Connection procedure
ABB recommends that you use a PROFIBUS-
approved D-SUB 9 connector. These
connectors have a built-in termination
network and inductors for station
capacitance compensation.
Connect the cable to the D-SUB connector as
shown in the figure.
Start-up
To control the drive with the adapter module, set at least the basic parameters listed in the table
below. For full parameter descriptions, refer to the adapter module’s user manual or to the drive’s
firmware manual.
Basic parameter settings
To take the settings into use, validate and refresh the parameters with parameter 51.27 FBA par
refresh.
Further information
Index Name Value
20.01 Ext1 commands Fieldbus A
22.11 Speed ref1 source FBA A ref 1
28.11 Frequency ref1 source FBA A ref 1
50.01 FBA A enable Enable (or select the option slot in which the module is installed).
50.02 FBA A comm loss func Fault
51.02 Node address Set the node address of the module according to the network
configuration.
51.05 Profile The ABB Drives communication profile is the default value.
52.01 FBA A data in1 SW 16bit
52.02 FBA A data in2 Act 16bit
53.01 FBA A data out1 CW 16bit
53.02 FBA A data out2 Ref1 16bit
See the latest version of FPBA-01 PROFIBUS DP adapter module
user's manual (3AFE68573271 [English]) in ABB library
(www.abb.com/drives/documents).
For more information on ABB fieldbus options and protocols,
see the fieldbus communications web page
(new.abb.com/drives/connectivity/fieldbus-connectivity).