Universal Inputs
When input is configured as Digital:
•LED Off: open circuit or logic 'off'
•LED On: logic 'on'
When input is configured as Resistor/thermistor:
•LED Off: valid resistance connected (Note: 0 Ωis counted as valid)
•LED Slow blink: resistor/thermistor not connected
When input is configured as Analog:
•LED intensity is modulated by the analog signal
When the LED is blinking:
•Fast blink indicates error condition
•Two short flashes followed by a value*indicates the input is in an override state (overridden by CXproHD).
*Note: The LED intensity illustrates the value measured at the input terminals. The flash indicates that this
value has been overridden.
UniPuts™ + Relay
When a Uniputchannel is configuredasan input, the LED signals are identical to Universal Inputs above. When configured
as an output the following apply:
When output is configured as Digital:
•LED Off: open circuit or logic 'off'
•LED On: logic 'on'
When output is configured as Analog:
•LED intensity is modulated by the analog signal
When the LED is blinking:
•Fast blink indicates error condition
•Two short flashes followed by a value indicates the output is in an override state (overridden by CXproHD or
HOA).
Strategy Loaded but no
network connectivity
StrategyLoaded and device
communicating onnetwork
During firmware upgrade the Yellow LED will remain on while the strategy/comms section reboots, and then the LEDs will
rotate Red-Green-Yellow while the IO section reboots.
Note: During typical operation, the Red LED
should be on, the Green LED should be
blinking and the Yellow LED should be off.
Output Override (CBXi-8R8-H only)
Bottom position: Off - outputs forced off.
Centre position: Auto - outputs are controlled by strategy.
Top position: Manual - for digital outputs, the output is forced on. For analog outputs the knob setting controls the output
value.
Note: Manual position is supervised, i.e. the strategy is aware of the manual value.
Push buttons
Reset IP/Password : while the controller is
running
, press SW 1until the LED lights up, then release SW1.
Full factory reset : while the controller is
booting
hold SW1 until the LED lights up, then release SW1.
Restart the controller : while the controller is
running
, press SW2until the LEDlights up., then release SW2.
Inter-module connection sockets
To join the FLX bus, place the devices side-by-side and place the FLX bus connector into the two adjacent sockets at once.
The end device on a FLX bus (either a FLX device or the CBXi itself) must have a terminator inserted into its interconnector socket. One
terminator is shipped with each CBXi-8R8(-H) device.