrical connection of the device is only allowed to
be made with the device isolated.
•
The wiring of the device must comply with the instructi-
ons in this user information, otherwise there is a risk that
the safety function will be lost.
Fig. 1 Block diagram SR2C
Fig. 2 Installation/removal
Fig. 3 Connections
A1: Power supply
A2. Power supply
S11: DC 24V control voltage
S10: Control line
S21: Start control line
S13: Control line
S14: Control line
S12: Control line
13-14: Safety contact 1
23-24: Safety contact 2
Safety Emergency Stop Relay SR2C
English translation
(not for plug-in terminals)

2
H. ZANDER GmbH & Co. KG • Am Gut Wolf 15 • D52070 Aachen • Tel +49 (0)241 9105010 • Fax +49 (0)241 91050138
info@zander-aachen.de • www.zander-aachen.de
User Information
B01
B101
E61-136-00
Note: The items listed under “Electrical connection” must be observed during commissioning.
Commissioning
Procedure
1. Wiring emergency stop circuit:
Wire the emergency stop circuit according to the required
Performance Level determined (see Fig. 1 to Fig. 5).
2. Wiring start circuit:
Wire the start circuit according to Fig. 6 or Fig. 7 to set the
starting behavior.
Warning:
If “Automatic start” is set, bear in mind that the safety con-
tacts will switch immediately after the power supply is
connected. If “Monitored manual start” is set, the start
button must be opened after wiring.
3. Wiring feedback loop:
If your application provides for external contactors or ex-
pansion modules, connect them to the device according to
Fig. 8 or Fig. 9.
4. Wiring power supply:
Connect the power supply to terminals A1 and A2 (Fig. 10).
Warning: Wiring only in de-energized state.
5. Starting the device:
Switch on the operating voltage.
Warning:
If the “Automatic start” starting behavior is set, the safety
contacts will close immediately.
If the “Monitored manual start” starting behavior is set, close
the start button to close the safety contacts.
LEDs K1 and K2 are lit.
6. Triggering safety function:
Open the emergency stop circuit by actuating the connec-
ted safety switch. The safety contacts open immediately.
7. Reactivation:
Close the emergency stop circuit. If “Automatic start” is
selected, the safety contacts will close immediately.
If the “Monitored manual start” starting behavior is set, close
the start button to close the safety contacts.
Fig. 6:
Monitored manual start.
It is monitored that the start
button was opened before the
emergency stop button closes.
(Prerequisite:
operating voltage must not be
interrupted.)
Fig. 7:
Automatic start.
Max perm. delay during
closing of the safety switches
on S12 and S13:
S12 before S13: 300 ms
S13 before S12: any
Warning:
Safety contacts switch
immediately when the
power supply is connected.
Depending on the application or the result of the risk assessment according to EN ISO 13849-1, the device must be wired as
shown in Fig. 1 to Fig. 11.
Applications
Fig. 3:
Single-channel emergency stop
circuit with earth fault monito-
ring.
(category 1, up to PL c)
Fig. 2:
Two-channel emergency stop
circuit with earth fault monitoring.
(category 3, up to PL d)
Fig. 1:
Two-channel emergency stop
circuit with short circuit and earth
fault monitoring.
(category 4, up to PL e)
Fig. 4:
Two-channel sliding guard
monitoring with short circuit and
earth fault monitoring.
(category 4, up to PL e)
Emergency Stop
Circuit
Starting Behavior
Safety Emergency Stop Relay SR2C
Notice:
In order to activate earth fault monitoring, S10 must be
connected to PE (protective earth) on the AC115/230V
devices. With AC/DC 24 V, connect PE only to the power
supply unit according to EN60204-1.
Fig. 5:
Two-channel emergency stop
with pnp-outputs/OSSD-outputs
with short circuit monitoring.
(category 4, up to PL e)
Fig. 8:
Feedback loop for monitored manual
start:
The feedback loop monitors contactors
or the expansion modules .
Feedback Loop
Fig. 9:
Feedback loop for automatic start:
The feedback loop monitors contac-
tors or the expansion modules .
Power supply
and
Safety contacts
Fig. 10:
Power supply A1 and A2.
(Power supply according to techn.
Data )
Fig. 11:
Connecting load to safety contacts.
(Figure shows example.
Voltage „+V“ according to techn.
Data)

3
H. ZANDER GmbH & Co. KG • Am Gut Wolf 15 • D52070 Aachen • Tel +49 (0)241 9105010 • Fax +49 (0)241 91050138
info@zander-aachen.de • www.zander-aachen.de
User Information
B01
B101
E61-136-00
Maintenance
The device must be checked once per month for proper
function and for signs of tampering and bypassing of the
safety function.
Techn. Data
Corresponds to the standards EN 60204-1; EN ISO 13849-1 ; EN 62061
Operating voltage AC 230V, AC 115V, AC/DC 24V
Rated supply frequency AC: 50-60Hz
Permissible deviation + / - 10%
Power consumption DC 24V AC 230V
approx. 1.2W approx. 3.5 VA
Control voltage at S11 DC 24V
Control current S11...S14 approx. 40mA
Safety contacts 2 NO contacts
Max. switching voltage AC 250V
Safety contact breaking capacity (13-14, 23-24) AC: 250V, 1500VA, 6A for ohmic load,
230V, 4A for AC-15
DC: 24V, 30W, 1.25A for ohmic load;
24V, 30W, 2A for DC-13
Minimum contact load 24V, 20mA
Min. Contact fuses 4A slow-blow or 6A quick-action or 10A gG
Max. line cross section 0.14 - 2.5mm
2
Max. length of control line 1000m with 0.75mm
2
Contact material AgNi
Contact service life mech. approx. 1 x 10
7
, electr. 1 x 10
5
operating cycles
Test voltage 2.5kV (control voltage/contacts)
Rated impulse withstand voltage, leakage path/air gap 4kV (DIN VDE 0110-1)
Rated insulation voltage 250V
Degree of protection IP20
Temperature range DC 24V: -15°C to +60°C
AC 230/115V: -15°C to +40°C
Degree of contamination 2 (DIN VDE 0110-1)
Overvoltage category 3 (DIN VDE 0110-1)
Weight approx. 230g
Mounting DIN rail according to EN 60715TH35
Note:
Additional data can be requested from the manufacturer for
applications that deviate from these conditions.
Safety
Characteristics
According to
EN ISO 13849-1
The device is certified according to EN ISO 13849-1 up to a
Performance Level of PL e.
Device cannot be switched on again after an emergency
stop:
•
Check whether the emergency stop circuit was closed
again.
•
Was the start button opened before closing of the emer-
gency stop circuit (with manual start)?
•
Is the feedback loop closed?
If the fault still exists, perform the steps listed under
“Commissioning Procedure”.
If these steps do not remedy the fault either, return the
device to the manufacturer for examination.
Opening the device is impermissible and will void the
warranty.
Device does not switch on:
•
Check the wiring by comparing it to the wiring diagrams.
•
Check the safety switch used for correct function and
adjustment.
•
Check whether the emergency stop circuit is closed.
•
Check whether the start button (with manual start) is
closed.
•
Check the operating voltage at A1 and A2.
•
Is the feedback loop closed?
What to Do in
Case of a Fault?
The device is otherwise maintenance free, provided that it
was installed properly.
Safety Emergency Stop Relay SR2C
Safety characteristics according to EN ISO 13849-1 for all variants of SR2C
Load (DC13; 24V) <= 0,1A <= 1A <= 2A
T10d [years] 20 20 20
Category 4 4 4
PL e e e
PFHd [1/h] 1,2E-08 1,2E-08 1,2E-08
nop [cycle / year] <= 400.000 <= 73.000 <= 17.000

4
H. ZANDER GmbH & Co. KG • Am Gut Wolf 15 • D52070 Aachen • Tel +49 (0)241 9105010 • Fax +49 (0)241 91050138
info@zander-aachen.de • www.zander-aachen.de
User Information
B01
B101
E61-136-00
Dimension
Drawing
114
99
22,5
Versions
Order no. 472150 SR2C, AC 230V (50-60Hz), fixed screw terminals
Order no. 472151 SR2C, AC 115V (50-60Hz), fixed screw terminals
Order no. 472152 SR2C, AC/DC 24V (AC: 50-60Hz), fixed screw terminals
Order no. 473150 SR2C, AC 230V (50-60Hz), plug-in terminals
Order no. 473151 SR2C, AC 115V (50-60Hz), plug-in terminals
Order no. 473152 SR2C, AC/DC 24V (AC: 50-60Hz), plug-in terminals
Order no. 472592 EKLS4, plug-in screw terminals kit
Order no. 472593 EKLZ4, plug-in spring-cage terminals kit
Safety Emergency Stop Relay SR2C
Other Zander Aachen Relay manuals

Zander Aachen
Zander Aachen ZX09 Series User manual

Zander Aachen
Zander Aachen SR7C User manual

Zander Aachen
Zander Aachen SR3D Operation manual

Zander Aachen
Zander Aachen SR4C User manual

Zander Aachen
Zander Aachen SR3C User manual

Zander Aachen
Zander Aachen SR3C Operation manual

Zander Aachen
Zander Aachen SR3E User manual

Zander Aachen
Zander Aachen SR7D User manual

Zander Aachen
Zander Aachen MINOS SD1E User manual

Zander Aachen
Zander Aachen MVisio HMI Pro User manual