M10x Parameter description | Motor control and protection unit 9
New features available in enhanced products
In comparison with previous firmware and hardware revisions:
General features
1One single type of integrated CT ranging from 0.24~63A replaces all 6 types of CTs in previous products.
2Products with options for 110VAC or 240VAC power supply and DI types are available in addition to 24VDC option.
3Additional SOE function in M102 provides event recorder data up to 256 events with time stamp.
4Products in the same categories are made with the same features and functionalities and are only different in power supply and
communication interface from each type. For example, M101's range of products has identical functionalities regardless of different types
of power supply and interfaces, such as M101-M 24VDC, M101-P 240VAC, etc.
Physical dimension
1Main unit dimension remains the same as previous revision. MDx panel is slightly larger in width and length (both 3mm extra) while cutout
dimension remains the same.
Control features
1Contactor feeder and contactor feeder/RCU are added into starter types.
2Two separate start types are available for two-speed starters. NR_2N is for two-speed motor with separate windings while NR_2N
Dahlander is for Dahlander connection motor.
3Control logic in NR_softstarter and REV_softstarter are modified slightly.
4Control authority feature in M10x-M has been revised to be identical to M10x-P.
Digital inputs and outputs
1All DIs in M10x are configurable and also selectable with NO or NC.
2E-stop, Limit 1, Limit 2, External trip input control definition has been revised.
3More features are added to DOs.
Protection
1Long start protection is available to provide stall protection during motor startup.
2Options are provided to enable or disable TOL protection during motor startup.
3PTC short circuit protection and PTC open circuit protection are available.
Communication
1Additional communication speeds are available for MODBUS: 38400 bps and 57600 bps.
Measuring and monitoring
1Additional running data are monitored, such as current phase unbalance, thermistor resistor, time to TOL trip, time to TOL reset, startup
time, DI status.
2Phase-to-phase instead of phase-to-neutral voltage is directly measured.
Maintenance
1More maintenance features are implemented, including providing number of trips, SOE with time stamp, etc.
Operator panel MDx
1MDx is provided as IP54.
2Color and function of LEDs are selectable.
3Messages on MD21 are selectable.
4Two languages are supported, ie, English and Chinese.
5Parameter setting via MD21 is available.
6Parameter setting port on MDx is mini USB connector in lieu of USB connector.