PRODUCT MANUAL
Maintenance Bypass Panel For 827E Inverter
Plant
6310408P
6310408P-1

Page 2
© Copyright 2023 ABB. All rights reserved. 827E MBS_MAN Rev. 2.4
PRODUCT MANUAL
Maintenance Bypass Panel For 827E Inverter
Plant
6310408P
6310408P-1
TABLE OF CONTENTS
TABLE OF CONTENTS ································································································································· 3
FOREWARD ·················································································································································· 7
PRODUCT INFORMATION ··························································································································· 7
WARNINGS···················································································································································9
CAUTIONS ················································································································································· 10
1 – THEORY OF OPERATION······················································································································ 13
2 – INSTALLER INFORMATIONL················································································································· 21
2.1. GENERAL ······················································································································································ 9
2.2. MAINTENANCE BYPASS PANEL DESCRIPTION······················································································· 9
2.3. MECHANICAL DIMENSION ························································································································ 9
2.4. ELECTRICAL SPECIFICATION···················································································································· 9
2.5. 827e INVERTER SYSTEM E/W MBS WIRING DIAGRAM·········································································10
3 – SYSTEM INSTALLATION······················································································································· 35
3.1. GENERAL ····················································································································································· 11
3.2. UTILITY (COMMERCIAL AC) INPUT CONNECTIONS·············································································12
3.3. INVERTER INPUT CONNECTIONS············································································································13
3.4. AC LOAD OUTPUT CONNECTIONS ·········································································································13
3.5. INPUT ALARM CONNECTIONS FROM THE 827E INVERTER PLANT ··················································14
3.6. OUTPUT ALARM CONNECTIONS FROM THE BAYPASS PANEL··························································15
3.7. BAT INPUT····················································································································································16
3.8. VERIFY INSTALLATION IS COMPLETE·····································································································16

Page 3
© Copyright 2023 ABB. All rights reserved. 827E MBS_MAN Rev. 2.4
Foreword
This manual is intended to help the user of the maintenance bypass panel to understand and install
the panel. If you should have any questions or problems, please contact one of the following sources:
SERVICE - If for any reason further assistance is needed on any power equipment, complete
engineering and field service groups are available at Phone: 1-877-546-3243 or 1-972-244-9288
PARTS ORDERING - Please contact +1 972-244-WATT (9288) or toll free at 877-546-3243 to request a
quote.
RETURN & REPAIR - Please contact +1 972-244-WATT (9288) or toll free at 877-546-3243 to request a
Return Material Authorization (RMA) for defective equipment.
Product Information
Please take a moment when the product is new to fill in this information. This data will allow faster
service when calling ABB Power to order accessories, spare parts, or request field service.
First, locate the product information label. This is typically located on the upper front of the
equipment frame, or on the rear of the frame. Fill in the part number, as it appears on the label, in
the space below.
PART NUMBER DATE CODE:
SERIAL NUMBER ECN Level:

Page 4
© Copyright 2023 ABB. All rights reserved. 827E MBS_MAN Rev. 2.4
Warnings
1. Electrical shock hazard. Do not attempt to remove, maintain, or install this equipment with power
applied. Personnel that attempt to work on this equipment with the power applied may subject
themselves or others to electrical shock that may cause serious injury or death.
Le danger électrique de choc. Pas la tentative pour enlever, maintenir, ou installer cet équipement
avec le pouvoir appliqué. Le personnel qui tente traiter cet équipement avec le pouvoir appliqué peut
s'exposer ou les autres au choc électrique qui peut causer la blessure ou la mort sérieuse
2. The use of this equipment by unauthorized or untrained personnel should not be attempted.
Personnel that work on this equipment without the proper training may subject themselves or
others to electrical shock that may cause serious injury or death.
L'usage de cet équipement par le personnel inautorisé ou sans formation ne devrait pas être tenté.
Le personnel qui traite cet équipement sans l'entraînement correct peut s'exposer ou les autres au
choc électrique qui peut causer la blessure ou la mort sérieuse
3. Do not attempt to work on this equipment if it is, or has been, exposed to a high moisture
condition. It is recommended the equipment be returned to ABB POWER to be properly tested.
Working on this equipment during a high moisture condition subjects the user to electrical shock
that may cause serious injury or death.
Pas la tentative pour traiter cet équipement si c'est, ou a été, exposé à une haute condition
d'humidité. Il est recommandé l'équipement s'est retourné à ABB POWER deux être convenablement
essayé. Traiter cet équipement pendant une haute condition d'humidité expose l'utilisateur au choc
électrique qui peut causer la blessure ou la mort Sérieuse
4. Use of an attachment other than one approved by ABB POWER will void any and all warranties,
implied or other, and will increase risk of fire, or may possibly cause electrical shock, injury, or death
to personnel
L'usage d'un attachement autrement qu'un approuvé par ABB POWER annulera n'importe quel et
toutes garanties, implicites ou autres, et augmentera le risque de feu, ou probablement peut causer
le choc électrique, la blessure, ou la mort au personnel.
5. Do not operate this equipment if it has been dropped or otherwise damaged. Trying to operate
this equipment if it has been damaged subjects yourself or others to electrical shock that may cause
serious injury or death.
L'usage d'un attachement autrement qu'un approuvé par ABB POWER annulera n'importe quel et
toutes garanties, implicites ou autres, et augmentera le risque de feu, ou probablement peut causer
le choc électrique, la blessure, ou la mort au personnel
6. Before you proceed, ensure the input source is not live and the input circuit breaker(s)/fuse(s) has
been tripped or removed. If these procedures have not been followed and the input/output power is
live, serious personnel injury or death may occur.

Page 5
© Copyright 2023 ABB. All rights reserved. 827E MBS_MAN Rev. 2.4
Warnings (continued)
Avant que vous procédez, assurez que la source d'entrée n'est pas en vie et le circuit d'entrée breaker
(s)/fuse(s) a été trébuché ou a été enlevé. Si ces procédures n'ont pas été suivies et le pouvoir
input-output est la blessure de personnel ou la mort en vie et sérieux peut arriver
7. A rack/shelf may contain several operating systems. If there is another system in the general area
you want to install this system, be cautious of any exposed connectors or wires and, with
permission, remove power to the other systems. Failure to take the necessary safety precautions
subjects the installer or maintenance personnel to severe electrical shock that may cause serious
injury or death.
Une étagère/étagère peut contenir plusieurs systèmes d'exploitation. S'il y a un autre système dans
le secteur général que vous voulez installer ce système, êtes prudent de connecteurs ou de fils
exposés et, avec la permission, enlevez le pouvoir aux autres systèmes. L'échec pour prendre les
précautions de sûreté nécessaires exposent le personnel d'installateur ou entretien au choc
électrique sévère qui peut causer la blessure ou la
mort sérieuse
8. This equipment may connect to lead-acid batteries. Battery posts, terminals, and related
accessories contain lead and lead compounds, chemicals known to the state of California to cause
cancer and birth defects or other reproductive harm. Wash hands after touching batteries.
Cet équipement peut connecter des piles mener- acides. Les postes de pile, les terminaux, et les
accessoires apparentés contient l'avance et les premiers composés, les produits chimiques connus à
l'état de Californie pour causer les défauts de cancer et naissance ou l'autre mal reproducteur. Laver
des mains après avoir touché des piles.
Cautions
1. Follow proper grounding instructions.
Suivre fonder correctes les instructions
2. If connecting batteries, remove the battery-box- fuse or trip the circuit breaker. Check batteries
and connections for proper polarity and power before connecting the batteries to the system.
Si connectant des piles, enlever la pile-boîte-le fusible ou trébuche le disjoncteur. Vérifier des piles et
des connexions pour la polarité et le pouvoir correcte avant de connecter les piles au système
3. To remove the circuit breakers or fuses, the DC and/or AC input to the system will need to be
disconnected, thereby disabling the system output to the load(s). Take the necessary precautions
and inform the plant engineer that the system output power to the loads will be disabled.
Pour enlever les disjoncteurs ou les fusibles, les données de courant alternatif de et/ou de DC au
système auront besoin d'être débranché, de cette façon rendant infirme la production de système au
chargement (les chargements). Prendre les précautions nécessaires et informer l'ingénieur de plante
que le pouvoir de production de système aux chargements seront rendus infirme.

Page 6
© Copyright 2023 ABB. All rights reserved. 827E MBS_MAN Rev. 2.4
Cautions (continued)
4. Before performing any maintenance, ensure AC or DC power is not applied to the system.
Avant d'exécuter n'importe quel entretien, assurer que le pouvoir de courant alternatif ou DC n'est
pas appliqué au système.
5. Fuse holders, fuses, and circuit breakers are not to be loaded to more than 80 percent of their
ampere rating.
Fondez les supports, fusibles, et des disjoncteurs ne doivent pas être chargés à plus de 80 pour cent
de leur estimation d'ampère.
6. This equipment is intended for restricted access locations only.
Cet équipement est projeté pour les emplacements d'accès limités seulement

Page 7
© Copyright 2023 ABB. All rights reserved. 827E MBS_MAN Rev. 2.4
1: Theory of Operation
The maintenance bypass panel (MBS) is designed to be used with the ABB POWER 827E inverter
plant. The main purpose of the MBS is to allow an AC load to be switched from its primary source
(Inverters) to an alternate source (commercial AC) and back to the primary source (Inverters) again.
This may be required, for example, when doing maintenance or upgrades to the Inverter Plant. The
transfer is done with a front panel mounted switch. The Inverter source and AC Line source are not
phase locked and the transfer is asynchronous, i.e., it occurs at random phase. For more information,
refer to schematic 4391036SD and 4391036SD-1 attached to the rear of this document.
A manual front panel “BYPASS” switch is used to select the load source. The “INVENTER.” mode
selects the Inverter source and is the normal state. The unit is said to be in “BYPASS” mode when the
“UTILITY” (commercial AC) source is selected. There are front panel LEDs to indicate if the
“INVERTER” and “commercial AC” voltages are present, and to indicate if the unit is in BYPASS mode.
While the INVENTER and AC LEDs indicate the presence of those source voltages, they do not prevent
the load transfer from occurring. It is the operator’s responsibility to know if the source that is being
transferred to is an energized source.
An alternate purpose of the MBS is to collect alarms from the inverter shelves and to extend these
alarms to the plant monitor. The status of the consolidated alarms is indicated by the upper three
LEDs on the front panel. Any Major alarm will light the Major LED and extend a form C transfer to the
plant monitor via a terminal block on the rear panel (see system schematic for details). A single Minor
alarm extend a minor alarm, however, two or more Minor alarms will generate a Major alarm and
retire (turn off) the Minor alarm. A Capacity alarm is an indication that an inverter shelf has exceeded
its programmed and/or equipped capacity. This alarm may be used as a prompt to add more inverter
capacity (i.e. shelves and modules). The load sharing capabilities of the 827E inverters will typically
cause multiple shelves to provide a Capacity Alarm at the same time, if configured and equipped
similarly. The Minor and Capacity alarms are extended to the plant monitor as form C transfers.
NOTE: The MBS is powered by a -48VDC battery input at the rear. If this input is not present, there
will be no LEDs lit on the front panel.

Page 8
© Copyright 2023 ABB. All rights reserved. 827E MBS_MAN Rev. 2.4

Page 9
© Copyright 2023 ABB. All rights reserved. 827E MBS_MAN Rev. 2.4
2: Installer Information
2.1 General
This section contains information that is intended to help the user install the maintenance bypass
panel. Included are physical and electrical specifications.
FIGURE 2-1: Front View of the 6310408P 10KVA Bypass Panel
FIGURE 2-2: Front View of the 6310408P-1 30KVA Bypass Panel
2.2 Maintenance Bypass Panel Description
The maintenance bypass panel provides a means to move a load from the inverter plant to utility
(commercial AC) source.
2.3 Mechanical Dimensions
HEIGHT : 6.97 inches
WIDTH : 23.00 inches
DEPTH : 14.88 inches
2.4 Electrical Specifications
Utility AC Power Input Input 1: 120 VAC, 60 Hz, 60 Amp max. AC, 1 Phase
Inverter Output AC Power Input Input 2: 120 VAC, 60 Hz, 60 Amp max. AC, 1 Phase
48VDC Input Input 3: 48VDC, 1.3 Amp
Maintenance Bypass Output Out put 1: 120 VAC, 60 Hz, 60 Amp max. AC, 1 Phase
CAPACITY:

Page 10
© Copyright 2023 ABB. All rights reserved. 827E MBS_MAN Rev. 2.4
2.4 Electrical Specifications (continued)
Utility AC Power Input Input 1: 120 VAC, 60 Hz, 240 Amp max. AC, 1 Phase
Inverter Output AC Power Input Input 2: 120 VAC, 60 Hz, 240 Amp max. AC, 1 Phase
48VDC Input Input 3: 48VDC, 1.3 Amp
Maintenance Bypass Output Out put 1: 120 VAC, 60 Hz, 240Amp max. AC, 1 Phase
CAPACITY:
FIGURE 2-3: MBS Wiring Diagram
2.5 827e Inverter System E/W MBS Wiring Diagram

Page 11
© Copyright 2023 ABB. All rights reserved. 827E MBS_MAN Rev. 2.4
3: System Installation
FIGURE 3-1: TYPICAL MAINTENANCE BYPASS PANEL INSTALLATION
3.1 General
NOTE: ABB POWER recommends that the Maintenance Bypass Panel is installed above the top-most
827E Inverter Shelf (refer to Figure 3-1). ABB POWER recommends leaving one rack mounting space
between the MBS and the first Inverter shelf as well as from Inverter shelf to inverter shelf to allow air
flow between units for proper heat dissipation (refer to Figure 3-1).
CABLING:
A. Remove the maintenance bypass panel from the shipping container.
B. Install the panel as follows:
1. Ensure there is proper clearance in the rack to install the maintenance bypass panel.
2. Put the panel into position and secure with the screws located at each outside corner (four screws total).
NOTE: The maintenance bypass panel is designed to be either flush or mid mounted.
MAINTENANCE
BYPASS PANEL

Page 12
© Copyright 2023 ABB. All rights reserved. 827E MBS_MAN Rev. 2.4
3.2 Utility (Commercial AC) Input Connections
WARNING: All power should remain in the OFF position for the entire installation section. Serious
injury or death could occur from live AC circuits. ABB POWER recommends that Licensed
Electricians wire all AC connections into the MBS.
A. Remove the rear cover to access the AC input connections. Refer to Figure 3-3.
B. Connect the commercial 120VAC power to the input connections as shown in Figure 3-3. Each input connection
is made via a compression screw. Maximum size cable is 350 MCM.
C. Ensure that commercial AC power is protected from the customer side of the bypass panel.
D. If used with an 827E Inverter Plant, a circuit breaker is provided in the inverter shelf to provide over current
protection or disconnect means between the inverter and MBS.
E. Over current protection for Commercial AC fed to the MBS is to be provided by the customer per the National
Electrical Code
NOTE: The NEC dictates that Commercial AC will have the Neutral strapped to ground. No
separately derived system (see NEC Article 100 for definition).
Figure 3-2: Model 827 Inverter System With Maintenance Bypass Switch And Optional Inverter Shelves

Page 13
© Copyright 2023 ABB. All rights reserved. 827E MBS_MAN Rev. 2.4
3.2 Utility (Commercial AC) Input Connections (continued)
Figure 3-3: Commercial AC Input Connections (view from top)
3.3 Inverter Input Connections
WARNING: Ensure that all DC input power is removed from the inverter system before beginning to
perform the maintenance bypass panel input connections. Serious injury or death could occur from
live AC circuits.
A. With the rear cover still removed, connect the output power from the inverter system to the
inverter input connections on the maintenance bypass panel as shown in Figure 3-4. Each input
connection is made via a compression screw. Maximum size cable is 6 GA.
Figure 3-4: Inverter Input Connections
3.4 AC Load Output Connections
WARNING: Ensure that all input power is removed from the maintenance bypass panel before
beginning to perform the load connections from the maintenance bypass panel. Serious injury or
death could occur from live AC circuits.
A. With the rear cover still removed, connect the LOAD (output power) from the maintenance
bypass panel to the load connections. Refer to Figure 3-5. Each LOAD output connection is made
via a compression screw. Maximum size cable is 350 MCM.
(GROUND )

Page 14
© Copyright 2023 ABB. All rights reserved. 827E MBS_MAN Rev. 2.4
3.4 AC Load Output Connections (continued)
Figure 3-5: Load Connections from Maintenance Bypass Panel
3.5 Input Alarm Connections From The 827E Inverter Plant
A. The maintenance bypass panel provides input alarm connections for each of the four inverter
shelves.
Inverter Shelf Number Panel
Inverter Shelf 1 J4
Inverter Shelf 2 J3
Inverter Shelf 3 J2
Inverter Shelf 4 J1
827E Inverter
Shelf.
Figure 3-6: Alarm Input Connections (from 827E Inverter Shelves)

Page 15
© Copyright 2023 ABB. All rights reserved. 827E MBS_MAN Rev. 2.4
3.6 Output Alarm Connections from the Bypass Panel
The maintenance bypass panel combines alarms from each inverter shelf and extends them from a
common set of alarm contacts. The four alarms include: Major, Minor, Capacity, and Bypass. Refer
to Table 3-1 for the alarm pin out connections
Table 3-1: Alarm Pin Out Connections for J6.
MAJOR 1CLOSE ON ALARM Any Major Alarm from inverter shelves 1, 2, 3, or 4.
Or
Two or more Minor Alarms from any inverter shelf.
3COMMON
2OPEN ON ALARM
MINOR 4OPEN ON ALARM
Any Minor Alarm from inverter shelves 1, 2, 3, or 4.
6COMMON
5CLOSE ON ALARM
CAPACITY 7OPEN ON ALARM
A Capacity Alarm from any of the inverter shelves (1, 2, 3, or 4).
9COMMON
8CLOSE ON ALARM
BYPASS 10 OPEN ON ALARM
12 COMMON
11 CLOSE ON ALARM
Compression
Figure 3-7: Alarm Output Connections (To customer alarms)

Page 16
© Copyright 2023 ABB. All rights reserved. 827E MBS_MAN Rev. 2.4
3.7 Bat Input
The maintenance bypass panel requires an input voltage of -48VDC protected with a 1 ⅓Amp
fuse from an external source.
J7: -48VDC Battery Input
Compression Style Terminal
Block.
Figure 3-8: BAT Input Connections
Pin 1 GROUND 3090125P-2Compression 14 – 20 AWG
Pin 2 -BATTERY
3.8 Verify Installation Is Complete
utility position and verify that the commercial AC power takes over the loads. Move
the switch back to the

Page 17
© Copyright 2023 ABB. All rights reserved. 827E MBS_MAN Rev. 2.4
We reserve the right to make technical changes or modify
the contents of this document without prior notice. With
regard to purchase orders, the agreed particulars shall
prevail. ABB does not accept any responsibility whatsoever
for potential errors or possible lack of information in this
document.
We reserve all rights in this document and in the subject matter and
illustrations contained therein. Any reproduction, disclosure to third
parties or utilization of its contents – in whole or in parts – is
forbidden without prior written consent of ABB.
Copyright© 2023 ABB
All rights reserved
ABB
601 Shiloh Rd.
Plano, TX USA
abbpowerconversion.com
This manual suits for next models
1
Table of contents
Other ABB Industrial Equipment manuals