manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Zephyr
  6. •
  7. Ventilation Hood
  8. •
  9. Zephyr Napoli Island ZNA-E42S Installation guide

Zephyr Napoli Island ZNA-E42S Installation guide

Use, Care, and Installation Guide
www.zephyronline.com
Model number:
Serial Number:
MAR09.0102 © Zephyr Corporation
Napoli Island
ZNA-M90S
ZNA-E42S
www.zephyronline.com
1
SAFETY NOTICE................................................................. 2-3
LIST OF MATERIALS....................................................... 4
INSTALLATION
Ducting Calculation Sheet....................................... 5
Mounting Height & Clearance................................ 6
Ducting Options........................................................... 7
Hood Specifications................................................... 8
Mounting the Hood..................................................... 9 - 10
Ductless Recirculation.............................................. 11
CONTROLS..................................................................................... 12-14
MAINTENANCE
Hood and Filter Cleaning......................................... 15
Lights................................................................................ 16
TROUBLESHOOTING................................................................ 17
LIST OF PARTS AND ACCESSORIES.............................. 18
Table of Contents
Important Safety Notice
READ AND SAVE THESE INSTRUCTIONS
2
www.zephyronline.com
WARNING
TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT USE THIS FAN WITH ANY SOLID-STATE CONTROL DEVICE.
WARNING
TO REDUCE THE RISK OF FIRE ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
a. Use this unit only in the manner intended by the manufacturer, if you have questions, contact the manufacturer.
b. Before servicing or cleaning unit, switch power off at service panel and lock panel to prevent power from being switched on accidentally.
When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service
panel.
CAUTION
For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors. Take care when using cleaning
agents or detergents. Suitable for use in household cooking area.
WARNING
TO REDUCE THE RISK OF RANGE TOP GREASE FIRE:
a. Never leave surface units unattended at high settings. Boilovers cause smoking and greasy spillovers that may ignite. Heat oils slowly
on low or medium settings.
b. Always turn hood ON when cooking at high heat or when flaming food
c. Clean ventilating fans frequently. Grease should not be allowed to accumulate on fan or filter.
d. Use proper pan size. Always use cookware appropriate for the size of the surface element.
e. Keep fan, filters and grease laden surfaces clean.
f. Use high setting on hood only when necessary.
g. Don’t leave hood unattended when cooking.
h. Always use cookware and utensils appropriate for the type of and amount of food being prepared.
WARNING
TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP FIRE, OBSERVE THE FOLLOWING:
a. SMOTHER FLAMES with a close-fitting lid, cookie sheet, or metal tray, then turn off the burner. BE CAREFUL TO PREVENT BURNS.
If the flames do not go out immediately, EVACUATE AND CALL THE FIRE DEPARTMENT.
b. NEVER PICK UPA FLAMING PAN – You may be burned.
c. DO NOT USE WATER, including wet dishcloths or towels – a violent steam explosion will result.
d. Use an extinguisher ONLY if:
1. You know you have a Class ABC extinguisher, and you already know how to operate it.
2. The fire is small and contained in the area where it started.
3. The fire department is being called.
4. You can fight the fire with your back to an exit
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
a. Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards.
Including fire-rated construction.
b. Sufficient air is needed for power combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent
back-drafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National
Fire Protection Association (NFPA) and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) and
the local code authorities.
c. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
d. Ducted fans must always vent to the outdoors.
e. If this unit is to be installed over a tub or shower, it must be marked as appropriate for the application and be connected to a GFI
(Ground Fault Interrupter protected branch circuit).
g. NEVER place a switch where it can be reached from a tub or shower.
h. Make sure the power is off before installing, wiring or maintenancing.
Important Safety Notice
3
WARNING
TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK.
CAUTION
To reduce risk of fire and to properly exhaust air outside - Do not vent exhaust air into spaces within walls, ceilings,
attics, crawl spaces or garages.
OPERATION
Always leave safety grilles and filters in place. Without these components, operating blowers could catch onto hair, fingers
and loose clothing.
The manufacturer declines all responsibility in the event of failure to observe the instructions given here for installation,
maintenance and suitable use of the product. The manufacturer further declines all responsibility for injury due to
negligence and the warranty of the unit automatically expires due to improper maintenance.
*NOTE: Please check www.zephyronline.com for revisions before doing any custom work.
ELECTRICAL REQUIREMENTS
Important:
Observe all governing codes and ordinances.
It is the customer’s responsibility:
- To contact a qualified electrical installer.
- To assure that the electrical installation is adequate and in conformance with National Electrical Code,ANSI/NFPA 70
latest edition* or CSA standards C22.1-94, Canadian Electrical Code, Part 1 and C22.2 No.0-M91 - latest edition** and
all local codes and ordinances.
If codes permit and a separate ground wire is used, it is recommended that a qualified electrician determine that the
ground path is adequate.
Do not ground to a gas pipe.
Check with a qualified electrician if you are not sure the range hood is properly grounded.
Do not have a fuse in the neutral or ground circuit.
*National Fire Protection Association Batterymarch Park, Quincy, Massachusetts 02269
** CSA International 8501 East Pleasant Valley Road, Cleveland, Ohio 44131-5575
This appliance requires a 120V 60Hz electrical supply and connected to an individual properly grounded branch circuit
protected by a 15 or 20 ampere circuit breaker or time delay fuse. Wiring must be 2 wire with ground. Please also refer to
Electrical Diagram on product.
A cable locking connector (not supplied) might also be required by local codes. Check with local requirements, purchase
and install appropriate connector if necessary.
ZNA-M90S - 500 Watts, 4.1 Amps
ZNA-E42S - 500 Watts, 4.1 Amps
List of Materials
4
www.zephyronline.com
(3) Wire Nuts (1) Suction Cup
(4)ø12 OD / ø5 ID
Washers
(4) M4 x 1-1/2”
Wood Screws
(2) M4 x 8
Philips Head Screws
1 - Hardware package
1 - Top support frame
1 - Bottom support frame
1 - Top duct cover
1 - Bottom duct cover
1 - Hood body
3 - Metal mesh filters
4 - 50W GU-10 halogen lights
1 - 6” round damper,
pre-installed
MODELS: ZNA-M90S, ZNA-E42S
PARTS SUPPLIED
HARDWARE PACKAGE CONTENTS
PARTS NOT SUPPLIED
- Ducting, conduit and all installation tools
- Cable connector (if required by local codes)
- Duct cover extension accessory - Z1C-00NA
- Recirculating kit accessory - ZRC-0060
5
Duct pieces To t a l
Equivalent number
length x used =
3-1/ 4” x 10”
Rect.,
straight
1 Ft. x ( ) = Ft.
8” Round,
straight
1 Ft. x ( ) = Ft.
3-1/ 4” x 10”
Rect.900
elbow
15 Ft. x ( ) = Ft.
3-1/ 4” x 10”
Rect.450
elbow
9 Ft. x ( ) = Ft.
3-1/ 4” x 10”
Rect.900
flat elbow
24 Ft. x ( ) = Ft.
3-1/ 4” x 10”
Rect.
wall cap
with damper
30 Ft. x ( ) = Ft.
3-1/ 4” x 10”
Rect.to
6” round
transition
5 Ft. x ( ) = Ft.
3-1/ 4” x 10”
Rect.to
6” round
transition
900 elbow
20 Ft. x ( ) = Ft.
6” Round,
900 elbow
15 Ft. x ( ) = Ft.
6” Round,
450 elbow
9 Ft. x ( ) = Ft.
Ft.
7” Round,
straight
1 Ft. x ( ) = Ft.
Subtotal column 1 =
Duct pieces To t a l
Equivalent number
length x used =
6”- 8”Round
wall cap
with damper
30 Ft. x ( ) = Ft.
Round
wall cap
with damper
30 Ft. x ( ) = Ft.
7” or 8”
Round,
900elbow
15 Ft. x ( ) = Ft.
7” or 8”
7” or 8”
Round,
450
elbow
9 Ft. x ( ) = Ft.
Ft.
Ft.
Ft.
6”- 8” Round,
roof cap
30 Ft. x ( ) = Ft.
7” or 8”
Round,
roof cap
30 Ft. x ( ) = Ft.
Subtotal column 2 =
Subtotal column 1 =
Total ductwork =
Maximum Duct Length: For satisfactory air movement,
the total duct length of a 3 1/ 4” x 10” rectangular 6” or 7”
diameter round duct should not exceed 100 equivalent feet.
6” round to
3-1/ 4” x 10”
rect.
transition
1 Ft. x ( ) = Ft.
6” round to
3-1/ 4” x 10”
rect.
transition
900 elbow
16 Ft. x ( ) = Ft.
7” round to
3 1/ 4” x 10”
rect.
transition
8 Ft. x ( ) = Ft.
7” round to
3-1/ 4” x 10”
rect.
transition
900 elbow
23 Ft. x ( ) = Ft.
Installation – Ducting Calculation Sheet
Installation – Mounting Height & Clearance
6
www.zephyronline.com
DUCTING
A minimum of 6” round ducting must be used to
maintain maximum air flow efficiency.
Always use rigid type metal ducts only. Flexible
ducts could restrict air flow by up to 50%.
Use calculation worksheet to compute total duct
work.
ALWAYS, when possible, reduce the number of
transitions and turns. If a long duct run is required,
increase duct size from 6” to 7” or 8”.
If turns or transitions are required: Install as far
away from opening and as far apart, between 2,
as possible.
Minimum mount height between range top to hood
bottom should be no less than 28”.
Maximum mount height should be no higher than
36”.
It is important to install the hood at the proper
mounting height. Hoods mounted too low could
result in heat damage and fire hazard; while hoods
mounted too high will be hard to reach and will
loose its performance and efficiency.
If available, also refer to range manufacturer’s
height clearance requirements and recommended
hood mounting height above range. Always check
your local codes for any differences.
Mounting Height (Recirculating or Ducted)
Minimum Ceiling Height 8’1”. Hood mounted 28”
above cooking surface; 64” from floor.
Maximum Ceiling Height 10’ 1”. Hood mounted
36” above cooking surface; 72” from floor.
Duct cover extension kit available for ceiling
heights up to 12 feet. Turn to page 18 for part
number and ordering information.
DAMAGE-SHIPMENT / INSTALLATION:
• Please fully inspect unit for damage before
installation.
• If the unit is damaged in shipment, return the
unit to the store in which it was bought for
repair or replacement.
• If the unit is damaged by the customer, repair
or replacement is the responsibility of the
customer.
• If the unit is damaged by the installer (if other
than the customer), repair of replacement must
be made by arrangement between customer
and installer.
36"
Min 28"-Max 36"
Min 8’1"
Max 10’
Min.ducted 33”
Min.recirc. 33”
Max. 48”
7
WARNING FIRE HAZARD
NEVER exhaust air or terminate duct work into spaces between walls, crawl spaces, ceiling, attics or garages.
All exhaust must be ducted to the outside, unless using the recirculating option.
Use single wall rigid Metal ductwork only.
Fasten all connections with sheet metal screws and tape all joints w/ certified Silver Tape or Duct Tape.
Some Ducting Options
Installation – Ducting Options
side wall cap
w/ gravity damper
Soffit or crawl space
Roof Pitch w/
Flashing & Cap
ductless
recirculating
8
www.zephyronline.com
Installation – Hood Specifications
35 7
16
"
/42"[1065]
900
Min
32
1
2
"
826
Max 49"[1244]
11
13
16
"
300
25 9
16
"
650
1
9
16
"
40
9
13
16
"
249
89
16
"
218
6
1
8
"
155
83
16
"
208
6
13
16
"
173
10
3
16
"
258
11
8
"
28
front of hood side of hood
top of hood
(blower housing and ceiling bracket)
9
Add Blockings
Fasten Support Frame
Install Duct Cover
Fasten upper duct cover
Adjust height & fasten frame
1. Add and secure blocking (minimum 2x4
studs onto ceiling joists.
2. Fasten mounting telescopic support frame
directly onto ceiling joist or stud blockings.
3. Adjust height requirement and fasten
support frames together. NOTE: If
recirculating the hood, install air diverter
plate onto support frame.
4. Slide upper and lower telescopic duct
duct covers onto support frame. Fasten
upper duct cover piece to frame.
5. Install duct work and electrical
CAUTION: At least two installers are
required due to the weight and size of the
hood.
!
Installation – Mounting the Hood
10
www.zephyronline.com
Mount hood onto support frame
6. Lift lower duct cover and hood body onto bottom of support frame.
7. Secure hood body to bottom support with (4) screws. Access the screws
from inside the hood. This will require at least two people.
Installation – Mounting the Hood
WARNING: Electrical wiring must be done by a qualified person(s) in
accordance with all applicable codes and standards. This range hood must be
properly grounded. Turn off electrical power at service entrance before wiring.
!
11
Ductless recirculation is intended for applications where an exhaust duct work is not possible to be installed.
When converted, the hood functions as a recirculating hood rather than an exhaust hood. Fumes and exhaust
from cooking are drawn and filtered by a set of optional charcoal filters. The air is then purified and re-
circulated back within the home.
We recommend toALWAYS exhaust air outside of the home by employing existing or installing new duct
work, if possible. The hood is most effective and efficient as an exhaust hood. Only when the exhaust option
is not possible should you recourse to converting the hood into a recirculating hood.
When converted to be a recirculating hood, a set of charcoal filters are required on top of its standard Metal
Filter set. Order according to its Part number below. The standard Metal Filters are intended to capture
residue from cooking and the optional charcoal filters help to purify fumes exhausted from cooking for re-
circulation.
RECIRCULATING KIT (REQUIRED IF NO DUCTING IS USED)
Kit includes charcoal filters and air diverter plate.
Hood Model Part No. Filters in Pkg.
ZNA-M90S ZRC-0060 3
ZNA-E42S ZRC-0060 3
1. Purchase recirculating kit per the part number above.
2. Secure air diverter plate to top support frame. (FIG. F) Open
sides of air diverter plate should face left and right and align
with louver holes on the duct covers. Run 6” ducting from top
of blower housing and secure to air diverter plate. See manual
included with recirculating kit for more detailed instructions.
3. Remove metal mesh filters from hood. Clip charcoal filters onto
each charcoal filter bracket. (FIG. G) The brackets are pre-installed and
located behind the mesh filters.
4. Re-install metal mesh filters.
5. Enable charcoal filter change indicator on control panel. (Refer details
to pg. 13)
6. Charcoal filters must be replaced after every 120 hours of use (or
approximately every 3 to 4 months based on the average of 1 to 2
hrs. of daily cooking time). The microprocessor in the controls when
set, will elapse and count usage time and indicate when charcoal filter
replacement is required every 120 hrs.
Charcoal Filter Replacements
Hood Model Part No. Qty to Order
ZNA-M90S Z0F-C002 3
ZNA-E42S Z0F-C002 3
Charcoal Filter Dimensions:
9in x 6 3/8in
228mm x 162mm
Installation – Ductless Recirculation
D
E
Install charcoal filter (plastic side exposed)
into charcoal filter bracket. Insert tab
cut-out side D of charcoal filter into bracket
first. Lock charcoal filter into place by
pushing down on side E with locking tabs.
front of the hood
back of the hood
FIG. F
FIG. G
12
www.zephyronline.com
Lights On/Dim/Off
15 Min Delay Off
Display (speed level, delay off, filter clean/change)
Adjust 6 Speed Levels
Blower On/Off
1. Blower On/Off
By pressing the blower is switched on and off. When switched on, the blower starts up on speed level 3.
2. Speed Selection
The 6 speed levels are selected by pressing to decrease and to increase speed levels. The display indicates levels
selected.
3. Delay Off
This feature is used for programmed shut down of blower 15 minutes after the function is activated. Press once, a dot
flashes in the lower right side of display indicating the function is on. The blowers will shut down after 15
minutes.
4. Lights On/Dim/Off
Switch lights on by pressing once, press a second time to dim and again to shut off lights.
5. Display Window
The display window indicates speed levels and features such as metal filter clean reminder, delay off and charcoal filter change
reminder.
Metal Filter Clean Reminder (metal mesh filter)
After every 30 hours of use the display will start flashing an reminding you to clean the metal filters from residue and
possible clogs.
F
The standard metal mesh filters are required to be cleaned frequently and as recommended in order to maintain blower
efficiency. If improperly maintained, residue from cooking will sift through filters and cause damage to hood blowers and
other sensitive components; and possible clog duct work and create a fire hazard.
Features & Controls – Touch Controls
Features & Controls – Charcoal Filter Change Reminder
13
Charcoal Filter Change Reminder (charcoal filter, if installed)
When your hood is installed as a recirculating unit, it is fitted with a set of charcoal filters to purify exhaust
and fumes from cooking, then re-circulates the air within the home. These charcoal filters are required to
be replaced after every 120 hours of use. The charcoal filters should never be cleaned or placed in a dish
washer.
The filter change reminder function in the microprocessor needs to be switched on. When switched on, the
microprocessor will elapse and count usage time and indicate by a flashing when charcoal filter
replacements are needed.
C
Setting the Filter Change Reminder
When off, hold for approximately 5 seconds.
The display will change from (exhaust mode) to
(recirculating mode) this indicates that the
elapse timer function is switched on and charcoal
filters are used.
Filter Replace Indicator
When the display starts flashing, the charcoal
filters need to be replaced.
Re-setting Function
Once filters are replaced, with hood off, press and
hold the display will appear; hold for apprimately
5 seconds until on displays disappears .
The filter change reminder is now re-set and a new
120 hour elapse cycle is initiated.
C
C
C
C
hold 5 sec. display from < - > to < C >
Set Mode
Set Mode
display < C > flashes
Change FIlters
C
hold 5 sec. display from < C > to < >
To Reset
C
Features & Controls – Metal Mesh Filter Clean Reminder
14
www.zephyronline.com
Metal Filter Clean Reminder (metal mesh filter)
Whether your hood is installed as an exhaust or purifying unit, a set if metal mesh filters are fitted by the
factory, These metal mesh filters are intended to filter out residue from cooking. They need not be
replaced on a regular basis but are required to be kept clean. The filter clean reminder function in the
microprocessor will automatically indicate by a flashing when the metal mesh filters need to be
cleaned after every 30 hours of use. Filters can be cleaned by hand with non-abrasive soap or in a
dishwasher. Heavily soiled filters should also be soaked in grease cutting detergent prior to cleaning.
Metal Filter Clean Indicator
When flashes on display, the metal filters
installed are required to be cleaned. This will occur
after every 30 hours of use.
Re-setting Function
Reset the filter clean reminder timer when filters are
cleaned and re-installed (with hood off). Press and
hold for approximately 5 seconds, the display will
appear; hold for approximately 5 seconds until on
display disappears . The filter clean reminder
function is now reset and a new 30 hours elapse
cycle is initiated.
F
Clean Filters
display < F > flashes
F
hold 5 sec. display from < F > to < >
To Reset
F
F
F
15
SURFACE MAINTENANCE:
Clean periodically with hot soapy water and clean cotton cloth. Do not use corrosive or abrasive detergent ,
or steel wool/scouring pads which will scratch and damage surface.
For heavier soil use liquid degreaser.
After cleaning it is recommended that you use non-abrasive stainless steel polish/cleaners, to polish and buff
out the stainless luster and grain. Always scrub lightly, with clean cotton cloth, and with the grain.
Do not use any product containing chlorine bleach. Do not use “orange” cleaners.
Metal Filters
The metal filters installed by the factory are intended to filter out residue and grease from cooking. They need
not be replaced on a regular basis but are required to be kept clean.
Filters should be cleaned after every 30 hours of use or once a month.
Remove and clean by hand or in dishwasher on low heat. Spray degreasing detergent and leave to soak if
heavily soiled.
Dry filters and re-install before using hood.
Replacing Metal Filters
Should filters wear out due to age and
prolonged use, replace with following part
number:
Hood Model: Part No. Qty. to Order.
ZNA-M90S 50200004 3
ZNA-E42S 50200004 3
Replace any damaged filter that has punctured
or broken mesh or damaged frame.
Maintenance – Hood and Filter Cleaning
16
www.zephyronline.com
REPLACING LIGHT BULBS
CAUTION: Light bulb becomes extremely hot when turned on.
DO NOT touch bulb until switched off and cooled. Touching hot bulbs could cause serious burns.
Make sure all power is turned off and bulbs are not hot.
Remove by turning bulb counter clockwise. Note: Bulb does not unscrew; it turns 60 degrees,
stops and falls out.
If bulbs are difficult to turn due to prolonged use, firmly attach a glass suction cup approximately the diameter of
the bulb or use a rubber/latex glove and turn counter clockwise.
Replacement bulbs are available at specialty lighting stores. Purchase type GU-10 50W halogen. Note: GU-10
halogen light bulbs apply to ZNA hoods ending in serial number xxxxxxxBxx only.
For Zephyr part numbers please turn to page 18 of the manual.
Maintenance – Lights
Troubleshooting
17
TROUBLESHOOTING PROCEDURES FOR NAPOLI ISLAND
Issue Cause What to do
After installation,
the unit doesn’t
work.
1. The power source is not turned ON. 1. Make sure the circuit breaker and the unit’s
power is ON.
2. The power line and the cable locking connector
is not connecting properly. 2. Check the power connection with the unit is
connected properly.
3. The switch board and control board wirings are
disconnected. 3. Make sure the wirings between the switch
board and control board are connected
properly.
4. The switch board or control board is defective. 4. Change the switch board or control board.
Light works,
but motor is not
turning.
1. The motor is defective, possibly seized. 1. Change the motor.
2. The thermally protected system detects if the
motor is too hot to operate and shuts the motor
down.
2. The motor will function properly after the
thermally protected system cool down.
3. Damaged capacitor. 3. Change the capacitor.
4. The switch board or control board is defective. 4. Change defective part.
The unit is
vibrating. 1. The motor is not secure in place. 1. Tighten the motor in place.
2. Damaged blower wheel. 2. Replace the blower.
3. The hood is not secured in place. 3. Check the installation of the hood.
4. The switch board or control board is defective. 4. Change defective part.
The motor is
working, but the
lights are not.
1. Defective halogen bulb. 1. Change the halogen bulb.
2. The light bulb is loose. 2. Tighten the light bulb.
The hood is
not venting out
properly.
1. The hood might be hanging to high from the
cook top. 1. Adjust the distance between the cook top and
the bottom of the hood within 28” and 36”
range.
2. The wind from the opened windows or opened
doors in the surrounding area are affecting the
ventilation of the hood.
2. Close all the windows and doors to eliminate
the outside wind flow.
3. Blockage in the duct opening or ductwork. 3. Remove all the blocking from the duct work or
duct opening.
4. The direction of duct opening is against the wind. 4. Adjust the duct opening direction.
5. Using the wrong size of ducting. 5. Change the ducting to at least 6” or higher
for the internal blower and 8” or higher for the
external blower.
Metal Filter is
vibrating. 1. Metal filter is loose. 1. Change the metal filter.
18
www.zephyronline.com
DESCRIPTION PART#
Replacement Parts
Light Bulb GU10 50W (each) Z0B-0020
Metal Filter (each) 50200004
Optional Accessories
Recirculating Kit ZRC-0060
Replacement Charcoal Filter (each) Z0F-C002
Duct Cover Extension Z1C-00NA
To order parts, visit us online at http://store.zephyronline.com or call us at 1.888.880.8368
List of Parts and Accessories

This manual suits for next models

1

Other Zephyr Ventilation Hood manuals

Zephyr ZNA-M90BS Installation guide

Zephyr

Zephyr ZNA-M90BS Installation guide

Zephyr Venezia ZVE-E30AS User manual

Zephyr

Zephyr Venezia ZVE-E30AS User manual

Zephyr Twister AK8000BS Installation guide

Zephyr

Zephyr Twister AK8000BS Installation guide

Zephyr Vortex AK9028BS Installation guide

Zephyr

Zephyr Vortex AK9028BS Installation guide

Zephyr ZPY-E30 (B Installation guide

Zephyr

Zephyr ZPY-E30 (B Installation guide

Zephyr AK6500 Installation guide

Zephyr

Zephyr AK6500 Installation guide

Zephyr AK0710 Installation guide

Zephyr

Zephyr AK0710 Installation guide

Zephyr ALU-E43 Quick start guide

Zephyr

Zephyr ALU-E43 Quick start guide

Zephyr Monsoon I AK9228AS Installation guide

Zephyr

Zephyr Monsoon I AK9228AS Installation guide

Zephyr Optica Island EOT-E42ASX Installation guide

Zephyr

Zephyr Optica Island EOT-E42ASX Installation guide

Zephyr ZMD-M90AS Installation guide

Zephyr

Zephyr ZMD-M90AS Installation guide

Zephyr elica Optica EOP-E42ASX Installation guide

Zephyr

Zephyr elica Optica EOP-E42ASX Installation guide

Zephyr Okeanito COK-E36BSX Installation guide

Zephyr

Zephyr Okeanito COK-E36BSX Installation guide

Zephyr Trapeze CTP-E 48SX User manual

Zephyr

Zephyr Trapeze CTP-E 48SX User manual

Zephyr Tornado Mini AK8400AS Installation guide

Zephyr

Zephyr Tornado Mini AK8400AS Installation guide

Zephyr Roma Pro Wall ZRP-E36AS Installation guide

Zephyr

Zephyr Roma Pro Wall ZRP-E36AS Installation guide

Zephyr Typhoon AK2100CS Installation guide

Zephyr

Zephyr Typhoon AK2100CS Installation guide

Zephyr CACHE CCA-E30ASX Use Installation guide

Zephyr

Zephyr CACHE CCA-E30ASX Use Installation guide

Zephyr Monsoon I Installation guide

Zephyr

Zephyr Monsoon I Installation guide

Zephyr AK6500 series Use Installation guide

Zephyr

Zephyr AK6500 series Use Installation guide

Zephyr CPA-E42ASX Installation guide

Zephyr

Zephyr CPA-E42ASX Installation guide

Zephyr ZMD-M90BS Installation guide

Zephyr

Zephyr ZMD-M90BS Installation guide

Zephyr ARC AHZ-M90AWX User manual

Zephyr

Zephyr ARC AHZ-M90AWX User manual

Zephyr Typhoon AK2100 Installation guide

Zephyr

Zephyr Typhoon AK2100 Installation guide

Popular Ventilation Hood manuals by other brands

Grundig GDKP5485BBSCH user manual

Grundig

Grundig GDKP5485BBSCH user manual

Faber WEST ANGOLO BIANCO SC instruction manual

Faber

Faber WEST ANGOLO BIANCO SC instruction manual

La Germania KV90LAG1NB installation manual

La Germania

La Germania KV90LAG1NB installation manual

AEG DPE4641M user manual

AEG

AEG DPE4641M user manual

Miele DA 289-3 Operating and installation instructions

Miele

Miele DA 289-3 Operating and installation instructions

Broan E60000 SERIES installation instructions

Broan

Broan E60000 SERIES installation instructions

ELICA ETR836WT Use, care and installation guide

ELICA

ELICA ETR836WT Use, care and installation guide

Lapetek TREKK X2 50 Installation and user manual

Lapetek

Lapetek TREKK X2 50 Installation and user manual

Electrolux EFC 9543 instruction manual

Electrolux

Electrolux EFC 9543 instruction manual

Venmar CIS700 SERIES installation instructions

Venmar

Venmar CIS700 SERIES installation instructions

KitchenAid KHTU100K Dimension Guide

KitchenAid

KitchenAid KHTU100K Dimension Guide

Rinnai RH-993CT Use and care guide

Rinnai

Rinnai RH-993CT Use and care guide

AllFuel HST AF-HST installation instructions

AllFuel HST

AllFuel HST AF-HST installation instructions

Cooke & Lewis CL60CGRF manual

Cooke & Lewis

Cooke & Lewis CL60CGRF manual

BKI Rotisserie Ventless Hood VGH-Series Installation and operation manual

BKI

BKI Rotisserie Ventless Hood VGH-Series Installation and operation manual

Smeg KR37XE user manual

Smeg

Smeg KR37XE user manual

Fisher & Paykel HI90BLX1 installation instructions

Fisher & Paykel

Fisher & Paykel HI90BLX1 installation instructions

JUNO JDK7090G Instruction booklet

JUNO

JUNO JDK7090G Instruction booklet

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.