manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ABB
  6. •
  7. Controllers
  8. •
  9. ABB Relion 620 Series User manual

ABB Relion 620 Series User manual

—
Quick Start Guide
Relion® 620 series
Display Default view can be selected from e.g. single line diagram (SLD), measurements, events
Self-supervision and
protection indicator LEDs
Ready-LED steady: OK, Ready-LED flashing: Internal Relay Fault (IRF), Start-LED steady: protection started,
Start-LED flashing: protection function blocked, Trip-LED: protection operated
Programmable LEDs Can be programmed for alarming and indication as latched the signal. Flashing/steady features.
Control Circuit Breaker or
disconnectors
Press open/close and confirm by pressing enter. If there is more than one controllable object select the object
first with navigation buttons. Note: control has to be in Local mode.
Escape / Cancel Used for canceling actions and leaving setting mode without saving the values. Returns back to menu.
Navigation Left = go back, Right = go further, Up = scroll up, Down = scroll down. Up/down can also be used when selecting
controllable objects like breakers and switches in single line diagram.
Enter / Select Entering to parameter setting mode and confirming new values
Authorization If authorization is used you can log in or log out using this button
Clear Clearing events and indications, see next page for further details
 Menu Switch views in between the main menu, single line diagram and measurements
 Local / Remote Changes the control between Local/Remote
 Help View help messages
 Function buttons Can be configured as control buttons









 

2QUICK START GUIDE RELION® 620 SERIES
—
Using the local HMI
Accessing main menu and local authorization
Press to navigate between main menu, measurements
and multiple single-line diagram pages.
If the local authorization has been enabled you must login
before entering the menu. To login press and select user
level with or . Confirm the selection with . Enter the
password one digit at the time using or and moving to
next digit with or . Confirm the password with or
cancel using . To logout press again.
Changing parameters
Press and select which setting value you want to change
and press to change it with or keys. If there is “#”
mark at the same line with parameter value, you have to first
select which setting group parameter you want to change.
If there is no “#” mark you can change the value directly by
pressing and then select value with or and or
keys. Confirm the selection with . After making changes to
parameters they have to be stored to get them into use.
Storing settings
Store the settings by going back to main menu by pressing
or using the key. When IED asks confirmation to commit
changes, answer “Yes“. Some changes require the IED to reboot
before the changes can be taken into use. Reboot the IED by
going to 
or switching the auxiliary power off and back on.
Changing the overcurrent start value
 select setting group, default 1
and press 
Clearing events and indications
There are two ways to do this:
• Go to clear menu by pressing or selecting Clear from
the main menu. Then select what you want to clear and
press , press (Clear text will appear and Cancel will
disappear) and then press .
• Press hold for three seconds to clear indications and
immediately after that three seconds again to clear LEDs.
Checking IED order code, serial number, HW revision


Display header area
The icon area at the upper right corner of the dislay shows
the current action or user level. These are described below:
S= Parameters are being stored, != Warning and/or indication
V= Viewer, = Operator, E= Engineer, A= Administrator
Using the function buttons
The function buttons can be configured as control buttons.
Configurations can be made with PCM600. Check the function
button action from the label, before pushing the button.
The action will take effect immediately when the button
is pressed.
If function buttons are set to follow L/R restriction, the control
must be set to Local for button to execute.
Monitored data

From here you can find a lot of information about the present
status of IED and monitored data. For example physical input
and output states, GOOSE counters, the states and I/O data
of the function blocks and the counter values of MMS vertical
communication. You can also find recorded data including
the currents and voltages of the latest faults.
Checking IED status (IRF)



Changing the display contrast
Hold and press or to change the display contrast.
If you want to store the contrast, go first in the menu and then
go back to the default view, so that A (Administrator) appears
to the right upper corner. If authentication is enabled you need
to login and then change the contrast.
Changing the language
 or you can push and anywhere in
the menu and language will be changed. English is always the
default language and there can be maximum of two additional
languages in the IED.
Changing function block naming from IEC 61850 names
to IEC 60617 or ANSI

Complete customer documentation is available in the product
pages that can be accessed through abb.com/relion.
QUICK START GUIDE RELION® 620 SERIES 3
—
Most common function blocks
Function   ANSI
Protection
Three-phase non-directional overcurrent protection, low stage PHLPTOC 3I> 51P-1
Three-phase non-directional overcurrent protection, high stage PHHPTOC 3I>> 51P-2
Three-phase non-directional overcurrent protection, instantaneous stage PHIPTOC 3I>>> 50 P/51P
Three-phase directional overcurrent protection, low stage DPHLPDOC 3I> → 67-1
Three-phase directional overcurrent protection, high stage DPHHPDOC 3I>> → 67-2
Non-directional earth fault protection, low stage EFLPTOC Io> 51N-1
Non-directional earth fault protection, high stage EFHPTOC Io>> 51N-2
Non-directional earth fault protection, instantaneous stage EFIPTOC Io>>> 50N/51N
Directional earth fault protection, low stage DEFLPDEF Io> → 67N-1
Directional earth fault porotection, hig stage DEFHPDEF Io>> → 67N-2
Admittance based earth-fault protection EFPADM Yo> → 21YN
Wattmetric based earth-fault protection WPWDE Po> → 32N
Transient / intermittent earth-fault protection INTRPTEF Io> → IEF 67NIEFH
Harmonics based earth-fault protection HAEFPTOC Io>HA 51NHA
Negative-sequence overcurrent protection NSPTOC I2> 46
Phase discontinuity protection PDNSPTOC I2/I1> 46PD
Residual overvoltage protection ROVPTOV Uo> 59G
Three-phase undervoltage protection PHPTUV 3U< 27
Three-phase overvoltage protection PHPTOV 3U> 59
Positive-sequence undervoltage protection PSPTUV U1< 47U+
Negative-sequence overvoltage protection NSPTOV U2> 47O-
Frequence protection FRPFRQ f>/f<,df/dt 81
Three-phase thermal protection for feeders, cables and distribution transformers T1PTTR 3lth>F 49F
Loss of phase (undercurrent) PHPTUC 3l< 37F
Circuit breaker failure protection CCBRBRF 3I>/Io>B F 51BF/51NBF
Three-phase inrush detector INRPHAR 3l2f> 68
Master trip TRPPTRC Master Trip 94/86
Arc protection ARCSARC ARC 50L/50NL
High impedance fault detection PHIZ PHIZ PHIZ
Load shedding and restoration LSHDPFRQ UFLS/R 81LSH
Multipurpose analog protection MAPGAPC MAP MAP
Loss of load supervision LOFLPTUC 3l< 37M
Motor load jam protection JAMPTOC Ist> 51LR
Motor start-up supervision STTPMSU Is2t n< 49,66,48,51LR
Phase reversal protection PREVPTOC I2>> 46R
Thermal overload protection for motors MPTTR 3lth>M 49M
Motor differential protection MPDIF 3dl>M 87M
Voltage per hertz protection OEPVPH U/f> 24
Three-phase thermal overload protection for power transformers, two time constants T2PTTR 3l t h>T 49T
Stabilized and instantaneous differential protection for 2-winding transformers TR2PTDF 3 dl>T 87T
Numerical stabilized low impedance resticted earth-fault protection LREFPNDF dIoHi> 87NL
High impedance based restricted earth-fault protection HREFPDIF dIoHi> 87NH
The most common function blocks are listed below, please refer to the 620 series Technical Manual for the full list.
The available function blocks varies depending on the selected IED and configuration used.
1MRS757922 REV B EN 02-2019
—
We reserve the right to make technical changes or modify the contents
of this document without prior notice. With regard to purchase orders,
the agreed particulars shall prevail. ABB does not accept any responsibility
whatsoever for potential errors or possible lack of information in this
document.
We reserve all rights in this document and in the subject matter and
illustrations contained therein. Any reproduction, disclosure to third
parties or utilization of its
contents – in whole or in parts – is forbidden
without prior written consent of ABB.
Copyright© 2019 ABB. All rights reserved.
—
For more information, please contact
ABB Distribution Solutions
P.O. Box 699
FI-65101 Vaasa, Finland
Phone: + 358 10 22 11
abb.com/substationautomation
—
Most common function blocks
Function   ANSI
Protection
Three-phase current measurement CMMXU 3I 3I
Sequence current measurement CSMSQI I1, I2, I0 I1, I2, I0
Residual current measurement RESCMMXU Io In
Three-phase voltage measurement VMMXU 3U 3V
Residual voltage measurement RESVMMXU Uo Vn
Sequence voltage measurement VSMSQI U1, U2, U0 V1, V2, V0
Three-phase power and energy measurement PEMMXU P, E P, E
Load profile LDPMSTA LOADPROF LOADPROF
Frequency measurement FMMXU f f
Control
Circuit-breaker control CBXCBR I ↔ O CB I ↔ O CB
Disconnector control DCXSWI I ↔ O DCC I ↔ O DCC
Earthing switch control ESXSWI I ↔ O ESC I ↔ O ESC
Disconnector position indication DCSXSWI I ↔ O DC I ↔ O DC
Earthing switch position indication ESSXSWI I ↔ O ES I ↔ O ES
Auto-reclosing DARREC O → I 79
Synchronism and energizing check SECRSYN SYNC 25
Emergency start-up ESMGAPC ESTART ESTART
Tap changer position indication TPOSSLTC TPOSM 84M
Tap changer control with voltage regulator OLATCC COLTC 90V
Logging functions
Disturbance recorder RDRE DR DFR
Fault recorder FLTMSTA FR FR
Sequence event recorder SER SER SER
Complete customer documentation is available in the product pages
that can be accessed through abb.com/relion.

Other manuals for Relion 620 Series

14

Other ABB Controllers manuals

ABB RHD16000 Series User manual

ABB

ABB RHD16000 Series User manual

ABB Ability BECL/D.200.16 User manual

ABB

ABB Ability BECL/D.200.16 User manual

ABB Relion 620 Series User manual

ABB

ABB Relion 620 Series User manual

ABB CR307 Series User manual

ABB

ABB CR307 Series User manual

ABB RMC-100 User guide

ABB

ABB RMC-100 User guide

ABB Bitric P User manual

ABB

ABB Bitric P User manual

ABB UMC22-FBP Parts list manual

ABB

ABB UMC22-FBP Parts list manual

ABB IRC5 Compact User manual

ABB

ABB IRC5 Compact User manual

ABB COMMANDER 300 Operating instructions

ABB

ABB COMMANDER 300 Operating instructions

ABB 6128/10 Series User manual

ABB

ABB 6128/10 Series User manual

ABB MotiFlex e180 User guide

ABB

ABB MotiFlex e180 User guide

ABB ACS800-04 User manual

ABB

ABB ACS800-04 User manual

ABB AC 800M User manual

ABB

ABB AC 800M User manual

ABB NIESSEN 2260 Series User manual

ABB

ABB NIESSEN 2260 Series User manual

ABB ACS880-07 User manual

ABB

ABB ACS880-07 User manual

ABB MO132 User manual

ABB

ABB MO132 User manual

ABB ACS 6000 Quick start guide

ABB

ABB ACS 6000 Quick start guide

ABB i-bus KNX AC/S 1.x.1 Series User manual

ABB

ABB i-bus KNX AC/S 1.x.1 Series User manual

ABB Powernet EIB 6972 AG-102-500 User manual

ABB

ABB Powernet EIB 6972 AG-102-500 User manual

ABB Cylon FBXi Series User manual

ABB

ABB Cylon FBXi Series User manual

ABB Jocab Safety Vital 2 User manual

ABB

ABB Jocab Safety Vital 2 User manual

ABB ES/S 4.1.2.1 User manual

ABB

ABB ES/S 4.1.2.1 User manual

ABB ACS 400 User manual

ABB

ABB ACS 400 User manual

ABB 07CR41 User manual

ABB

ABB 07CR41 User manual

Popular Controllers manuals by other brands

Allegion LCN 8310-813 installation instructions

Allegion

Allegion LCN 8310-813 installation instructions

FASTRON. F330 Series CALIBRATION PROCEDURE

FASTRON.

FASTRON. F330 Series CALIBRATION PROCEDURE

GTAKE GK500-2T0.4B user manual

GTAKE

GTAKE GK500-2T0.4B user manual

EP Solar Tracer-1206RN instruction manual

EP Solar

EP Solar Tracer-1206RN instruction manual

EQ3 HmIPW-DRS4 Installation instructions and operation manual

EQ3

EQ3 HmIPW-DRS4 Installation instructions and operation manual

EP Solar SS1024R instruction manual

EP Solar

EP Solar SS1024R instruction manual

CUTES CT-2000F Series Instruction

CUTES

CUTES CT-2000F Series Instruction

Delta DTD Series instruction sheet

Delta

Delta DTD Series instruction sheet

Exalux CONTROLSKY user manual

Exalux

Exalux CONTROLSKY user manual

HomeMatic HM-LC-Dim1T-DR Installation and operating manual

HomeMatic

HomeMatic HM-LC-Dim1T-DR Installation and operating manual

Technische Alternative UVR 63H Operation and installation manual

Technische Alternative

Technische Alternative UVR 63H Operation and installation manual

BEING L Series Programming guide

BEING

BEING L Series Programming guide

Lenze C520 Commissioning

Lenze

Lenze C520 Commissioning

Concens icon quick guide

Concens

Concens icon quick guide

Shelly 2LED user guide

Shelly

Shelly 2LED user guide

Epever XTRA Series user manual

Epever

Epever XTRA Series user manual

CKD ER300 instruction manual

CKD

CKD ER300 instruction manual

Argus Cordex CXC Setup

Argus

Argus Cordex CXC Setup

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.