ABB Relion 615 series User manual

Relion® 615 series
Transformer Protection and Control
RET615 ANSI
DNP3 Point List Manual


Document ID: 1MAC203317-MB
Issued: 01/20/2010
Revision: A
Product version: 2.0
© Copyright 2010 ABB. All rights reserved

Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third party,
nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or product
names mentioned in this document may be trademarks or registered trademarks of their
respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB Inc.
Distribution Automation
4300 Coral Ridge Drive
Coral Springs, FL 33065, USA
Toll-free: 1 (800) 523-2620
Phone: +1 954-752-6700
Fax: +1 954 345-5329
http://www.abb.com/substationautomation

Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or
product description and are not to be deemed as a statement of guaranteed properties.
All persons responsible for applying the equipment addressed in this manual must
satisfy themselves that each intended application is suitable and acceptable, including
that any applicable safety or other operational requirements are complied with. In
particular, any risks in applications where a system failure and/or product failure would
create a risk for harm to property or persons (including but not limited to personal
injuries or death) shall be the sole responsibility of the person or entity applying the
equipment, and those so responsible are hereby requested to ensure that all measures
are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested to
notify the manufacturer. Other than under explicit contractual commitments, in no
event shall ABB be responsible or liable for any loss or damage resulting from the use
of this manual or the application of the equipment.

Conformity
This product complies with the directive of the Council of the European Communities
on the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for
use within specified voltage limits (Low-voltage directive 2006/95/EC). This
conformity is the result of tests conducted by ABB in accordance with the product
standards EN 50263 and EN 60255-26 for the EMC directive, and with the product
standards EN 60255-6 and EN 60255-27 for the low voltage directive. The IED is
designed in accordance with the international standards of the IEC 60255 series and
ANSI C37.90. The DNP protocol implementation in the IED conforms to "DNP3
Intelligent Electronic Device (IED) Certification Procedure Subset Level 2", available
at www.dnp.org .

Table of contents
Section 1 Introduction............................................................................3
This manual..............................................................................................3
Intended audience....................................................................................3
Product documentation.............................................................................4
Product documentation set..................................................................4
Document revision history...................................................................5
Related documentation........................................................................6
Symbols and conventions.........................................................................6
Safety indication symbols....................................................................6
Manual conventions.............................................................................6
Functions, codes and symbols............................................................7
Section 2 DNP3 data mappings..........................................................11
Overview.................................................................................................11
Section 3 DNP3 protocol implementation............................................25
DNP3 device profile................................................................................25
DNP3 implementation table....................................................................27
Section 4 Glossary..............................................................................31
Table of contents
RET615 ANSI 1
Point List Manual

2

Section 1 Introduction
1.1 This manual
The point list manual describes the outlook and properties of the data points specific to
the IED. The manual should be used in conjunction with the corresponding
communication protocol manual.
1.2 Intended audience
This manual addresses the communication system engineer or system integrator
responsible for pre-engineering and engineering for communication setup in a
substation from an IED perspective.
The system engineer or system integrator must have a basic knowledge of
communication in protection and control systems and thorough knowledge of the
specific communication protocol.
1MAC203317-MB A Section 1
Introduction
RET615 ANSI 3
Point List Manual

1.3 Product documentation
1.3.1 Product documentation set
Planning & purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
deinstalling & disposal
Application manual
Operation manual
Installation manual
Service manual
Engineering manual
Commissioning manual
Communication protocol
manual
Technical manual
Planning & purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
deinstalling & disposal
Planning & purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
deinstalling & disposal
Application manualApplication manual
Operation manualOperation manual
Installation manualInstallation manual
Service manualService manual
Engineering manualEngineering manual
Commissioning manualCommissioning manual
Communication protocol
manual
Communication protocol
manual
Technical manualTechnical manual
en07000220.vsd
IEC07000220 V1 EN
Figure 1: The intended use of manuals in different lifecycles
The engineering manual contains instructions on how to engineer the IEDs using the
different tools in PCM600. The manual provides instructions on how to set up a
PCM600 project and insert IEDs to the project structure. The manual also recommends
a sequence for engineering of protection and control functions, LHMI functions as well
as communication engineering for IEC 61850 and DNP3.
The installation manual contains instructions on how to install the IED. The manual
provides procedures for mechanical and electrical installation. The chapters are
organized in chronological order in which the IED should be installed.
The commissioning manual contains instructions on how to commission the IED. The
manual can also be used by system engineers and maintenance personnel for assistance
Section 1 1MAC203317-MB A
Introduction
4RET615 ANSI
Point List Manual

during the testing phase. The manual provides procedures for checking of external
circuitry and energizing the IED, parameter setting and configuration as well as
verifying settings by secondary injection. The manual describes the process of testing
an IED in a substation which is not in service. The chapters are organized in
chronological order in which the IED should be commissioned.
The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for monitoring, controlling and
setting the IED. The manual also describes how to identify disturbances and how to
view calculated and measured power grid data to determine the cause of a fault.
The service manual contains instructions on how to service and maintain the IED. The
manual also provides procedures for de-energizing, de-commissioning and disposal of
the IED.
The application manual contains application descriptions and setting guidelines sorted
per function. The manual can be used to find out when and for what purpose a typical
protection function can be used. The manual can also be used when calculating settings.
The technical manual contains application and functionality descriptions and lists
function blocks, logic diagrams, input and output signals, setting parameters and
technical data sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during normal
service.
The communication protocol manual describes a communication protocol supported by
the IED. The manual concentrates on vendor-specific implementations.
The point list manual describes the outlook and properties of the data points specific to
the IED. The manual should be used in conjunction with the corresponding
communication protocol manual.
Some of the manuals are not available yet.
1.3.2 Document revision history
Document revision/date Product series version History
A/01/20/2010 2.0 First release
Download the latest documents from the ABB web site http://
www.abb.com/substationautomation.
1MAC203317-MB A Section 1
Introduction
RET615 ANSI 5
Point List Manual

1.3.3 Related documentation
Name of the document Document ID
DNP3 Communication Protocol Manual 1MAC052460-MB
1.4 Symbols and conventions
1.4.1 Safety indication symbols
The caution icon indicates important information or warning related to
the concept discussed in the text. It might indicate the presence of a
hazard which could result in corruption of software or damage to
equipment or property.
The information icon alerts the reader to important facts and conditions.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Although warning hazards are related to personal injury, it should be understood that
operation of damaged equipment could, under certain operational conditions, result in
degraded process performance leading to personal injury or death. Therefore, comply
fully with all warning and caution notices.
1.4.2 Manual conventions
Conventions used in IED manuals. A particular convention may not be used in this
manual.
• Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the push
button icons, for example:
To navigate between the options, use and .
•HMI menu paths are presented in bold, for example:
Select Main menu/Settings.
• LHMI messages are shown in Courier font, for example:
Section 1 1MAC203317-MB A
Introduction
6RET615 ANSI
Point List Manual

To save the changes in non-volatile memory, select Yes and press .
•Parameter names are shown in italics, for example:
The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks, for example:
The corresponding parameter values are "Enabled" and "Disabled".
• IED input/output messages and monitored data names are shown in Courier font,
for example:
When the function picks up, the PICKUP output is set to TRUE.
• Dimensions are provided both in inches and mm. If it is not specifically mentioned
then the dimension is in mm.
1.4.3 Functions, codes and symbols
Table 1: Functions included in the RET615 standard configuration
Function IEC 61850 IEC 60617 ANSI
Protection
Three-phase non-directional time overcurrent
protection, low stage, high-voltage side
PHLPTOC1 3I>(1) 51P (1)
Three-phase non-directional time overcurrent
protection, high stage 1, high-voltage side
PHHPTOC1 3I>>(1) 50P (1)
Three-phase non-directional time overcurrent
protection, low stage, low-voltage side
PHLPTOC2 3I>(2) 51P (2)
Three-phase non-directional time overcurrent
protection, high stage 1, low-voltage side
PHHPTOC3 3I>>(3) 50P (2)
Ground non-directional time overcurrent protection,
low stage (Calculated), high-voltage side
EFLPTOC2 I0>(2) 51N (1)
Ground non-directional time overcurrent protection,
high stage 1 (Calculated), high-voltage side
EFHPTOC3 I0>> (3) 50N (1)
Ground non-directional time overcurrent protection,
high stage 1 (Calculated), low-voltage side
EFHPTOC5 I0>> (5) 50N (2)
Three-phase thermal overload protection, two time
constants, high-voltage side
T2PTTR1 3Ith>T 49T (1)
Loss of load protection, high-voltage side LOFLPTUC1 3I< 37 (1)
Circuit breaker failure protection, low-voltage side CCBRBRF1 3I>/IoBF(1) 50BF (2)
Low impedance restricted ground fault protection,
low-voltage side
LREFPNDF1 dIoLo> 87LOZREF (2)
Transformer differential protection for two winding
transformers
TR2PTDF1 3dI>T 87T
Three-phase overvoltage protection, stage 1, low-
voltage side
PHPTOV1 3U>(1) 59 (2)
Three-phase undervoltage protection, stage 1, low-
voltage side
PHPTUV1 3U<(1) 27 (2)
Ground overvoltage protection, low-voltage side ROVPTOV1 U0>(1) 59G (2)
Table continues on next page
1MAC203317-MB A Section 1
Introduction
RET615 ANSI 7
Point List Manual

Function IEC 61850 IEC 60617 ANSI
Negative sequence overvoltage protection, low-
voltage side
NSPTOV1 U2> 47 (2)
Directional ground-fault protection, low stage, low-
voltage side
DEFLPDEF1 I0>->(1) 67/51N (2)
Three-phase directional overcurrent protection, low
stage, low-voltage side
DPHLPDOC1 3I>->(1) 67/51P (2)
Ground non-directional time overcurrent protection,
low stage (Measured)
EFLPTOC1 I0>(1) 51G
Ground non-directional time overcurrent protection,
high stage 1 (Measured)
EFHPTOC1 I0>> (1) 50G
Ground non-directional time overcurrent protection,
low stage (Calculated), low-voltage side
EFLPTOC3 I0>(3) 51N (2)
Arc flash detector 1, low-voltage side ARCSARC1 ARC(1) AFD-1 (2)
Arc flash detector 2, low-voltage side ARCSARC2 ARC(2) AFD-2 (2)
Arc flash detector 3, low-voltage side ARCSARC3 ARC(3) AFD-3 (2)
Control
Circuit breaker control, low-voltage side CBXCBR1 I<->O CB 52 (2)
Supervision and monitoring
Circuit breaker condition monitoring, low-voltage side SSCBR1 CBCM 52CM (2)
Trip circuit monitoring 1 TCSSCBR1 TCS(1) TCM-1
Trip circuit monitoring 2 TCSSCBR2 TCS(2) TCM-2
Fuse failure supervision, low-voltage side SEQRFUF1 FUSEF 60 (2)
Measurement
Three-phase current measurement, high-voltage
side
CMMXU1 3I IA,IB,IC (1)
Three-phase current measurement, low-voltage side CMMXU2 3I(B) IA,IB,IC (2)
Three-phase voltage measurement, low-voltage side VMMXU1 3U VA,VB,VC (2)
Sequence current measurement , high-voltage side CSMSQI1 I1,I2,I0I1, I2, I0 (1)
Sequence current measurement , low-voltage side CSMSQI2 I1,I2,I0(B) I1, I2, I0 (2)
Sequence voltage measurement, low-voltage side VSMSQI1 U1,U2,U0V1,V2,V0 (2)
Three-phase power and energy measurement, low-
voltage side
PEMMXU1 P,E P,E (2)
Ground current measurement RESCMMXU1 I0 IG
Ground voltage measurement RESVMMXU1 U0 VG
Tap position TPOSSLTC1 TPOSM 84T
Digital fault recorder RDRE1 DR DFR
Sequence of events recorder SER SER SER
Table continues on next page
Section 1 1MAC203317-MB A
Introduction
8RET615 ANSI
Point List Manual

Function IEC 61850 IEC 60617 ANSI
Fault recorder FLTMSTA FR FLR
Electrically latched/self resetting trip output 1 TRPPTRC1 Trip(1) 86/94-1
Electrically latched/self resetting trip output 2 TRPPTRC2 Trip(2) 86/94-2
1MAC203317-MB A Section 1
Introduction
RET615 ANSI 9
Point List Manual

10

Section 2 DNP3 data mappings
2.1 Overview
This document describes the DNP3 data points and structures available in RET615
Ver. 2.0 ANSI.
The point tables show all the available DNP3 data points in this IED. The data objects
in the point tables are listed in alphabetical order based on the objects' IEC61850
names. Also the default point indexes, class assignments and scaling configurations are
shown. The DNP3 points can be freely added, removed, reorganized and reconfigured
using PCM600.
This list represents the superset of DNP3 points. The actual set of available points is
determined by the IED's ordercode. An asterisk (*) in a No Events column indicates
that no events can be generated for that point regardless of class assignment. An
asterisk (*) in Disabled column indicates that the point is not active. Inactive points can
be made active through PCM600.
Table 2: Binary inputs
No
event
61850 Path Default
Index
Default
Class
Disabled Description
* LD0.LLN0.LEDRs1.stVal 0 0 Protection LLN0 Indications and LEDs
* LD0.LLN0.LEDRs2.stVal 1 0 Protection LLN0 Alarm LEDs
LD0.LLN0.SetSeld.stVal 2 0,1 Protection LLN0 Settings reservation
LD0.LLN0.SetChg.stVal 3 0,1 Protection LLN0 Settings change
LD0.LEDPTRC1.Op.general 4 0,1 Global conditioning Operate
LD0.LEDPTRC1.Op.phsA 5 0,1 Global conditioning Operate
LD0.LEDPTRC1.Op.phsB 6 0,1 Global conditioning Operate
LD0.LEDPTRC1.Op.phsC 7 0,1 Global conditioning Operate
LD0.LEDPTRC1.Str.general 8 0,1 Global conditioning Start
LD0.LEDPTRC1.Str.neut 9 0,1 Global conditioning Start
LD0.LEDPTRC1.Str.phsA 10 0,1 Global conditioning Start
LD0.LEDPTRC1.Str.phsB 11 0,1 Global conditioning Start
LD0.LEDPTRC1.Str.phsC 12 0,1 Global conditioning Start
LD0.TRPPTRC1.Tr.general 13 0,1 TRPPTRC1 General trip output signal
LD0.TRPPTRC1.Op.general 14 0,1 TRPPTRC1 Operate input signal
Table continues on next page
1MAC203317-MB A Section 2
DNP3 data mappings
RET615 ANSI 11
Point List Manual

No
event
61850 Path Default
Index
Default
Class
Disabled Description
LD0.TRPPTRC2.Tr.general 15 0,1 TRPPTRC2 General trip output signal
LD0.TRPPTRC2.Op.general 16 0,1 TRPPTRC2 Operate input signal
* LD0.SSCBR1.InSprChStr.stVal 17 0 SSCBR1 CB spring charging started input
* LD0.SSCBR1.InSprCha.stVal 18 0 SSCBR1 CB spring charged input
* LD0.SSCBR1.InPresAlm.stVal 19 0 SSCBR1 Binary pressure input for alarm
* LD0.SSCBR1.InPresLO.stVal 20 0 SSCBR1 Binary pressure input for lockout indication
* LD0.SSCBR1.InPosOpn.stVal 21 0 SSCBR1 POSOPEN
* LD0.SSCBR1.InPosCls.stVal 22 0 SSCBR1 POSCLOSE
LD0.SSCBR1.OpnAlm.stVal 23 0,1 SSCBR1 CB open travel time exceeded set value
LD0.SSCBR1.ClsAlm.stVal 24 0,1 SSCBR1 CB close travel time exceeded set value
LD0.SSCBR1.SprChaAlm.stVal 25 0,1 SSCBR1 Spring charging time has crossed the set value
LD0.SSCBR1.OpNumAlm.stVal 26 0,1 SSCBR1 Number of CB operations exceeds alarm limit
LD0.SSCBR1.OpNumLO.stVal 27 0,1 SSCBR1 Number of CB operations exceeds lockout limit
LD0.SSCBR1.LonTmAlm.stVal 28 0,1 SSCBR1 CB 'not operated for long time' alarm
LD0.SSCBR1.PresAlm.stVal 29 0,1 SSCBR1 Pressure below alarm level
LD0.SSCBR1.PresLO.stVal 30 0,1 SSCBR1 Pressure below lockout level
* LD0.SSCBR1.PosOpn.stVal 31 0 SSCBR1 CB position is open
* LD0.SSCBR1.PosIvd.stVal 32 0 SSCBR1 INVALIDPOS
* LD0.SSCBR1.PosCls.stVal 33 0 SSCBR1 CB position is closed
LD0.SSCBR1.APwrAlm.stVal 34 0,1
SSCBR1 Accumulated currents power (Iyt) exceeded alarm
limit
LD0.SSCBR1.APwrLO.stVal 35 0,1
SSCBR1 Accumulated currents power (Iyt) exceeded lockout
limit
LD0.SSCBR1.CBLifAlm.stVal 36 0,1 SSCBR1 Remaining life of CB exceeded alarm limit
LD0.EFHPTOC1.Str.general 83 0,1 EFHPTOC1 Start
LD0.EFHPTOC1.Op.general 84 0,1 EFHPTOC1 Operate
* LD0.EFHPTOC1.InEnaMult.stVal 85 0 EFHPTOC1 Enable current multiplier
LD0.EFLPTOC1.Str.general 86 0,1 EFLPTOC1 Start
LD0.EFLPTOC1.Op.general 87 0,1 EFLPTOC1 Operate
* LD0.EFLPTOC1.InEnaMult.stVal 88 0 EFLPTOC1 Enable current multiplier
LD0.EFLPTOC2.Str.general 89 0,1 EFLPTOC2 Start
LD0.EFLPTOC2.Op.general 90 0,1 EFLPTOC2 Operate
LD0.EFLPTOC3.Str.general 91 0,1 EFLPTOC3 Start
LD0.EFLPTOC3.Op.general 92 0,1 EFLPTOC3 Operate
LD0.EFHPTOC3.Str.general 97 0,1 EFHPTOC3 Start
LD0.EFHPTOC3.Op.general 98 0,1 EFHPTOC3 Operate
Table continues on next page
Section 2 1MAC203317-MB A
DNP3 data mappings
12 RET615 ANSI
Point List Manual

No
event
61850 Path Default
Index
Default
Class
Disabled Description
LD0.EFHPTOC5.Str.general 101 0,1 EFHPTOC5 Start
LD0.EFHPTOC5.Op.general 102 0,1 EFHPTOC5 Operate
LD0.DEFLPTOC1.Str.general 105 0,1 DEFLPDEF1 Start
LD0.DEFLPTOC1.Op.general 106 0,1 DEFLPDEF1 Operate
LD0.INTRPTEF1.Str.general 109 0,1 INTRPTEF1 Start
LD0.INTRPTEF1.Op.general 110 0,1 INTRPTEF1 Operate
LD0.XGGIO130.Ind1.stVal 111 0,1 X130 (BIO) X130-Input 1
LD0.XGGIO130.Ind2.stVal 112 0,1 X130 (BIO) X130-Input 2
LD0.XGGIO130.Ind3.stVal 113 0,1 X130 (BIO) X130-Input 3
LD0.XGGIO130.Ind4.stVal 114 0,1 X130 (BIO) X130-Input 4
LD0.XGGIO130.Ind5.stVal 115 0,1 X130 (BIO) X130-Input 5
LD0.XGGIO130.Ind6.stVal 116 0,1 X130 (BIO) X130-Input 6
LD0.XGGIO130.SPCSO1.stVal 117 0,1 X130 (BIO) X130-Output 1
LD0.XGGIO130.SPCSO2.stVal 118 0,1 X130 (BIO) X130-Output 2
LD0.XGGIO130.SPCSO3.stVal 119 0,1 X130 (BIO) X130-Output 3
LD0.XAGGIO130.Ind1.stVal 120 0,1 X130 (AIM) X130-Input 1
LD0.XAGGIO130.Ind2.stVal 121 0,1 X130 (AIM) X130-Input 2
LD0.XAGGIO130.Ind3.stVal 122 0,1 X130 (AIM) X130-Input 3
LD0.XAGGIO130.Ind4.stVal 123 0,1 X130 (AIM) X130-Input 4
LD0.XGGIO120.Ind1.stVal 124 0,1 X120 (AIM) X120-Input 1
LD0.XGGIO120.Ind2.stVal 125 0,1 X120 (AIM) X120-Input 2
LD0.XGGIO120.Ind3.stVal 126 0,1 X120 (AIM) X120-Input 3
LD0.XGGIO120.Ind4.stVal 127 0,1 X120 (AIM) X120-Input 4
LD0.XGGIO110.Ind1.stVal 128 0,1 X110 (BIO) X110-Input 1
LD0.XGGIO110.Ind2.stVal 129 0,1 X110 (BIO) X110-Input 2
LD0.XGGIO110.Ind3.stVal 130 0,1 X110 (BIO) X110-Input 3
LD0.XGGIO110.Ind4.stVal 131 0,1 X110 (BIO) X110-Input 4
LD0.XGGIO110.Ind5.stVal 132 0,1 X110 (BIO) X110-Input 5
LD0.XGGIO110.Ind6.stVal 133 0,1 X110 (BIO) X110-Input 6
LD0.XGGIO110.Ind7.stVal 134 0,1 X110 (BIO) X110-Input 7
LD0.XGGIO110.Ind8.stVal 135 0,1 X110 (BIO) X110-Input 8
LD0.XGGIO110.SPCSO1.stVal 136 0,1 X110 (BIO) X110-Output 1
LD0.XGGIO110.SPCSO2.stVal 137 0,1 X110 (BIO) X110-Output 2
LD0.XGGIO110.SPCSO3.stVal 138 0,1 X110 (BIO) X110-Output 3
LD0.XGGIO110.SPCSO4.stVal 139 0,1 X110 (BIO) X110-Output 4
LD0.XGGIO100.SPCSO1.stVal 140 0,1 X100 (PSM) X100-Output P01
Table continues on next page
1MAC203317-MB A Section 2
DNP3 data mappings
RET615 ANSI 13
Point List Manual

No
event
61850 Path Default
Index
Default
Class
Disabled Description
LD0.XGGIO100.SPCSO2.stVal 141 0,1 X100 (PSM) X100-Output P02
LD0.XGGIO100.SPCSO3.stVal 142 0,1 X100 (PSM) X100-Output S01
LD0.XGGIO100.SPCSO4.stVal 143 0,1 X100 (PSM) X100-Output S02
LD0.XGGIO100.SPCSO5.stVal 144 0,1 X100 (PSM) X100-Output S03
LD0.XGGIO100.SPCSO6.stVal 145 0,1 X100 (PSM) X100-Output S04
LD0.LEDGGIO1.SPCSO1.stVal 146 0,1 Alarm LEDs LED 1
LD0.LEDGGIO1.SPCSO2.stVal 147 0,1 Alarm LEDs LED 2
LD0.LEDGGIO1.SPCSO3.stVal 148 0,1 Alarm LEDs LED 3
LD0.LEDGGIO1.SPCSO4.stVal 149 0,1 Alarm LEDs LED 4
LD0.LEDGGIO1.SPCSO5.stVal 150 0,1 Alarm LEDs LED 5
LD0.LEDGGIO1.SPCSO6.stVal 151 0,1 Alarm LEDs LED 6
LD0.LEDGGIO1.SPCSO7.stVal 152 0,1 Alarm LEDs LED 7
LD0.LEDGGIO1.SPCSO8.stVal 153 0,1 Alarm LEDs LED 8
LD0.LEDGGIO1.SPCSO9.stVal 154 0,1 Alarm LEDs LED 9
LD0.LEDGGIO1.SPCSO10.stVal 155 0,1 Alarm LEDs LED 10
LD0.LEDGGIO1.SPCSO11.stVal 156 0,1 Alarm LEDs LED 11
LD0.CMMXU1.HiAlm.stVal 157 0,1 CMMXU1 High alarm
LD0.CMMXU1.HiWrn.stVal 158 0,1 CMMXU1 High warning
LD0.CMMXU1.LoWrn.stVal 159 0,1 CMMXU1 Low warning
LD0.CMMXU1.LoAlm.stVal 160 0,1 CMMXU1 Low alarm
LD0.CMMXU2.HiAlm.stVal 161 0,1 CMMXU2 High alarm
LD0.CMMXU2.HiWrn.stVal 162 0,1 CMMXU2 High warning
LD0.CMMXU2.LoWrn.stVal 163 0,1 CMMXU2 Low warning
LD0.CMMXU2.LoAlm.stVal 164 0,1 CMMXU2 Low alarm
LD0.RESCMMXU1.HiAlm.stVal 165 0,1 RESCMMXU1 High alarm
LD0.RESCMMXU1.HiWrn.stVal 166 0,1 RESCMMXU1 High warning
LD0.RESVMMXU1.HiAlm.stVal 169 0,1 RESVMMXU1 High alarm
LD0.RESVMMXU1.HiWrn.stVal 170 0,1 RESVMMXU1 High warning
LD0.VMMXU1.HiAlm.stVal 171 0,1 VMMXU1 High alarm
LD0.VMMXU1.HiWrn.stVal 172 0,1 VMMXU1 High warning
LD0.VMMXU1.LoWrn.stVal 173 0,1 VMMXU1 Low warning
LD0.VMMXU1.LoAlm.stVal 174 0,1 VMMXU1 Low alarm
LD0.PHHPTOC1.Str.general 196 0,1 PHHPTOC1 Start
LD0.PHHPTOC1.Str.phsA 197 0,1 PHHPTOC1 Start
LD0.PHHPTOC1.Str.phsB 198 0,1 PHHPTOC1 Start
LD0.PHHPTOC1.Str.phsC 199 0,1 PHHPTOC1 Start
Table continues on next page
Section 2 1MAC203317-MB A
DNP3 data mappings
14 RET615 ANSI
Point List Manual
Other manuals for Relion 615 series
41
This manual suits for next models
1
Table of contents
Other ABB Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

RNA
RNA PARU Operating and assembly instruction

Nexen
Nexen AIR CHAMP FC-605 user manual

HEIDENHAIN
HEIDENHAIN MSE 1180 installation instructions

Allen-Bradley
Allen-Bradley ControlNet Coax Tap 1786-TPR installation instructions

WIKA
WIKA MTUT007MOEN User and maintenance manual

Pitzl
Pitzl 10529.1093 quick start guide