AB B A BILIT Y™ S M ART S ENSO R GAT EWAY
DOCUMENT ID REV. DATE LANG. PAGE
9AKK107046A4620 G April 2020 EN 4/17
© Copyright 2020 ABB. All rights reserved.
2 Installation
2.1 Prerequisites for installation
Internet connection:
- Gateway does not operate in networks with VPN (Virtual Private Network).
- In case there is a firewall used, following ports need to be opened:
Type Port M/O
Partner for
Gateway
Direction Description
UDP 5246,
5247 Mandatory Access Controller
(AC) OUT Default CAPWAP communication
between AC and router
UDP 6246,
6247 Optional Access Controller
(AC) OUT Backup CAPWAP communication
between AC and router
TCP 8883 Optional Access Controller
(AC) OUT MQTT communication between
AC and router
TCP 1883 Optional Local MQTT broker OUT MQTT bypass function
TCP/HTTP 80 Mandatory Access Controller
(AC) OUT Container/APP download from
AC
TCP/HTTPS 443 Mandatory Smart Sensor
Platform OUT
Communication with Smart
Sensor Platform
Container/APP download from
AC
TCP 9999 Mandatory Access Controller
(AC) OUT Remote SSH to container
UDP 53 Mandatory DNS server OUT DNS lookup for AC address
The above table is considered from gateway perspective, thus all communication with
Direction Out is from the gateway to the communication partner. All communication with
Direction In is from the communication partner towards the gateway. All communication
with In-out is bidirectional.
AC – Access Controller
Global: abb.cassia.pro
China: gw.smartsensor.abb.com.cn
Smart Sensor Platform
Global: smartsensor.abb.com
China: smartsensor.abb.com.cn
- Mobile network needs to have adequate signal strength. In most demanding
locations, an extension USB cable or external antenna might be needed for USB
modem/dongle.