© Zennio Avance y Tecnología S.L. Edition 1 Further information www.zennio.com Page. 1/ 2
DALIBOX Broadcast 4CH
KNX-DALI Broadcast Interface for up to 4 channels
ZDI-DLB4 Technical Documentation
FEATURES
Control of up to 20 DALI ballasts per channel in up to 4 channels.
Ballast replacement allowed with automatic detection.
Error detection and monitoring (except multiaddress DALI ballasts).
Burn-in, Stand-by and Auto-off functionality for each channel.
Not suitable for emergency lighting control.
Manual control through buttons and status LED indicators.
110/230V 50/60Hz external power supply required.
Total data saving on power failure.
KNX BCU integrated.
Size 67 x 90 x 80mm (4,5 DIN units).
DIN rail unit assembly (EN 50022), with snap fit clamp.
DALI Standard compatible.
CE directives compliant.
Programming/test button: short button press to set programming mode. If this button is held while plugging the device into the KNX bus, it goes into
safe mode.
Programming/Test LED: programming mode indicator (red). When the device goes into safe mode, it blinks (red) every half second. The test mode is
indicated by the green color. During start up (after reset or power failure) and if the device is not in safe mode, LEDs indicator blinks red once.
1. DALI channel output 2. External supply 3. DALI channel control button 4. DALI channel status LED
5. Programming/Test button 6. External supply LED 7. Programming/Test LED 8. KNX connector
Figure 1. DALIBOX Broadcast 4CH
GENERAL SYSTEM SPECIFICATIONS
Type of device Electric operation control device
KNX supply
Voltage (typical) 29VDC SELV
Voltage range 21…31VDC
Maximum
consumption
Voltage mA mW
29VDC (typical) 7 203
24VDC(1) 10 240
Bus connection Typical bus connector TP1; 0,80mm² section
Ext. power
supply Voltage and frequency 110/230VAC 50/60Hz
Maximum consumption 150mA
Ambient temperature from 0ºC to +45ºC
Storage temperature from -20ºC to +55ºC
Ambient humidity 5 to 95% RH (no condensation)
Storage humidity (relative) 5 to 95% RH (no condensation)
Complementary characteristics Class B
Safety class II
Operation type Continuous operation
Device action type Type 1
Electrical solicitations period Long
Type of protection IP20, clean environment
Assembly Independent control assembly device to be mounted inside of electrical panels with
DIN rail (EN 50022).
Minimal clearances Not required
KNX bus failure response Data saving according to parameterization.
Response when restarting KNX bus Data recovering change according to parameterization.
Operation indication Programming LED indicates programming mode (red) and test mode (green). Each
DALI channel LED indicates its status (flashing = error, see Fig. 2; fixed = active
output). Power supply LED indicates the presence of supply voltage.
Weight 124g
PCB CTI index 175V
Enclosure PC FR V0 halogen free
(1)
Maximum consumption in the worst