Default protection settings
—
Example of study in EDSA
Protection Function Frame Enabled Trip
Enabled
Function /
Curve
Threshold /
Pickup Time / Delay Thermal
Memory Pre-alarm
Long Time Protection
ON -
ON
- -
ON - -
- - -
ON
-
-
-
-
*Protection must be Enabled=ON to input the settings.
—
Example of study in EDSA
Protection Function Frame Threshold / Pickup Range Time / Delay Range
Long Time Protection L Protection
-
1UL version: t2 Max = 0.4s
2I3 threshold must be higher than I2 (if S Enabled = ON)
3UL version: I4 Max = 1200A
4UL version: t4 max = 0.4s
—
Example of study in EDSA
CB: UPS-B-Load 1
MFR
Model XT5-N
Size 400
Rating
Cont. Amp
3-Phase kA
LG kA
Base kV
LV Solid state trip device
MFR
Model
Sensor
Phase setting
Long-time
INST
PROTECTION SETTINGS SETUP FOR EKIP TOUCH TRIP UNITS 5