
18 / 80
Identificazione: MD-AL-GI-00
Rev. 4.0 del 31.01.18 - Applicazione: GID
Manual of 07/06/2019 Rev. 1.1“User Manual for 50K-70K TL”
B.2 Feeding reactive power into the grid
The inverter is capable of generating reactive power and can then feed it into the grid by setting the Power
Factor. The feed-in management can be controlled directly by the network operator via a dedicated RS485
serial interface.
B.3 Limiting the active power fed into the grid
If properly set, the inverter can limit the amount of active power fed into the grid at the desired value
(expressed as a percentage). To achieve this limitation, it is necessary to use an external device (Anti-
Reverse Power Controller) not supplied with the inverter.
B.4 Automatic power reduction when grid frequency exceeds the limit
When the grid frequency exceeds the limit set, the inverter reduces the power in order to ensure the
stability of the grid.
B.5 Power reduction due to environmental conditions, input and output voltage
The power reduction value and temperature of the inverter at which it occurs depends on the ambient
temperature and on many operating parameters, such as: input voltage, grid voltage and power available
from the photovoltaic field. The inverter can therefore reduce the power at certain times of the day and
depending on the value of these parameters.
C. Data transmission
The inverter (or a group of inverters) can be monitored remotely via an advanced communication system
based on a RS485 interface or via Wi-Fi.
D. Software update
A microSD card is used to update the firmware.
E. Monitoring input strings
The inverter monitors and displays the input voltage and current of each string. It also controls the status of
the strings and in the event of a fault generates an alarm in the error list (visible from the display).
F. Overvoltage arrester monitoring (only for S4 and S5 versions)
The inverter monitors the status of the overvoltage arresters (both AC and DC), and in the event of a fault
generates an alarm in the error list (visible from the display).
2.3. Module protection
A. Anti-islanding
The inverter is equipped with a protection system that automatically shuts down the system during power
outages. This so-called “anti-islanding” system protects electrical workers when they are trying to repair lines on
the grid according to the applicable national laws and regulations.
B. RCMU
The inverters are equipped with a redundancy on the reading of the ground leakage current, on both the direct
and alternating current sides. The ground leakage current is measured simultaneously and independently by two
different processors: it is sufficient for one of the two to detect a fault in order to trigger the protection, resulting
in separation from the grid and shutdown of the operation.