AEC NST3100010 User manual

1
Uninterruptible Power Supply-UPS
NST3 1KVA-6KVA
USER MANUAL

1.Safety Instructions
1.1 Transport
★Please transport the UPS system only in the original pa kaging (to prote t against sho k and impa t).
1.2 Set-up
★Condensation may o ur if the UPS system is moved dire tly from a old to a warm environment. The UPS
system must be absolutely dry before being installed. Please allow an a limatization time of at least two
hours.
★Do not install the UPS system near water or in damp environments.
★Do not install the UPS system where it would be exposed to dire t sunlight or near heat.
★Do not blo k off ventilation openings in the UPS system’s housing.
1.3 Installation
★Do not onne t applian es or items of equipment whi h would overload the UPS system (e.g. laser printers) to
the UPS outlet so ket
★Pla e ables in su h a way that no one an step on or trip over them.
★Do not onne t domesti applian es su h as hair dryers to UPS output so kets.
★The UPS an be operated by any individuals with no previous experien e
★ Conne t the UPS system only to an earthed sho kproof so ket outlet.
★The building wiring so ket outlet (sho kproof so ket outlet) must be easily a essible and lose to the UPS
system.
★Please use only VDE-tested, CE-marked mains able (e.g. the mains able of your omputer) to onne t the
UPS system to the building wiring so ket outlet (sho kproof so ket outlet).
★Please use only VDE-tested, CE-marked power ables to onne t the loads to the UPS system.
★ This is operator installable.
★ When installing the equipment, it should ensure that the sum of the leakage urrent of the
UPS and the onne ted onsumer does not ex eed 3.5mA.
2
Please read the FOLLOWING user manual and the safety
instru tions before installing the unit and starting it up!

1.4 Operation
★Do not dis onne t the mains able on the UPS system or the building wiring so ket outlet (sho kproof so ket
outlet) during operations sin e this would an el the prote tive earthing of the UPS system and of all
onne ted loads.
★The UPS system features its own, internal urrent sour e (batteries). The UPS output so kets or output
terminals blo k may be ele tri ally lived even if the UPS system is not onne ted to the building wiring so ket
outlet.
★In order to fully dis onne t the UPS system, first press the Standby swit h then dis onne t the mains lead
★Ensure that no fluids or other foreign obje ts an enter the UPS system.
★The UPS operates with hazardous voltages. Only qualified maintenan e personnel may arry out repairs
1.5 Maintenance, servicing and faults
★The UPS system operates with hazardous voltages. Repairs may be arried out only by qualified
maintenan e personnel.
★Caution - risk of ele tri sho k. Even after the unit is dis onne ted from the mains power supply (building
wiring so ket outlet), omponents inside the UPS system are still onne ted to the battery and are still
ele tri ally live and dangerous.
★Before arrying out any kind of servi ing and/or maintenan e, dis onne t the batteries and verify that no
urrent is present and no hazardous voltage exist in the terminals of high apability apa itor su h as BUS-
apa itors.
★Only persons are adequately familiar with batteries and with the required pre autionary measures may
repla e batteries and supervise operations. Unauthorised persons must be kept well away from the batteries.
★Caution - risk of ele tri sho k. The battery ir uit is not isolated from the input voltage. Hazardous voltages
may o ur between the battery terminals and the ground. Before tou hing, please verify that no voltage is
present!
★Batteries may ause ele tri sho k and have a high short- ir uit urrent. Please take the pre autionary
measures spe ified below and any other measures ne essary when working with batteries:
remove wristwat hes, rings and other metal obje ts
use only tools with insulated grips and handles.
★When hanging batteries, install the same number and same type of batteries.
★Do not attempt to dispose of batteries by burning them. This ould ause battery explosion.
★Do not open or destroy batteries. Es aping ele trolyte an ause injury to the skin and eyes. It may be toxi .
★Please repla e the fuse only by a fuse of the same type and of the same amperage in order to avoid fire
hazards.
★Do not dismantle the UPS system.
3

2. Description of commonly used notations
Some or all of the following Notations may be used in this manual and may appear in your appli ation pro ess.
Therefore, all users should be familiar with them and understand their explanations.
4

3. Introduction
This On-Line-Series is an uninterruptible power supply in orporating double- onverter te hnology. It provides
perfe t prote tion spe ifi ally for Novell, Windows NT and UNIX servers.
The double- onverter prin iple eliminates all mains power disturban es. A re tifier onverts the alternating
urrent from the so ket outlet to dire t urrent. This dire t urrent harges the batteries and powers the inverter.
On the basis of this DC voltage, the inverter generates a sinusoidal AC voltage, whi h permanently supplies the
loads.
Computers and periphery are thus powered entirely by the mains voltage. In the event of power failure, the
maintenan e-free batteries power the inverter.
This manual overs the UPS listed as follows. Please onfirm whether it is the model you intend to pur hase by
performing a visual inspe tion of the Model No. on the rear panel of the UPS.
Model No. Std Model No. Long ba k
NST3100010 NST3100010-L
NST3100020 NST3100020-L
NST3100030 NST3100030-L
NST3100050 NST3100050-L
NST3100060 NST3100060-L
Remark
“L” Model: Long ba kup time
5

4. System Description
Fi ure 1: LED Display Panel
Switc Function
ON - Switch Turn on UPS system:
By pressing the ON-Swit h “I” the UPS system is turned on.
OFF-Switch When mains power is normal, the UPS system swit hes to Standby mode by
pressing OFF-Swit h . It is then swit hed to Bypass and the inverter is off. At this
moment, the output so kets are supplied with voltage via the bypass if the mains
power is available.
Multi-Function
Switch
When UPS system turned on, tou h this button, “Load apa ity LED” and
“Battery apa ity LED” will shine by turns, then its apa ity will be shown.
Display Function
LINE mode LED The LINE mode LED lights up if mains voltage is applied to the UPS input.
LINE mode LED blinks when the phase and neutral ondu tor have been
reversed at the input of the UPS system.
BAT mode LED The BAT mode LED lights up when the mains power has failed and the inverter is
being powered by the batteries.
BYPASS mode
LED
The BYPASS mode LED lights up when the UPS system is supplying voltage
provided by the mains power via the bypass.
FAULT mode LED The FAULT mode LED lights up and an a ousti warning signal is issued
ontinuously when the UPS system is in fault ondition.
LOAD and BAT
capacity LEDs
These LEDs show the load of the UPS system if the LOAD apa ity LED light up:
1st LED 0-25% 2nd LED 26-50%
3rd LED 51-75% 4th LED 76-100%
These LEDs show the battery apa ity of the UPS system if the BAT apa ity LED
light up 1st LED 0-25% 2nd LED 26-50%
3rd LED 51-75% 4th LED 76-100%
6
Load apa ity LED
Bat apa ity LED
Fault mode LED
Bat mode LED
Indi ator 4
Indi ator 3
Indi ator 2
Indi ator 1
Line mode LED
Bypass mode LED
ON – Swit h
OFF – Swit h
Multi-Fun tion
Swit h

Fi ure 2: LED Display Panel
LCD display details as followin :
Wel ome
WEL COME TO USE
GREEN PO WER
System status
SYST E M STATUS
LINE MODE
Input hara teristi
INPUT
120 Vac 60 .0Hz
Input hara teristi
OUTPUT
120Vac 60.0Hz
Battery hara teristi
ATTERY
80.2V 100 %
Load and temperature
LOAD T EMP
25% 25
℃
Note: the Line mode LED and the Bypass mode LED is the same LED in LCD panel UPS.
7
Fault mode LED
Bat mode LED
Line &Bypass
mode LED
LCD Display

5. Connection and Operation
5.1 Connection and operation for 1K(L)1.5k(L)/ 2K(L)/ 3K(L)
1) Inspe tion: Inspe t the pa kaging arton and its ontents for damage. Please inform the transport agen y
immediately should you find signs of damage.
Please keep the pa kaging in a safe pla e for future use.
Note: Please ensure t at t e incoming feeder is isolated and secured to prevent it from being
switc ed back on again.
2) Conne tion:
2.1) UPS Input Connection
If the UPS is onne ted via the power ord, please use a proper so ket with prote tion against
ele tri urrent, and pay attention to the apa ity of the so ket: over 15A for 1~3K.
2.2) UPS Output Connection
Simply plug the load power ord to the output so kets to omplete onne tion.
Model No. Output Socket (pcs) Terminal Block
NST3100010 2 Nil
NST3100020 3+1high urrent output Nil
NST3100030 3+1high urrent output Nil
NST3100050-L 0 1
NST3100060 0 1
2.3) Computer Connection:
Conne t your omputer to the outlet so kets of the UPS system following the above diagram.
8
Caution!
*Do not onne t equipment whi h would overload the UPS system (e.g. laser printers)
When installing the ele tri al wiring, please note the nominal amperage of your
in oming feeder
The system may be installed and wired only by qualified ele tri ians in a ordan e with
appli able safety regulations!

3) Battery Charge: Fully harge the batteries of the UPS system by leaving the UPS system onne ted to the
mains for 1-2 hours. You may use the UPS system dire tly without harging it but the
stored energy time may be shorter than the nominal value spe ified.
4) Turn On the UPS:
4.1) With utility power connecting:
Conne t the utility power UPS will get into the Bypass mode, the Bypass mode LED will light up.
Press “ON” button ontinuously for more than 1 se ond to turn on the UPS. Then the UPS will get
into self-test status first. After having finishing the self-test, the UPS will get into the inverter mode,
at this time, the LINE mode LED will light up.
4.2) Without utility power connecting:
Even though utility power is not onne ted to the UPS, the UPS still an be turned on by just
simply pressing “ON” button ontinuously for more than 1 se ond. Then the UPS will get into self-
test status first. After having finishing the self-test, the UPS will get into the inverter mode, at this
time, Battery mode LED, will light up.
5) Test Fun tion:
Test the fun tion of the UPS system by either pressing the On-Swit h or dis onne ting the input of the UPS
system from the power supply.
6) Turn Off the UPS:
6.1) In In erter Mode:
Press “OFF“ button ontinuously for more than 1 se ond to turn off the UPS. Then the UPS will get
into self-test status first. After having finished the self-test, the UPS will get into bypass mode and
Bypass mode LED will light up. At this time, the UPS might has output. Dis onne t the utility power
to turn off the output.
6.2) In Battery Mode:
Press “OFF“ button ontinuously for more than 1 se ond to turn off the UPS. Then the UPS will get
into self-test status first. After having finished the self-test, the UPS will be turned off ompletely.
7) Audible Alarm Mute Fun tion: If the alarm is too annoying in battery mode, you may press “ON” button
ontinuously for more than 1 se ond to lear it. Moreover, the alarm will be enabled when the battery is
low to remind you to shutdown the load soon.
9

8) Operation Pro edure of External Battery for Long Ba kup time Model (“L” Model)
(1) Use the battery pa k with right voltage. Conne tion of batteries more than or less than required will
ause abnormality
(2) One end of the external battery ord is a plug for onne ting the UPS and the other end has a plug
for onne ting the user battery abinet
(3) Do not onne t the UPS to any load yet. Then, onne t the power ord of the UPS to supply utility
power to the UPS to make the UPS operate in utility power mode.
(4) Conne t the plug of the external battery ord to the external battery so ket on the rear panel of the
UPS to omplete the onne tion pro edure and the UPS will start to harge the battery pa k.
6. Maintenance
6.1 Operation
The UPS system ontains no user-servi eable parts. If the battery servi e life (3 - 5 years at 25°C ambient
temperature) has been ex eeded, the batteries must be repla ed. In this ase please onta t your dealer.
6.2 Stora e
If the batteries are stored in temperate limati zones, they should be harged every three months for 1-2
hours. You should shorten the harging intervals to two months at lo ations subje t to high temperatures.
10

7. Technical Data
7.1 Electrical specifications
INPUT
Model No. 1KVA 2KVA 3KVA 5KVA 6KVA
Phase Single
Frequen y 50/60Hz
OUTPUT
Model No. 1KVA 2KVA 3KVA 5KVA 6KVA
Power rating 1kVA/0.8kW 2kVA/1.6kW 3kVA/2.4kW 5KVA/4KW 6KVA/4.8KW
Voltage 220/230/240×1-2%VAC OR 110/115/120×1-
2%VAC
220/230/240×1-2%VAC
Frequen y 50/60×1±0.3%Hz (Battery mode)
Wave form sinusoidal
BATTERIES
Model No. 1KVA 2KVA 3KVA 5KVA 6KVA
Number and type 3×12V 7/9Ah 6×12V 7/9Ah 8×12V 7/9Ah 10×12V 9Ah 20×12V 7/9Ah
7.2 Operatin Environment
Ambient Temperature 0 oC to 40 oC
Operating humidity < 95%
Altitude < 7000Feet
Storage temperature 0 oC ~ 40 oC
7.3 Dimensions and wei hts
Model No. Dimensions W x D x H (mm) Net Weight kg
1KVA 144X 420X215 16KG (3p s batteries)
1KVA-L 144X 420X215 8
2KVA 191X475X340 31KG (6p s batteries)
2KVA-L 191X475X340 18
3KVA 191X475X340 35KG (8p s batteries)
3KVA-L 191X475X340 18
5-6KVA-L 213 X 475 X 340 18
5KVA 213 X 510 X 427 45KG (10p s batteries)
6KVA 213 X 510 X 427 70KG (20p s batteries)
11

the followin standards:
EN62040-1-1 (safety)
Condu ted Emission: EN50091-2..............................................................Class B
Radiated Emission: EN50091-2.................................................................Class B
Harmoni Current: EN61000-3-2
Voltage Flu tuations and Fli ker: EN61000-3-3
EMS: EN61000-4-2(ESD)...........................................................................Level 4
EN61000-4-3(RS) ......................................................................................Level 3
EN61000-4-4(EFT).....................................................................................Level 4
EN61000-4-5(lighting surge).......................................................................Level 4
EN61000-2-2 (Immunity to low frequen y signals)
12

9. Communication Port
9.1 RS232 Interface
The following is the pin assignment and des ription of DB-9 onne tor.
Pin # Des ription I/O
2 TXD Output
3 RXD Input
5 GND Input
9.2 AS400 Interface(Option)
Ex ept for the ommuni ation proto ol as mentioned above, this series UPS has AS400 ard (an optional
a essory) for AS400 ommuni ation proto ol . Please onta t your lo al distributor for details. The following is
the pin assignment and des ription of DB-9 onne tor in AS400 ard.
Pin # Description I/O
1 UPS Fail Output
2 Summary Alarm Output
3 GND Input
4 Remote
Shutdown
Input
5 Common Input
6 Bypass Output
7 Battery Low Output
8UPS ON Output
9 Line Loss Output
Figure 16.2: DB-9 Interfa e of AS400 ommuni ation
proto ol

10. Appendix 1The Correspondin Form of the LED Display for 1-3K
●: Solid ON ★ : Flash ↑ : LED display and alarm warning are dependent on other onditions.
No. state LED Display uzzer
25% 50% 75% 100
%
load bat line bps bat fault
1 Load
Capacity
0~25● ● ↑ ↑ ↑ No sound
2 26~50● ● ● ↑ ↑ ↑ No sound
3 51~75● ● ● ● ↑ ↑ ↑ No sound
4 76~100● ● ● ● ● ↑ ↑ ↑ No sound
5
6 attery
capacity
0~25● ● ↑ ↑ ↑ uzzing every 1sec
7 26~50● ● ● ↑ ↑ ↑ uzzing every 4sec
8 51~75● ● ● ● ↑ ↑ ↑ uzzing every 4sec
9 76~100● ● ● ● ● ↑ ↑ ↑ uzzing every 4sec
10
11 ypass Mode ● ↑ ↑ ↑ ↑ ↑ ● uzzing every 2min
12 Overload in line mode, change to
ypass ●●●● ★● ● uzzing
continuously
13 Overload in line mode, Not change
to bypass ●●●● ★●uzzing every
0.5sec
14 Line Fault ● ↑ ↑ ↑ ↑ ↑ ★↑ ↑ ↑
15 Overload in bat mode ●●●● ★●uzzing every
0.5sec
16 Overload in bat mode ★●uzzing
continuously
17 Over-temperature ● ↑ ● uzzing
continuously
18 Inverter abnormal ● ↑ ● uzzing
continuously
19 US voltage anomalies ● ↑ ● uzzing
continuously
20 Charging-V is too high ● ↑ ● uzzing
continuously
21 at-V abnormal ● ↑ ↑ ↑ ↑ ↑ ↑ ↑ ★↑
22 Line L and N changed ● ↑ ↑ ↑ ↑ ↑ ★uzzing every 2min
23 Charging oard or battery Fault ● ↑ ↑ ↑ ↑ ↑ ↑ ↑ ★●uzzing every 1sec
24 O/P short ● ● ● uzzing
continuously
25 Fan Fault ● ● ↑ ↑ ↑ ● uzzing every 1sec
This manual suits for next models
9
Table of contents
Other AEC UPS manuals