ABB Ekip Touch User manual

—
OPERATING INSTRUCTIONS
Protection settings setup for
Ekip Touch Trip Units


—
Table of contents
004 Index of terms & settings table
005 Default protection settings
006– 040 Protection Setting Setup
006– 025 XT5, XT7/XT7M and Emax 2
026– 040 XT2 and XT4
041 – 052 Arc flash mitigation / RELT / 2I
Protection setup
053 – 055 Appendix for changing language
back to English
056– 062 How to set date and time
056 – 059 XT5, XT7/XT7M and Emax 2
060 – 062 XT2 and XT4

—
Index of terms / Field setting sheet
Traditional/Study ABB Ekip Touch
Reference Reference
Long Time Protection
t In
—
Settings table for breaker
Settings Value Traditional/Study ABB Ekip Touch Standards
Reference Reference Reference
Amps
Seconds
Amps
Seconds
Curve Type I Step OR Slope
Amps
Amps
Seconds
Curve Type I Step OR Slope
Amps
Advance
4EKIP TOUCH TRIP UNITS

—
Default protection settings
—
Example of study in EDSA
Protection Function Frame Enabled Trip
Enabled
Function /
Curve
Threshold /
Pickup Time / Delay Thermal
Memory Pre-alarm
Long Time Protection
ON -
ON
- -
ON - -
- - -
ON
-
-
-
-
*Protection must be Enabled=ON to input the settings.
—
Example of study in EDSA
Protection Function Frame Threshold / Pickup Range Time / Delay Range
Long Time Protection L Protection
-
1UL version: t2 Max = 0.4s
2I3 threshold must be higher than I2 (if S Enabled = ON)
3UL version: I4 Max = 1200A
4UL version: t4 max = 0.4s
—
Example of study in EDSA
CB: UPS-B-Load 1
MFR
Model XT5-N
Size 400
Rating
Cont. Amp
3-Phase kA
LG kA
Base kV
LV Solid state trip device
MFR
Model
Sensor
Phase setting
Long-time
INST
PROTECTION SETTINGS SETUP FOR EKIP TOUCH TRIP UNITS 5

—
Protection setting setup
XT5, XT7/XT7M and Emax 2
6EKIP TOUCH TRIP UNITS
d
f
Ekip TT Plug EndTrip Unit Service Connector
Power
Warning
Alarm
Home
iTEST
c
b
a
g
e
*Powered via USB port on laptop/computer
—

PROTECTION SETTINGS SETUP FOR EKIP TOUCH TRIP UNITS 7
HOME
Turn on
3
4

—
Factory Default Settings
Protection Function Frame Enabled Trip Enabled Function /
Curve
Threshold /
Pickup
Time /
Delay
Thermal
Memory Pre-alarm
Long Time Protection
ON -
—
Range Adjustability
Protection Function Frame Threshold / Pickup Range Time / Delay Range
Long Time Protection
8EKIP TOUCH TRIP UNITS
6
Protections Icon
ADJUSTING THE LONG TIME PROTECTION SETTINGS
5
L Protection Overload (49)

PROTECTION SETTINGS SETUP FOR EKIP TOUCH TRIP UNITS 9
7
8
Threshold I1
Confirm to accept zero
Confirm
This will allow Protection Settings to be changed per the coordination study.

10 EKIP TOUCH TRIP UNITS
ADJUSTING THE LONG TIME PICK UP OR THRESDHOLD I1
Long Time Pickup / Threshold I1
minus iconplus icon
Confirm
Long Time Delay / Time t1
10
ADJUSTING THE LONG TIME DELAY OR TIME T1
Time t1

PROTECTION SETTINGS SETUP FOR EKIP TOUCH TRIP UNITS 11
minus icon plus icon
Confirm
Long Time / L Protection
12

—
Range Adjustability
Protection Function Frame Threshold / Pickup Range Time / Delay Range
12 EKIP TOUCH TRIP UNITS
ADJUSTING THE SHORT TIME PROTECTION SETTINGS
OFF or ENABLE = OFF
13
14
Enable
—
Factory Default Settings
Protection Function Frame Enabled Trip Enabled Function /
Curve
Threshold /
Pickup
Time /
Delay
Thermal
Memory Pre-alarm
S Protection Selective
ON
- -
S Protection SelectiveShortCircuit(51/50TD)

PROTECTION SETTINGS SETUP FOR EKIP TOUCH TRIP UNITS 13
Enable On
15
16
ADJUSTING THE SHORT TIME CURVE TYPE OR FUNCTION
Function t=k (ANSI 50TD)

14 EKIP TOUCH TRIP UNITS
Function
ADJUSTING THE SHORT TIME PICK UP OR THRESHOLD I2
Threshold I2 4.0In
17
18

PROTECTION SETTINGS SETUP FOR EKIP TOUCH TRIP UNITS 15
20
ADJUSTING THE SHORT TIME DELAY OR TIME T2
Time t2 0.05s
Short Time Pickup / Threshold I2
minus iconplus icon
Confirm

16 EKIP TOUCH TRIP UNITS
Short Time Delay / Time t2
minus iconplus iconthe value in the coordination study
Confirm
Short Time / S Protection
22
left

—
Range Adjustability
Protection Function Frame Threshold / Pickup Range Time / Delay Range
-
PROTECTION SETTINGS SETUP FOR EKIP TOUCH TRIP UNITS 17
23
24
ADJUSTING THE INSTANTANEOUS PROTECTION SETTINGS
ADJUSTING THE INSTANTANEOUS PICK UP OR THRESHOLD I3
Threshold I3 4.0
—
Factory Default Settings
Protection Function Frame Enabled Trip Enabled Function /
Curve
Threshold /
Pickup
Time /
Delay
Thermal
Memory Pre-alarm
ON - - - - -
I Protection Short circuit (50)

18 EKIP TOUCH TRIP UNITS
Instantaneous Pickup / Threshold I3
minus iconplus icon
Confirm
Instantaneous / I Protection
26

—
Range Adjustability
Protection Function Frame Threshold / Pickup Range Time / Delay Range
PROTECTION SETTINGS SETUP FOR EKIP TOUCH TRIP UNITS 19
27
28
ADJUSTING THE GROUND FAULT PROTECTION SETTINGS
OFF or ENABLE = OFF
Enable
—
Factory Default Settings
Protection Function Frame Enabled Trip Enabled Function /
Curve
Threshold /
Pickup
Time /
Delay
Thermal
Memory Pre-alarm
ON
-
Step 27. Press the G Protection Earth fault (51N/50NTD) row

20 EKIP TOUCH TRIP UNITS
Enable On
G Protection
30
ADJUSTING THE GROUND FAULT CURVE OR FUNCTION
Function t=k (ANSI 50TD)
29
This manual suits for next models
6
Table of contents
Other ABB Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

Nordson
Nordson AD-31 Series product manual

Arcteq
Arcteq AQ 1000 instruction manual

RK Rose+Krieger
RK Rose+Krieger LZ60 S/P Assembly instructions

Baileigh Industrial
Baileigh Industrial B8105 Operator's manual

BVA Hydraulics
BVA Hydraulics HULN3002 instruction manual

Dwyer Instruments
Dwyer Instruments MTL7706 instruction manual