manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. AERMEC
  6. •
  7. Chiller
  8. •
  9. AERMEC FHX User manual

AERMEC FHX User manual

FHX
TECHNICAL MANUAL
IFHXTY
0809
4267320_00
ISO 9001 - Cert. n° 0128/4
Replace: 5266420_00 / 0705
FAN COIL WITH GERMICIDAL LAMP
UV
UVP
UVPO
FHX
3
English
4
5
6
7
8
9
10
11
15
16
22
23
24
25
26
27
29
30
39
40
40
41
42
43
43
45
DECLARATION OF CONFORMITY
Carriage • Safety symbol
Important information
Description • Versions
Main components• Component description
Selection
System configuration
Technical data
Operating limits
Delivery cooling capacity
Heating power input (3R)
Heating power input ( (4R)
Hanging version available static pressure
Battery pressure drop
Correction factors in functioning with glycoled water
Sound power and sound pressure
Sound power level for ducted wall/ceiling-mounting models
Accessories
Unit installation
Electrical connections
Replacing the lamps
Dip-Switch
Rotating the coil
Technical areas
Dimensions
Wiring diagram
INDEX
Store the manuals in a dry location to avoid deterioration, as
they must be kept for at least 10 years for any future reference.
All the information in this manual must be carefully read and
understood. Pay particular attention to the operating stan-
dards with “DANGER” or “WARNING” signals as failure to
comply with them can cause damage to the machine and/or
persons or objects.
If any malfunctions are not included in this manual, contact
the local After-sales Service immediately.
The apparatus must be installed in such a way that maintenan-
ce and/or repair operations are possible.
The apparatus's warranty does not in any case cover costs due
to automatic ladders, scaffolding or other lifting systems neces-
sary for carrying out repairs under guarantee.
Normal wear of components and filter is not covered by the
warranty.
AERMEC S.p.A. declines all responsibility for any damage
whatsoever
caused by improper use of the machine, and a partial or super-
ficial acquaintance with the information contained in this
manual.
The number of pages in this manual is: 48.
REMARKS
5
1
2
3
4
5
6
35Kg
NON bagnare • Do NOT wet
CRAINT l’humidité • Vor Nässe schützen
NO mojar
NON lasciare gli imballi sciolti durante il trasporto.
Do NOT leave loose packages during transport.
ATTACHER les emballages pendant le transport.
Die Verpackungen nicht ungesichert transportieren.
NO lleve las cajas sueltas durante el transporte.
Sovrapponibilità: controllare sull’imballo la posizione della freccia per
conoscere il numero di macchine impilabili.
Stacking: control the packing for the arrow position to know the num-
ber of machines that can be stacked.
Empilement: vérifier sur l’emballage la position de la flèche pour con-
naître le nombre d’appareils pouvant être empilés.
Stapelung: Anhand der Position des Pfeiles an der Verpackung kontrol-
lieren, wieviele Geräte stapelbar sind.
Apilamiento: observe en el embalaje la posición de la flecha para saber
cuántos equipos pueden apilarse.
NON calpestare • Do NOT trample
NE PAS marcher sur cet emballage • Nicht betreten
NO pisar
NON trasportare la macchina da soli se il suo peso supera i 35 Kg.
DO NOT handle the machine alone if its weight is over 35 Kg.
NE PAS transporter tout seul l’appareil si son poids dépasse 35 Kg.
Das Gerät NICHT alleine tragen, wenn sein Gewicht 35 Kg überschreitet.
NO maneje los equipos en solitario si pesan más de 35 kg.
Pericolo: Pericolo: Pericolo!!!
Tensione Organi in movimento
Danger: Danger: Danger!!!
Power supply Movings parts
Danger: Danger: Danger!!!
Tension Organes en mouvement
Gefahr ! Gefahr ! Gefahr!!!
Spannung Rotierende Teile
Peligro: Peligro: Peligro!!!
Tensión Elementos en movimiento
TRASPORTO • CARRIAGE • TRANSPORT • TRANSPORT • TRANSPORTE
SIMBOLI DI SICUREZZA • SAFETY SYMBOL • SIMBOLES DE SECURITE
SICHERHEITSSYMBOLE • SÍMBOLOS DE SEGURIDAD
6
English
The fan coils are shipped in standard packaging which consists of expanded polystyrene foam and cardboard shells.
PACKAGING
IMPORTANT INFORMATION AND MAINTENANCE
Consult the control panel manual for operating instructions.
USE
WARNING: the electrical wirings, the
installation of the fan coils and their
accessories, maintenance and the yearly
replacement of the germicidal lamps
must be performed only by a techni-
cian who has the necessary technical
and professional qualifications to install,
modify, extend and service the systems
and who is capable of assessing these
systems for the purposes of safety and
functionality.
WARNING: before carrying out any
work, wear the proper personal protec-
tive equipment.
WARNING: the fan coil is connected to
the power supply and a water circuit.
Any operation by persons who do not
possess the required technical skills can
lead to personal injury to the operator
or damage to the unit and surrounding
objects.
WARNING: The appliance must be fit-
ted according to the national regulation
on process plant engineering.
WARNING: Check that the power sup-
ply is disconnected before carrying out
any procedures on the unit.
WARNING: Install a device, main switch
or plug which makes it possible to com-
pletely cut off the power supply from
the unit.
DANGER! The UVC radiation emitted
by the germicidal lamp is dangerous
and may cause conjunctivitis, burns and
erythema.
It is absolutely prohibited to operate the
device with the germicidal lamp when it
has been removed from the fan coil.
It is absolutely prohibited to operate
the device with the germicidal lamp if
the fan coil has not been adequately
installed.
WARNING! DANGER! Any use of the
unit not expressly indicated by Aermec
is strictly prohibited.
MALFUNCTIONS
In the event of a malfunction, cut off
power supply to the unit, then restore
the power and start the unit again.
If the problem occurs again, contact
your After Sales Service department
immediately.
ONLY POWER THE FAN COIL AT
230 VAC 50 HZ
Any other type of power supply could
permanently damage the fan coil.
DO NOT USE THE FAN COIL IMPROP-
ERLY
Do not use the fan coil in animal hus-
bandry applications (e.g. incubation).
AIRING THE ROOM
Periodically air the room in which the
fan coil has been installed. This is partic-
ularly important if the room is occupied
by many people, or if gas appliances or
sources of odours are present.
DURING OPERATION
Always leave the filter fitted on the fan
coil during operation (otherwise dust in
the air could soil the coil surface area).
CORRECT TEMPERATURE ADJUST-
MENT
The room temperature should be regulat-
ed in order to provide maximum comfort
to the people in the room, especially if
they are elderly, children or ill; avoiding
temperature differences of more than 7°C
between outside and inside the room in
summer.
In summer, a temperature that is too low
causes higher electrical consumption.
CORRECT AIR JET AIMING ADJUST-
MENT
The air coming out of the fan coil must
not impact directly on people; in fact,
even if temperature is higher than the
room temperature, it could cause a cold
sensation resulting in discomfort.
DO NOT USE EXCESSIVELY HOT
WATER
Clean the fan coil with a soft cloth or
sponge soaked in water not over 40 °C.
Do not use chemical products or sol-
vents to clean any part of the fan coil.
Do not spray water on the outer or inner
surfaces of the fan coil (it might cause
short circuits).
CLEAN THE FILTER FREQUENTLY
Before performing any maintenance pro-
cedures requiring access to the internal
parts of the fan coil, cut off the power
supply in order to avoid being exposed
to the light emitted by the lamp.
Cleaning the filter frequently guarantees
enhanced operating efficiency.
Check whether the filter is very dirty: if it
is, clean it more often.
Clean frequently; remove the accumu-
lated dust with a vacuum cleaner.
Once the filter is clean, refit it to the fan
coil following the removal instructions
but in reverse order.
SUPPLEMENTARY CLEANING
Before performing any maintenance pro-
cedures requiring access to the internal
parts of the fan coil, cut off the power
supply in order to avoid being exposed
to the light emitted by the lamp.
The fact that the blades of inspectable
shrouds can be removed (operation done
only by adequately skilled technicians)
ensures a thorough cleaning of the inter-
nal components, which is particularly
important when installing the unit in
crowded areas or venues requiring high
hygiene standards.
WHAT IS NORMAL
In the cooling function, water vapour
may be present in the air delivery of the
fan coil.
In the heating function, a slight hiss
might be heard close to the fan coil.
Sometimes the fan coil might give off
unpleasant smells due to the accumula-
tion of substances present in the air of
the environment (clean the filter more
often especially if the room is not venti-
lated regularly).
During the operation, there could be
noises and creaks inside the device, due
to the various thermal expansions of the
elements (plastic and metallic), but this
does not indicate any malfunction and
does not damage the unit unless the
maximum input water temperature is
exceeded.
REPLACING THE LAMPS
This procedure may only be performed
by people with the necessary specific
technical skills.
Before performing any maintenance pro-
cedures requiring access to the internal
parts of the fan coil, cut off the power
supply in order to avoid being exposed
to the light emitted by the lamp.
Never let yourself come into direct con-
tact with the light produced by the lamp,
as the UVC radiation may cause serious
eye and skin irritation.
Lamps should be replaced every year
in order to ensure that the germicidal
action remains constant.
7
English
FHX - FAN COIL WITH GERMICIDAL LAMP
The FHX fan coil concentrates high technological and func-
tional characteristics that make it the ideal climate control unit
for all types of rooms. The supply of climate-controlled air is
immediate and distributed throughout the room. FHX gener-
ates heat if included in a heating system with boiler or heat
pump, but may also be used in summer as an air conditioner if
the heating system has a water chiller.
The FHX fan coil is fitted with an exclusive device featuring
a mercury-vapour germicidal lamp for air sterilisation, offer-
ing anti-microbiological action which is 99.999% effective in
combating all Gram - and Gram + microorganisms. The germi-
cidal lamp, positioned in the air delivery flow, cleans the coil
more thoroughly and prevents the formation of mould on the
surface of the fins, thereby ensuring the unit operates at its
maximum efficiency level in the long term, while reducing the
need for coil cleaning procedures.
The fact that the tray and the fan shrouds can be inspected
means you can carefully clean the internal parts as well.
These characteristics make the FHX unit indispensable in ven-
ues requiring high hygiene standards, such as:
• hospitals
• dentists' surgeries
• doctors' and vets' consulting rooms
• clynical analysis laboratories
• pharmaceutical companies
• waiting rooms
• beauty salons
• homes
• offices
• public premises
The new centrifugal fan unit is so quiet that at a normal oper-
ating speed you cannot hear when the FHX cuts in.
All models in the FHX range are supplied without a control
panel.
The PXAI and PXAE combinable control panels are supplied as
accessories; they activate the germicidal lamp operation as well
as the ventilation function, and are fitted with an electronic ther-
mostat which controls fan coil operation in order to maintain the
set temperature in the room. They also make electronic tempera-
ture adjustment and manual/automatic fan speed adjustment
possible, while the heating or cooling operating mode is selected
automatically (change of season) and depends on the temperature
of the water circulating inside the system.
The PXAI control panel may be fitted underneath the flap to the
right of the FHX_UV fan coil.
The PXAE control panel to be wall-mounted may be used com-
bined with all versions of the FHX range.
The fan coils in the FHX range are designed to satisfy all
system requirements, thanks to the wide range of accessories
available.
Full compliance with accident prevention regulations.
Congratulations on your purchase of this Aermec FHX fan coil.
Made with materials of superior quality in strict compliance with safety regulations, "FHX" is easy to use and will
have a long life.
VERSIONS
FHX_UV: with a 3-row coil, a
3-speed motor, universal cabinet for
vertical and horizontal installation
and anti-corrosive polyester powder
coated finish, RAL 9002. The air de-
livery and suction louvers are made
of plastic material, RAL 7044.
The control panel may be fitted on
board the unit (PXAI accessory) or
externally (PXAE accessory).
FHX_UVP: with 3- or 4-row
coils, version without casing, with
a 3-speed motor, for horizontal and
vertical wall installation, requires
external control panel (PXAE acces-
sory).
FHX_UVPO: with 3- or 4-row
coils, version without casing, with
a boosted motor set to operate at 7
speeds (3 of which may be selected),
for horizontal and vertical ceiling
installation, requires external con-
trol panel (PXAE accessory).
FHX UVP - UVPO
FHX 22 ÷ 50 UV FHX 62 - 82 UV
Available in 3 versions and 6 sizes with a 3-row coil and, only for ducted versions, in 6 sizes with a 4-row coil:
FHX 22 - 24
FHX 32 - 34
FHX 42 - 44
FHX 50 - 54
FHX 62 - 64
FHX 82 - 84
8
English
MAIN COMPONENTS
HEAT EXCHANGE COIL
Coil with copper pipe and alumini-
um fins held in place by means of the
mechanical expansion of the pipes. The
manifolds are fitted with female connec-
tions and air vents in the upper part of
the coil.
FILTRATION SECTION
Easily removable and made from regen-
erable materials. May be cleaned by
washing.
P and PO versions are equipped with G2
class filter.
CABINET
Casing in RAL9002
Air delivery and suction louvers in
RAL7044
Made from specially treated, polyester
powder-coated sheet metal to ensure
superior rust and corrosion resistance.
UV Version : at the upper part, there are
the louver (it is orientable and can be
closed again for sizes 22; 32; 42 and 50;
flat and fixed for sizes 62 and 82), made
from thermoplastic material to distribute
air, and the door to access the control
panel. With the orientable louver fully
closed, the tripping of the microswitch
stops ventilation, thus interrupting any
further heat exchange with the environ-
ment.
The casing also features a ther-
moplastic air recirculation louver at the
front.
ELECTRIC FAN ASSEMBLY
It consists of double suction radial fans
with lengthways blades to obtain a high
air flow with a low number of revs. The
electrical motor, protected against over-
loading, has three speeds with the run-
ning capacitor always on, directly cou-
pled with the fans and cushioned with
flexible supports. The FHX UVPO ver-
sion is equipped with a boosted motor
set to operate at 7 speeds (3 of which
may be selected).
BEARING STRUCTURE
Made of galvanised sheet metal of an
adequate thickness. Hole in the back
for wall mounting. A fan cover panel is
available for front-mounted ceiling units.
Each unit is equipped with a condensate
collection tray.
CONDENSATE DRAIN
Every device is fitted with a tray for col-
lecting condensation, with a connection
for draining condensation produced by
the unit in cooling mode.
PLUMBING CONNECTIONS
The connections, located on the left
hand side, are female. The coil may also
be rotated.
GERMICIDAL LAMP
Germicidal lamp that emits UVC rays.
This lamp has a one-year life span; after
that time, it should be replaced with a
similar lamp. The lamp serves to prevent
mould from forming in the fan coil, to
eliminate microbiological contamination
and to avoid its spread into the room.
The UVC radiation emitted by the lamp
destroys the main cellular DNA and
RNA.
The immediate effect is that cells cannot
reproduce and are killed; therefore, the
risk of airborne-transmitted infections is
reduced up to 90%.
Germicidal lamps emitting UVC rays
installed in the fan coils can prevent:
- TB conversions within healthcare facili-
ties.
- Legionnaire's disease.
- Microorganisms in the discharge cir-
cuits.
- Contaminated filters or overpressure.
- Spread of infections.
DESCRIPTION OF COMPONENTS
1Heat exchange coil
2Air filter
3Protective cabinet (RAL9002)
4Fan motor
5Fan
6Load-bearing structure
7Condensate drain
8Plumbing connections
9Head with orientable fins (RAL7044)
10Germicidal lamp
FHX 42 UV
1
9
8
7
6
5
4
3
2
10
9
English
SELECTION CRITERIA
Models with universal cabinet (UV) fea-
ture a front intake and can be mounted
either vertically on a wall or horizon-
tally on the ceiling.
Wall/ceiling-mounting (UVP and UVPO)
versions, without protective cabinet
and with intake at the bottom, can be
installed either vertically or horizontally.
In case of ducted installations where
pressure drops in the ducts are consid-
erable, the UVPO model (with boosted
multi-speed motors) enables to have the
effective pressure needed to guarantee a
correct air flow rate.
The UVP and UVPO models are avail-
able with 3- and 4-row coils.
The UV model has to be combined with
a control panel to be installed internally
or externally. Consult the characteristics
and compatibility of the control panels
supplied as accessories.
The UVP and UVPO models have to be
combined with a control panel to be
installed externally. Consult the charac-
teristics and compatibility of the control
panels supplied as accessories.
The control panels can control a net-
work of fan coils if they are used in
combination with the interface cards
SIT3 and SIT5 supplied as accessories.
The main technical data of the FHX
range are summarised in the tables.
The total and sensible cooling capacities
yielded at maximum speed according to
the temperature and thermal head of
the incoming water, the air temperature
with dry bulb or wet bulb for sensible
yield and total yield respectively for
models with a 3-row coil are shown
in the table. Performances at medium
and minimum speeds can be obtained
by multiplying the values in the table
by the correction factors indicated; for
4-row coil models, by multiplying the
values in the table by the correction fac-
tors indicated for each speed.
Pressure drops on the water side for 3-
and 4-row coils respectively are shown
in the graphs.
The correction factors when the unit
operates with glycol water for cooling
and heating function modes are shown
in the graphs in percentages of glycol of
10%, 20% and 35%.
The heating capacity yielded by the 3-
and 4-row coils according to the water
flow rate and the difference in tem-
perature between the incoming water
and the incoming air is represented in
a graph and it refers to the maximum
speed. Performances at medium and
minimum speeds can be obtained by
multiplying the values obtained from
the graph at maximum speed by the
correction factors indicated.
For the ducted wall/ceiling-mounting
models (UVP and UVPO), the perform-
ances described before must be con-
sidered as referring to air flow rates
equal to those corresponding to the
(UV) models at maximum speed (rated
capacities).
The pressure for the wall/ceiling-mount-
ing models according to the air flow
rate and the fan speed are shown as
a table; the curves show each speed.
For scaling the ducted wall/ceiling-
mounting models, it is advisable to pro-
ceed as follows: choose the size that
given a normal flow rate has a power
immediately above that required; after-
wards, mark out the curve of the duct
pressure drops on the rate-pressure dia-
gram related to the machine in ques-
tion in order to individualise the points
of machine operation at the different
speeds. Based on the capacity values
of these points, you will obtain the cor-
rection factors that help calculate the
capacity yielded given the actual condi-
tions of air flow rate. For multi-speed
models, this procedure helps to suitable
choose the speeds to be set.
The pressure and sound power levels
of fan coils at the different speeds are
shown in separated tables for 3- and
4-row coils models. For the ducted wall/
ceiling models, the sound power level
is expressed according to the air flow
rate and pressure, and represented as
graphs.
There is a wide range of accessories for
FHX fan coils, sometimes some of them
cannot be used at the same time; check
that the accessories are compatible with
the fan coil chosen. The manual shows
the description of each accessory plus a
drawing and its compatibility.
The installation information is includ-
ed in the manuals supplied together
with each fan coil or its accessory. This
manual is limited to provide general
information in order to obtain a correct
installation; it also contains drawings
with fan coil dimensions and the wiring
diagrams with the connections to con-
trol panels.
10
English
SW
AIR
SW
AIR
SW
AIR
SA
SA
230V 230V 230V
UVGI UVGI
SA
UVGI
VCF VCF
AIR AIR AIR
SA
SA
230V 230V 230V
UVGI UVGI
SA
UVGI
VCF VCF
SW Water temperature sensor
VCF Solenoid valve (Heating / Cooling) SA Room temperature sensor
V3,V2,V1 Maximum, Medium or Minimum fan speed
SYSTEM CONFIGURATIONS FOR FHX FAN COILS
System with 2 pipes, without water sensor
Key:
System with 2 pipes, with water sensor
11
English
TECHNICAL DATA
Performance values refer to the following conditions:
Sound pressure measured in semi-reverberating chamber, 85m3,
and with reverberation time Tr = 0.5s.
Cooling:
- room air temperature 27°C D.B., 19°C W.B.;
• maximum speed:
- water inlet temperature 7°C; ∆t water 5°C.
• medium and minimum speed:
- water inlet temperature 7°C;
- water flow rate as at maximum speed.
Heating:
room air temperature 20°C D.B.;
• maximum speed:
- water inlet temperature 70°C; ∆t water 10°C.
• medium and minimum speed:
- water inlet temperature 70°C;
- water flow rate as at maximum speed.
• maximum speed (water inlet 50°C):
- water inlet temperature 50°C;
- water flow rate as for cooling operation.
Mod.
Heating
W (max.)
Heating capacity W (med.)
W (min.)
Heating capacity * W(E)
(water inlet 50°C)
Water flow rate l/h
Water pressure drops kPa
Cooling
W (max.) (E)
Total cooling capacity W (med.)
W (min.)
W (max.) (E)
Sensible cooling capacity W (med.)
W (min.)
Water flow rate l/h
Water pressure drops kPa (E)
m
3/h (max.)
Air flow rate m3/h (med.)
m
3/h (min.)
Number of fans
dB (A) (max.)
Sound pressure dB (A) (med.)
dB (A) (min.)
dB (A) (max.) (E)
Sound power dB (A) (med.) (E)
dB (A) (min.) (E)
Water content l
Max. motor power W (E)
Max. input current A
3R Coil connections ø
1R Coil connections ø
FHX UV - UVP with a 3-row coil
Electrical power supply = 230V ~ 50Hz (E) = EUROVENT certified performances
FHX 22 FHX 32 FHX 42 FHX 50 FHX 62 FHX 82
3400 4975 7400 8620 12920 15140
2700 4085 6415 7530 10940 13350
1915 3380 5115 5420 8330 10770
2100 3160 4240 4900 6460 7990
292 427 636 741 1110 1300
6,3 14,2 14,1 14,2 14,8 19,8
1500 2210 3400 4190 4860 7420
1330 2055 2800 3640 4660 5500
1055 1570 2310 2840 3950 4710
1240 1750 2760 3000 3980 5680
1055 1540 2115 2750 3510 4250
755 1100 1635 2040 2825 3450
258 380 585 721 836 1276
5,8 16,6 14,3 19,3 11,6 13,5
290 450 600 720 920 1140
220 350 460 600 720 930
140 260 330 400 520 700
1 2 2 2 3 3
41,5 39,5 42,5 47,5 48,5 53,5
34,5 32,5 35,5 42,5 42,5 48,5
22,5 25,5 28,5 33,5 33,5 41,5
50 48 51 56 57 62
43 41 44 51 51 57
31 34 37 42 42 50
0,79 1,11 1,48 1,48 2,52 2,52
50 69 82 92 182 206
0,24 0,33 0,4 0,47 0,84 0,93
1/2” 1/2” 3/4” 3/4” 3/4” 3/4”
1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
12
English
TECHNICAL DATA
Mod.
Heating
W (max.)
Heating capacity W (med.)
W (min.)
Heating capacity * W(E)
(water inlet 50°C)
Water flow rate l/h
Water pressure drops kPa
Cooling
W (max.) (E)
Total cooling capacity W (med.)
W (min.)
W (max.) (E)
Sensible cooling capacity W (med.)
W (min.)
Water flow rate l/h
Water pressure drops kPa (E)
m
3/h (max.)
Air flow rate m3/h (med.)
m
3/h (min.)
Number of fans
dB (A) (max.)
Sound pressure dB (A) (med.)
dB (A) (min.)
dB (A) (max.) (E)
Sound power dB (A) (med.) (E)
dB (A) (min.) (E)
Water content l
Max. motor power W
Max. input current A
3R Coil connections ø
1R Coil connections ø
FHX UVPO with a 3-row coil
Electrical power supply = 230V ~ 50Hz (E) = EUROVENT certified performances
Performance values refer to the following conditions:
Sound pressure measured in semi-reverberating chamber, 85m3,
and with reverberation time Tr = 0.5s.
Cooling:
- room air temperature 27°C D.B., 19°C W.B.;
• maximum speed:
- water inlet temperature 7°C; ∆t water 5°C.
• medium and minimum speed:
- water inlet temperature 7°C;
- water flow rate as at maximum speed.
Heating:
room air temperature 20°C D.B.;
• maximum speed:
- water inlet temperature 70°C; ∆t water 10°C.
• medium and minimum speed:
- water inlet temperature 70°C;
- water flow rate as at maximum speed.
• maximum speed (water inlet 50°C):
- water inlet temperature 50°C;
- water flow rate as for cooling operation.
FHX 22 FHX 32 FHX 42 FHX 50 FHX 62 FHX 82
3400 4975 7400 8620 12920 15140
2700 4085 6415 7530 10940 13350
1915 3380 5115 5420 8330 10770
2100 3160 4240 4900 6460 7990
292 427 636 741 1110 1300
6,3 14,2 14,1 14,2 14,8 19,8
1500 2210 3400 4190 4860 7420
1330 2055 2800 3640 4660 5500
1055 1570 2310 2840 3950 4710
1240 1750 2760 3000 3980 5680
1055 1540 2115 2750 3510 4250
755 1100 1635 2040 2825 3450
258 380 585 721 836 1276
5,8 16,6 14,3 19,3 11,6 13,5
290 450 600 720 920 1140
220 350 460 600 720 930
140 260 330 400 520 700
1 2 2 2 3 3
41,5 39,5 42,5 47,5 48,5 53,5
34,5 32,5 35,5 42,5 42,5 48,5
22,5 25,5 28,5 33,5 33,5 41,5
50 48 51 56 57 62
43 41 44 51 51 57
31 34 37 42 42 50
0,79 1,11 1,48 1,48 2,52 2,52
79 122 136 107 197 235
0,37 0,57 0,63 0,48 0,92 1,06
1/2” 1/2” 3/4” 3/4” 3/4” 3/4”
1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
13
English
TECHNICAL DATA
Mod.
Heating
W (max.)
Heating capacity W (med.)
W (min.)
Heating capacity * W (E)
(water inlet 50°C)
Water flow rate l/h
Water pressure drops kPa
Cooling
W (max.) (E)
Total cooling capacity W (med.)
W (min.)
W (max.) (E)
Sensible cooling capacity W (med.)
W (min.)
Water flow rate l/h
Water pressure drops kPa (E)
m
3/h (max.)
Air flow rate m3/h (med.)
m
3/h (min.)
Number of fans
dB (A) (max.)
Sound pressure dB (A) (med.)
dB (A) (min.)
dB (A) (max.) (E)
Sound power dB (A) (med.) (E)
dB (A) (min.) (E)
Water content l
Max. motor power W (E)
Max. input current A
Coil connections 4R ø
FHX UVP with a 4-row coil
Electrical power supply = 230V ~ 50Hz (E) = EUROVENT certified performances
Performance values refer to the following conditions:
Sound pressure measured in semi-reverberating chamber, 85m3,
and with reverberation time Tr = 0.5s.
Cooling:
- room air temperature 27°C D.B., 19°C W.B.;
• maximum speed:
- water inlet temperature 7°C; ∆t water 5°C.
• medium and minimum speed:
- water inlet temperature 7°C;
- water flow rate as at maximum speed.
Heating:
room air temperature 20°C D.B.;
• maximum speed:
- water inlet temperature 70°C; ∆t water 10°C.
• medium and minimum speed:
- water inlet temperature 70°C;
- water flow rate as at maximum speed.
• maximum speed (water inlet 50°C):
- water inlet temperature 50°C;
- water flow rate as for cooling operation.
FHX 24 FHX 34 FHX 44 FHX 54 FHX 64 FHX 84
3950 5850 8600 10100 14300 17100
3200 4850 6930 8760 11500 14420
2200 3850 5200 6240 8500 11200
2320 3550 5250 6100 7810 10400
340 503 740 869 1230 1471
4 8 21 22 22 30
1730 2800 4450 4970 6350 8600
1500 2450 3780 4770 5520 7600
1150 2050 2970 3620 4500 6270
1380 2130 3300 3540 5030 5780
1140 1789 2722 3101 4195 5016
828 1441 2079 2281 3330 4013
297 482 765 855 1092 1479
3 9 19,2 25,9 13 22
290 450 600 720 920 1140
220 350 460 600 720 930
140 260 330 400 520 700
1 2 2 2 3 3
42,5 39,5 46,5 47,5 48,5 52,5
37,5 32,5 41,5 44,5 42,5 48,5
26,5 27,5 32,5 35,5 35,5 42,5
51 48 55 56 57 61
46 41 50 53 51 57
35 36 41 44 44 51
1 1,5 1,9 1,9 3,4 3,4
50 69 82 92 182 206
0,24 0,33 0,4 0,47 0,84 0,93
3/4” 3/4” 3/4” 3/4” 3/4” 3/4”
14
English
TECHNICAL DATA
Mod.
Heating
W (max.)
Heating capacity W (med.)
W (min.)
Heating capacity * W(E)
(water inlet 50°C)
Water flow rate l/h
Water pressure drops kPa
Cooling
W (max.) (E)
Total cooling capacity W (med.)
W (min.)
W (max.) (E)
Sensible cooling capacity W (med.)
W (min.)
Water flow rate l/h
Water pressure drops kPa (E)
m
3/h (max.)
Air flow rate m3/h (med.)
m
3/h (min.)
Number of fans
Sound pressure dB (A) (max.)
Sound pressure dB (A) (max.)
Water content l
Max. motor power W (E)
Max. input current A
Coil connections 4R ø
FHX UVPO with a 4-row coil
Electrical power supply = 230V ~ 50Hz (E) = EUROVENT certified performances
Performance values refer to the following conditions:
Sound pressure measured in semi-reverberating chamber, 85m3,
and with reverberation time Tr = 0.5s.
Cooling:
- room air temperature 27°C D.B., 19°C W.B.;
• maximum speed:
- water inlet temperature 7°C; ∆t water 5°C.
• medium and minimum speed:
- water inlet temperature 7°C;
- water flow rate as at maximum speed.
Heating:
room air temperature 20°C D.B.;
• maximum speed:
- water inlet temperature 70°C; ∆t water 10°C.
• medium and minimum speed:
- water inlet temperature 70°C;
- water flow rate as at maximum speed.
• maximum speed (water inlet 50°C):
- water inlet temperature 50°C;
- water flow rate as for cooling operation.
FHX 24 FHX 34 FHX 44 FHX 54 FHX 64 FHX 84
3950 5850 8600 10100 14300 17100
3200 4850 6930 8760 11500 14420
2200 3850 5200 6240 8500 11200
2320 3550 5250 6100 7810 10400
340 503 740 869 1230 1471
4 8 21 22 22 30
1730 2800 4450 4970 6350 8600
1500 2450 3780 4770 5520 7600
1150 2050 2970 3620 4500 6270
1380 2130 3300 3540 5030 5780
1140 1789 2722 3101 4195 5016
828 1441 2079 2281 3330 4013
297 482 765 855 1092 1479
3 9 19,2 25,9 13 22
290 450 600 720 920 1140
220 350 460 600 720 930
140 260 330 400 520 700
1 2 2 2 3 3
49,5 44 50 50,5 53,5 55,5
58 52,5 58,5 59 62 64
1 1,5 1,9 1,9 3,4 3,4
79 122 136 107 197 235
0,37 0,57 0,63 0,48 0,92 1,06
3/4” 3/4” 3/4” 3/4” 3/4” 3/4”
15
English
MINIMUM MEDIUM WATER TEMPERATURE Room air temperature with dry bulb °C
21 23 25 27 29 31
15 3 3 3 3 3 3
Temperature with wet bulb 17 3 3 3 3 3 3
of air in the room °C 19 3 3 3 3 3 3
21 6 5 4 3 3 3
23 - 8 7 6 5 5
Maximum water input temperature .......................... 80 °C
Maximum operating pressure..................................... 8 bar
Operating voltage ..............................230V(±10%) ~ 50Hz
Room temperature .................................................. 0-45°C
Humidity of the air ...........................................<85% U.R.
To avoid condensate forming on the external structure of
the unit while the fan is functioning, the medium water
temperature must not be lower than the limits shown in the
table below, that depend on the thermohygrometric condition
of the air in the room.
These limits refer to unit operating with fan at minimum speed.
In the case of a prolonged situation with the fan off and the
passage of cold water in the coil, condensation can form on
the outside of the unit, so it is recommended that a 3-way valve
accessory be fitted.
Output limits (3-row coil):
MODEL FHX 22 32 42 50 62 82
Minimum output [l/h] 100 100 150 150 300 300
Maximum output [l/h] 750 750 1100 1100 2200 2200
OPERATING LIMITS
Output limits (4-row coil):
MODEL FHX 24 34 44 54 64 84
Minimum output [l/h] 150 150 150 150 300 300
Maximum output [l/h] 1100 1100 1100 1100 2200 2200
Minimum medium water temperature
16
English
COOLING CAPACITY
FHX 22
TOTAL COOLING CAPACITY [W] SENSIBLE COOLING CAPACITY [W]
Air temperature - wet bulb [°C] Air temperature - dry bulb [°C]
Water temp.
Inlet [°C] ∆t 15 17 19 21 23 21 23 25 27 29 31
31238 1731 2254 – – 1065 1253 1434 1590 1743 1891
41110 1579 2090 2613 3163 973 1162 1350 1512 1669 1823
5 5 948 1372 1893 2440 3003 864 1048 1236 1430 1594 1751
6866 1167 1677 2250 2826 814 955 1124 1322 1511 1673
7– 1049 1436 2028 2631 768 907 1033 1207 1407 1591
31085 1555 2086 2613 – 980 1164 1352 1511 1667 1814
4963 1387 1917 2440 2994 875 1068 1252 1432 1591 1745
6 5 837 1198 1701 2258 2826 786 955 1143 1334 1514 1672
6779 1015 1478 2063 2640 742 882 1038 1229 1422 1594
7– 946 1247 1811 2436 698 840 969 1119 1314 1510
3948 1372 1893 2440 – 885 1066 1262 1432 1589 1736
4841 1207 1719 2258 2817 783 977 1165 1350 1513 1666
7 5 750 1033 1500 2072 2640 719 869 1056 1240 1432 1595
6707 908 1280 1841 2445 673 814 953 1139 1326 1513
7– 847 1107 1597 2232 627 766 905 1036 1223 1419
3837 1198 1701 2258 – 794 983 1164 1349 1508 1662
4748 1046 1512 2072 2631 701 891 1073 1260 1430 1590
8 5 683 901 1311 1862 2449 649 786 971 1149 1340 1514
6– 817 1119 1625 2245 603 742 882 1049 1235 1430
7– – 994 1390 1997 558 696 839 967 1129 1327
3750 1033 1527 2072 – 714 890 1079 1261 1429 1582
4671 907 1314 1878 2440 625 793 984 1166 1350 1511
9 5 616 783 1137 1640 2250 580 717 878 1061 1250 1434
6– 738 966 1420 2019 534 673 813 966 1147 1337
7– – 889 1198 1762 487 627 766 904 1047 1230
3683 901 1311 1862 2449 633 799 986 1163 1347 1505
4593 796 1134 1652 2241 554 711 897 1073 1260 1431
10 5 – 713 977 1433 2037 510 648 790 979 1159 1345
6– – 858 1222 1780 464 603 741 884 1062 1245
7– – – 1052 1542 415 558 696 840 968 1143
3– 782 1137 1640 2250 551 719 893 1078 1257 1424
4– 716 978 1433 2032 486 629 801 986 1167 1349
11 5 – 646 854 1238 1795 441 579 717 888 1067 1252
6– – 767 1061 1555 393 534 673 812 975 1151
7– – – 933 1329 342 487 627 764 904 1058
3– 713 977 1433 2037 467 638 804 988 1162 1343
4– 637 854 1247 1801 416 554 720 901 1075 1259
12 5 – – 753 1073 1564 370 510 648 799 985 1161
6– – 701 918 1350 322 464 603 741 889 1070
7– – – 840 1143 266 415 558 696 836 974
3– 646 854 1238 1795 392 556 723 896 1078 1253
4– – 762 1058 1561 346 485 638 809 989 1165
13 5 – – 678 921 1350 299 440 578 720 896 1070
6– – – 806 1155 246 393 534 671 812 983
7– – – – 988 181 342 487 627 764 902
NB: The yield values in bold type indicate the nominal value.
If sensible yield values are above the total output, this means that cooling is carried out without dehumidification. If this occurs,
take into consideration only the sensible yield values.
The cooling capacities yielded shown in the table must be multiplied by the following factors:
MODEL FHX 22 FHX 24
Maximum speed
total power
1.00 1.15
sensible power
1.00 1.11
Medium speed
total power
0.89 1.00
sensible power
0.85 0.92
Minimum speed
total power
0.70 0.77
sensible power
0.61 0.67
17
English
COOLING CAPACITY
FHX 32
The cooling capacities yielded shown in the table must be multiplied by the following factors:
MODEL FHX 32 FHX 34
Maximum speed
total power
1.00 1.17
sensible power
1.00 1.12
Medium speed
total power
0.86 1.02
sensible power
0.81 0.94
Minimum speed
total power
0.65 0.85
sensible power
0.58 0.76
TOTAL COOLING CAPACITY [W] SENSIBLE COOLING CAPACITY [W]
Air temperature - wet bulb [°C] Air temperature - dry bulb [°C]
Water temp.
Inlet [°C] ∆t 15 17 19 21 23 21 23 25 27 29 31
31303 1866 2512 3148 – 1134 1368 1612 1817 2004 2184
41618 2281 2921 – – 1351 1604 1851 2055 2253 2438
551415 2026 2728 3419 – 1231 1485 1750 1973 2176 2371
61231 1793 2502 3228 3968 1088 1360 1623 1881 2090 2292
71064 1556 2246 3010 3770 997 1222 1493 1753 2001 2210
31587 2241 – – – 1347 1593 1831 2029 2220 2409
41407 2013 2693 – – 1230 1477 1733 1954 2153 2340
651236 1780 2491 3189 3924 1103 1366 1623 1867 2076 2272
61056 1552 2219 2984 3732 974 1236 1494 1755 1989 2193
7960 1332 1964 2759 3528 906 1104 1368 1630 1895 2106
31363 1989 – – – 1219 1479 1726 1928 2120 2313
41205 1758 2456 3138 – 1095 1355 1604 1849 2054 2246
751069 1552 2210 2947 3681 987 1240 1488 1750 1973 2174
6939 1341 1956 2733 3489 878 1114 1377 1630 1884 2090
7871 1152 1705 2456 3272 817 997 1248 1501 1759 2004
31174 1723 2403 – – 1084 1349 1593 1827 2022 2212
41056 1523 2193 2895 – 990 1233 1476 1744 1950 2149
85942 1337 1938 2693 3438 878 1114 1372 1625 1868 2072
6841 1161 1710 2448 3228 785 990 1255 1501 1755 1989
7– 1012 1490 2170 2997 727 906 1120 1382 1636 1896
31042 1475 2162 – – 981 1221 1477 1722 1921 2115
4952 1320 1912 2649 – 881 1114 1357 1616 1848 2046
95843 1152 1688 2413 3182 764 1001 1248 1492 1752 1970
6– 1009 1472 2158 2959 695 881 1128 1386 1632 1882
7– 911 1275 1881 2693 635 817 1003 1263 1261 1771
3942 1264 1872 – – 875 1089 1348 1591 1819 2013
4847 1131 1653 2386 3112 774 997 1240 1491 1743 1948
10 5– 1014 1447 2113 2914 663 891 1134 1376 1624 1864
6– 900 1271 1864 2680 622 785 1008 1266 1513 1755
7– – 1104 1623 2378 542 727 906 1145 1389 1638
3839 1095 1600 2320 – 769 983 1224 1474 1716 1914
4– 1007 1420 2078 2851 661 891 1109 1359 1615 1844
11 5– 909 1258 1832 2636 574 778 1010 1254 1503 1749
6– – 1102 1618 2355 512 695 895 1148 1392 1634
7– – 963 1398 2078 448 635 817 1015 1274 1524
3– 992 1363 2035 – 661 880 1091 1349 1587 1813
4– 904 1212 1793 2579 546 783 1003 1242 1491 1737
12 5– – 1087 1583 2316 483 667 902 1141 1379 1622
6– – 971 1390 2030 419 605 788 1021 1274 1517
7– – – 1209 1789 347 542 727 911 1159 1405
3– 891 1172 1739 – 552 774 987 1210 1472 1709
4– – 1063 1534 2267 452 672 898 1114 1359 1610
13 5– – 971 1352 1995 391 574 792 1019 1260 1503
6– – – 1198 1754 321 512 695 911 1158 1394
7– – – 1042 1534 238 448 635 817 1033 1291
NB: The yield values in bold type indicate the nominal value.
If sensible yield values are above the total output, this means that cooling is carried out without dehumidification. If this occurs,
take into consideration only the sensible yield values.
18
English
COOLING CAPACITY
FHX 42
The cooling capacities yielded shown in the table must be multiplied by the following factors:
MODEL FHX 42 FHX 44
Maximum speed
total power
1.00 1.31
sensible power
1.00 1.20
Medium speed
total power
0.82 1.11
sensible power
0.77 0.99
Minimum speed
total power
0.68 0.87
sensible power
0.59 0.75
TOTAL COOLING CAPACITY [W] SENSIBLE COOLING CAPACITY [W]
Air temperature - wet bulb [°C] Air temperature - dry bulb [°C]
Water temp.
Inlet [°C] ∆t 15 17 19 21 23 21 23 25 27 29 31
32871 – – – – 2336 2730 3088 3401 3715 –
42491 3516 4551 – – 2149 2550 2942 3279 3602 3907
5 5 2156 3110 4241 5329 – 1920 2332 2752 3134 3468 3791
61808 2717 3825 5010 6191 1648 2113 2530 2955 3320 3653
71602 2278 3368 4635 5854 1544 1850 2298 2737 3155 3507
32491 3497 – – – 2131 2542 2918 3240 3552 –
42166 3103 4194 – – 1939 2349 2755 3112 3437 3749
6 5 1879 2730 3832 4963 6126 1706 2143 2554 2962 3303 3628
61563 2343 3426 4626 5816 1496 1908 2337 2754 3150 3489
71457 1924 2962 4204 5460 1402 1685 2094 2528 2951 3339
32146 3071 – – – 1929 2336 2730 3076 3393 3702
41882 2742 3825 4898 – 1740 2160 2553 2941 3275 3592
7 5 1621 2375 3400 4579 5751 1523 1944 2343 2760 3133 3465
61415 2014 2987 4223 5423 1355 1679 2138 2558 2960 3322
71321 1689 2556 3471 5048 1260 1544 1878 2338 2754 3163
31850 2704 3761 – – 1740 2136 2539 2909 3228 3540
41647 2382 3381 4523 – 1564 1948 2357 2754 3108 3429
8 5 1482 2040 3013 4185 5357 1334 1751 2160 2561 2958 3298
61279 1737 2601 3748 5010 1216 1507 1940 2353 2761 3151
7– 1518 2195 3297 4616 1118 1402 1695 2140 2559 2975
31644 2324 3342 – – 1571 1934 2334 2739 3064 3379
41482 2033 2987 4128 – 1388 1753 2166 2554 2936 3267
9 5 1266 1782 2588 3741 4954 1169 1557 1962 2369 2758 3131
6– 1515 2233 3297 4588 1074 1355 1733 2172 2565 2964
7– 1386 1859 2846 4109 976 1260 1540 1932 2362 2760
31482 1995 2936 – – 1398 1746 2135 2536 2899 3215
41312 1769 2581 3683 4869 1203 1581 1961 2357 2750 3100
10 5 – 1563 2246 3284 4532 1027 1368 1772 2169 2560 2956
6– 1350 1924 2846 4109 932 1214 1534 1977 2380 2762
7– – 1615 2446 3619 831 1118 1402 1718 2169 2573
31320 1727 2517 3625 – 1224 1577 1938 2333 2732 3052
4– 1579 2195 3245 4448 1010 1405 1767 2168 2547 2929
11 5 – 1392 1927 2852 4083 885 1179 1584 1990 2373 2757
6– – 1647 2465 3613 788 1074 1361 1770 2186 2570
7– – 1450 2098 3155 684 976 1260 1547 1966 2373
3– 1566 2149 3149 – 1047 1407 1753 2136 2529 2883
4– 1412 1901 2800 4012 841 1226 1598 1984 2356 2741
12 5 – – 1669 2433 3580 744 1027 1402 1794 2177 2561
6– – 1466 2117 3142 642 932 1213 1574 1999 2385
7– – – 1789 2710 529 831 1118 1402 1768 2189
3– 1405 1850 2730 – 863 1233 1584 1945 2329 2717
4– – 1669 2375 3535 698 1037 1422 1780 2172 2545
13 5 – – 1502 2104 3103 600 885 1206 1604 2003 2374
6– – – 1824 2691 491 788 1072 1382 1808 2195
7– – – 1544 2317 359 684 976 1260 1564 2004
NB: The yield values in bold type indicate the nominal value.
If sensible yield values are above the total output, this means that cooling is carried out without dehumidification. If this occurs,
take into consideration only the sensible yield values.
19
English
COOLING CAPACITY
FHX 50
The cooling capacities yielded shown in the table must be multiplied by the following factors:
MODEL FHX 50 FHX54
Maximum speed
total power
1.00 1.26
sensible power
1.00 1.18
Medium speed
total power
0.87 1.14
sensible power
0.92 1.03
Minimum speed
total power
0.68 0.86
sensible power
0.68 0.76
TOTAL COOLING CAPACITY [W] SENSIBLE COOLING CAPACITY [W]
Air temperature - wet bulb [°C] Air temperature - dry bulb [°C]
Water temp.
Inlet [°C] ∆t 15 17 19 21 23 21 23 25 27 29 31
33542 – – – – 2624 2952 3296 3632 – –
43227 4260 5468 – – 2461 2810 3145 3500 3836 4164
552912 3892 5083 6406 – 2284 2643 2999 3343 3704 4039
62588 3516 4663 6011 7451 2064 2467 2831 3185 3545 3896
72246 3130 4234 5565 7043 1755 2251 2646 3015 3369 3740
33170 – – – – 2448 2788 3113 3458 3791 –
42885 3848 5031 – – 2290 2642 2980 3326 3663 3989
652605 3498 4628 5960 – 2096 2470 2829 3168 3523 3861
62307 3139 4225 5539 6979 1848 2290 2656 3013 3356 3720
71983 2789 3813 5083 6546 1537 2053 2471 2841 3194 3556
32833 3778 – – – 2278 2623 2941 3280 3619 –
42579 3454 4575 – – 2105 2472 2809 3139 3486 3819
752329 3130 4190 5486 – 1892 2301 2657 3000 3343 3690
62062 2806 3796 5039 6495 1618 2104 2483 2838 3182 3541
71721 2474 3402 4593 6037 1355 1827 2292 2670 3020 3370
32535 3376 – – – 2090 2448 2786 3096 3443 3772
42325 3078 4129 5390 – 1900 2298 2642 2975 3307 3647
852075 2789 3791 4996 6406 1675 2119 2483 2829 3165 3516
61817 2496 3393 4558 5986 1367 1892 2308 2666 3006 3357
7– 2189 3034 4137 5503 – 1581 2102 2496 2854 3195
32299 3008 4024 – – 1884 2282 2612 2931 3262 3598
42097 2745 3700 4908 – 1690 2122 2478 2808 3129 3468
951861 2491 3358 4505 5909 1448 1917 2318 2659 2994 3329
6– 2229 3017 4094 5468 1147 1666 2127 2502 2845 3172
7– 1940 2693 3700 4987 – 1367 1884 2320 2683 3024
32075 2675 3603 – – 1678 2093 2449 2775 3079 3421
41874 2456 3279 4435 – 1476 1917 2308 2644 2967 3291
10 5– 2237 2982 4032 5398 1210 1702 2138 2492 2828 3141
6– 1992 2684 3665 4926 – 1428 1929 2331 2675 3005
7– – 2386 3279 4479 – – 1650 2137 2515 2853
31852 2412 3192 – – 1469 1892 2288 2606 2916 3240
4– 2224 2920 3962 5267 1255 1706 2134 2478 2803 3111
11 5– 2010 2653 3603 4847 951 1481 1941 2332 2662 2979
6– – 2395 3253 4418 – 1174 1706 2154 2513 2836
7 – – 2123 2912 3997 – v 1400 1932 2342 2693
3– 2193 2833 3831 – 1258 1687 2102 2448 2762 3061
4– 2001 2605 3507 4733 1025 1493 1929 2316 2641 2955
12 5– – 2377 3192 4339 – 1251 1727 2157 2500 2823
6– – 2150 2885 3927 – – 1476 1957 2344 2679
7– – – 2579 3551 – – – 1706 2170 2527
6– 1970 2531 3398 – 1045 1481 1896 2288 2612 2897
4– – 2351 3113 4243 765 1275 1718 2146 2480 2797
13 5– – 2150 2833 3848 – 992 1509 1957 2343 2660
6– – – 2561 3489 – – 1222 1739 2175 2516
7– – – 2299 3139 – – – 1457 1972 2365
NB: The yield values in bold type indicate the nominal value.
If sensible yield values are above the total output, this means that cooling is carried out without dehumidification. If this occurs,
take into consideration only the sensible yield values.
20
English
COOLING CAPACITY
FHX 62
TOTAL COOLING CAPACITY [W] SENSIBLE COOLING CAPACITY [W]
Air temperature - wet bulb [°C] Air temperature - dry bulb [°C]
Water temp.
Inlet [°C] ∆t 15 17 19 21 23 21 23 25 27 29 31
34190 5511 6974 – – 3490 3981 4464 4949 5415 5861
43725 5018 6500 8084 – 3214 3725 4222 4720 5208 5681
5 5 3185 4460 5949 7583 9315 2836 3424 3955 4465 4977 5465
62739 3818 5335 7015 8801 2611 3030 3637 4184 4717 5231
72586 3241 4609 6365 8205 2460 2867 3249 3848 4419 4963
33734 5009 6460 – – 3253 3735 4210 4701 5175 5620
43302 4506 5967 7556 9248 2970 3482 3982 4468 4964 5441
6 5 2804 3967 5409 7041 8774 2558 3171 3710 4219 4727 5224
62501 3325 4776 6446 8233 2387 2818 3372 3934 4465 4986
72358 2953 4050 5762 7624 2236 2975 3053 3581 4167 4714
33316 4498 5930 – – 3017 3499 3977 4456 4934 5388
42924 4023 5418 7015 8706 2704 3240 3738 4227 4721 5200
7 5 2478 3501 4860 6474 8205 2314 2909 3463 3980 4471 4977
62287 2907 4237 5847 7651 2163 2606 3102 3685 4213 4733
7– 2693 3492 5149 6988 2012 2460 2869 3304 3913 4453
32943 4004 5391 6946 – 2757 3262 3728 4205 4691 5155
42618 3567 4869 6446 8151 2411 3001 3499 3985 4471 4960
8 5 2394 3083 4330 5874 7637 2089 2616 3216 3729 4233 4731
62073 2618 3725 5251 7028 1938 2387 2836 3431 2967 4482
7– 2460 3111 4553 6338 1783 2236 2671 3066 3648 4203
32655 3544 4833 6392 – 2480 3031 3502 3965 4448 4915
42339 3149 4349 5855 7569 2099 2742 3266 3742 4226 4714
9 5 2004 2720 3827 5279 7028 1865 2323 2967 3489 3982 4474
6– 2390 3251 4665 6392 1714 2163 2906 3170 3717 4227
7– – 2813 3976 5688 1558 2012 2455 2867 3382 3955
32394 3135 4302 5800 – 2202 2777 3269 3735 4198 4675
42050 2800 3836 5260 6974 1797 2455 3029 3508 3980 4462
10 5 – 2418 3363 4702 6392 1641 2089 2694 3252 3742 3982
6– 2176 2822 4107 5744 1485 1938 2382 2897 3472 3982
7– – 2567 3437 5056 1327 1783 2231 2973 3107 3697
32125 2800 3790 5204 6866 1914 2498 3043 3506 3957 4433
4– 2520 3380 4693 6352 1598 2158 2777 3278 3746 4208
11 5 – 2125 2962 4153 5744 1417 1865 2382 3005 3514 3986
6– – 2515 3595 5111 1258 1714 2158 2626 3229 3746
7– – 2348 2981 4441 1091 1558 2007 2455 2880 3447
3– 2539 3334 4618 6257 1612 2221 2786 3273 3727 4182
4– 2246 2990 4135 5698 1344 1836 2494 3049 3520 3978
12 5 – – 2627 3651 5111 1190 1641 2094 2753 3281 3753
6– – 2278 3139 4506 1027 1485 1936 2382 2972 3504
7– – – 2683 3864 845 1327 1783 2231 2674 3188
3– 2278 2957 4064 5614 1283 1938 2513 3050 3504 3944
4– – 2683 3632 5064 1116 1566 2202 2806 3293 3744
13 5 – – 2344 3204 4506 959 1415 1860 2451 3044 3522
6– – – 2748 3939 813 1258 1711 2158 2681 3268
7– – – 2451 3344 575 1091 1558 2007 2455 2921
NB: The yield values in bold type indicate the nominal value.
If sensible yield values are above the total output, this means that cooling is carried out without dehumidification. If this occurs,
take into consideration only the sensible yield values.
The cooling capacities yielded shown in the table must be multiplied by the following factors:
MODEL FHX 62 FHX 64
Maximum speed
total power
1.00 1.31
sensible power
1.00 1.19
Medium speed
total power
0.96 1.14
sensible power
0.83 0.99
Minimum speed
total power
0.81 0.93
sensible power
0.67 0.79
21
English
COOLING CAPACITY
FHX 82
The cooling capacities yielded shown in the table must be multiplied by the following factors:
MODEL FHX 82 FHX 84
Maximum speed
total power
1.00 1.24
sensible power
1.00 1.06
Medium speed
total power
0.80 1.10
sensible power
0.85 1.00
Minimum speed
total power
0.68 0.91
sensible power
0.69 0.80
TOTAL COOLING CAPACITY [W] SENSIBLE COOLING CAPACITY [W]
Air temperature - wet bulb [°C] Air temperature - dry bulb [°C]
Water temp.
Inlet [°C] ∆t 15 17 19 21 23 21 23 25 27 29 31
35591 7373 – – – 4995 5671 6366 7036 7680 8303
44979 6701 8676 10810 0 4612 5326 6023 6722 7409 8055
5 5 4320 5975 7952 10144 12453 4127 4927 5664 6367 7082 7760
63553 5167 7131 9381 11749 3569 4400 5232 5983 6715 7440
73291 4225 6243 8503 10985 3346 3939 4689 5556 6331 7069
34979 6688 – – – 4656 5338 6008 6699 7344 7987
44427 6014 7965 10106 – 4262 4990 5672 6373 7073 7735
6 5 3815 5315 7212 9401 11729 3710 4576 5313 6019 6732 7428
63217 4549 6405 8597 10985 3248 3978 4879 5643 6357 7085
73008 3782 5517 7696 10164 3032 3658 4291 5193 5969 6718
34427 6002 7925 – – 4318 4996 5669 6354 7018 7657
43930 5369 7218 9361 – 3890 4652 5337 6011 6723 7401
7 5 3392 4710 7420 8638 10966 3256 4211 4972 5680 6381 7084
62927 3984 5705 7803 10203 2934 3591 4504 5290 6015 6742
72725 3432 4817 6902 9342 2718 3346 3953 4818 5619 6367
33949 5342 7185 – – 3950 4670 5337 5999 6679 7324
43526 4763 6486 8611 10887 3480 4310 5009 5681 6364 7056
8 5 3210 4159 5773 7830 10183 2852 3815 4624 5337 6022 6740
62645 3473 5033 6997 9381 2621 3248 4115 4938 5668 6380
7– 3143 4172 6136 8477 2405 3032 3651 4427 5263 6006
33566 4724 6432 – – 3555 4340 5002 5654 6329 6978
43156 4219 5786 7803 10106 3054 3942 4671 5347 6008 6711
9 5 2585 3687 5113 7024 9361 2532 3375 4275 4996 5688 6375
6– 3096 4414 6230 8503 2308 2934 3674 4588 5320 6032
7– 2861 3648 5382 7589 2083 2718 3346 4008 4898 5660
33210 4192 5719 7723 – 3151 3971 4678 5336 5978 6644
42773 3762 5113 6997 9283 2599 3539 4340 5017 5686 6356
10 5 – 3291 4508 6270 8503 2219 2905 3898 4668 5357 6034
6– 2780 3875 5503 7642 1995 2621 3271 4219 4984 5694
7– – 3284 4697 6754 1770 2405 3032 3666 4538 5315
32847 3755 5046 6916 – 2741 3576 4355 4997 5647 6300
4 – 3392 4522 6230 8450 2136 3114 3986 4692 5357 6000
11 5 – 2894 3984 5530 7628 1905 2532 3472 4329 5026 5694
6– – 3405 4831 6808 1679 2308 2934 3808 4650 5351
7– – 2995 4077 5948 1442 2088 2718 3346 4132 4968
3– 3405 4448 6136 – 2323 3181 3994 4679 5326 5953
4– 3015 4003 5503 7562 1811 2681 3584 4370 5026 5671
12 5 – – 3553 4871 6781 1589 2219 3017 3971 4704 5369
6– – 2988 4239 6002 1358 1995 2621 3346 4297 5026
7– – – 3539 5194 1103 1770 2405 3032 3718 4617
3– 3049 3957 5402 7440 1868 2774 3599 4365 4995 5622
4– – 3600 4831 6727 1495 2196 3166 4024 4713 5348
13 5 – – 3176 4293 5988 1270 1905 2554 3547 4372 5038
6– – – 3728 5275 1025 1679 2308 2949 3915 4691
7– – – 3156 4535 732 1444 2088 2718 3346 4254
NB: The yield values in bold type indicate the nominal value.
If sensible yield values are above the total output, this means that cooling is carried out without dehumidification. If this occurs,
take into consideration only the sensible yield values.

This manual suits for next models

3

Other AERMEC Chiller manuals

AERMEC FCX Manual

AERMEC

AERMEC FCX Manual

AERMEC NRL FC 800 User manual

AERMEC

AERMEC NRL FC 800 User manual

AERMEC SAF User manual

AERMEC

AERMEC SAF User manual

AERMEC NXP 0500 User manual

AERMEC

AERMEC NXP 0500 User manual

AERMEC AN R407C Installation and operation manual

AERMEC

AERMEC AN R407C Installation and operation manual

AERMEC FCS 22 User manual

AERMEC

AERMEC FCS 22 User manual

AERMEC NRL FC 028 Manual

AERMEC

AERMEC NRL FC 028 Manual

AERMEC NRA Installation and operation manual

AERMEC

AERMEC NRA Installation and operation manual

AERMEC NRA F 275 A Installation and operation manual

AERMEC

AERMEC NRA F 275 A Installation and operation manual

AERMEC NRB Series Manual

AERMEC

AERMEC NRB Series Manual

AERMEC NXP 0500 Manual

AERMEC

AERMEC NXP 0500 Manual

AERMEC NRL F Series User manual

AERMEC

AERMEC NRL F Series User manual

AERMEC ANL User manual

AERMEC

AERMEC ANL User manual

AERMEC ZX Series User manual

AERMEC

AERMEC ZX Series User manual

AERMEC nrl R410A Instruction Manual

AERMEC

AERMEC nrl R410A Instruction Manual

AERMEC NBW Series Installation and operation manual

AERMEC

AERMEC NBW Series Installation and operation manual

AERMEC NRV 0550 Manual

AERMEC

AERMEC NRV 0550 Manual

AERMEC NRB 0800-3600 User manual

AERMEC

AERMEC NRB 0800-3600 User manual

AERMEC NRL 0280 User manual

AERMEC

AERMEC NRL 0280 User manual

AERMEC ANL 020 User manual

AERMEC

AERMEC ANL 020 User manual

AERMEC NRW Series Installation and operation manual

AERMEC

AERMEC NRW Series Installation and operation manual

AERMEC AN Installation and operation manual

AERMEC

AERMEC AN Installation and operation manual

AERMEC Turbocor User manual

AERMEC

AERMEC Turbocor User manual

AERMEC NRB 0800 Manual

AERMEC

AERMEC NRB 0800 Manual

Popular Chiller manuals by other brands

NANO Precision NPC 015 Service manual

NANO

NANO Precision NPC 015 Service manual

Skope ActiveCore TME-N Series Service manual

Skope

Skope ActiveCore TME-N Series Service manual

Daikin EWAP800AJYNN Installation, operation and maintenance manual

Daikin

Daikin EWAP800AJYNN Installation, operation and maintenance manual

Crysalli CP-JR-CT1SW install guide

Crysalli

Crysalli CP-JR-CT1SW install guide

Galletti ACQVARIA i AQB0 Technical manual

Galletti

Galletti ACQVARIA i AQB0 Technical manual

Johnson Controls SABROE ChillPAC operating manual

Johnson Controls

Johnson Controls SABROE ChillPAC operating manual

Carrier Model F-30HR Installation, Start-Up and Service Instructions

Carrier

Carrier Model F-30HR Installation, Start-Up and Service Instructions

Randell BC-3 Operator's manual

Randell

Randell BC-3 Operator's manual

SMC Networks HRL100-A*-20 Series Operation manual

SMC Networks

SMC Networks HRL100-A*-20 Series Operation manual

omran tahvieh OALC 010 manual

omran tahvieh

omran tahvieh OALC 010 manual

SMC Networks HRZD020-WS-WS Operation manual

SMC Networks

SMC Networks HRZD020-WS-WS Operation manual

CLIVET WSH Series Installation, use and maintenance manual

CLIVET

CLIVET WSH Series Installation, use and maintenance manual

MAXA i-32V5H MIDI 0121 Technical bulletin

MAXA

MAXA i-32V5H MIDI 0121 Technical bulletin

ATS Chill V Series Instructional manual

ATS

ATS Chill V Series Instructional manual

Carrier CRECOMZR076A00 installation instructions

Carrier

Carrier CRECOMZR076A00 installation instructions

Hitecsa ADVANCE EQUI-PF 117 Installation, user and maintenance manual

Hitecsa

Hitecsa ADVANCE EQUI-PF 117 Installation, user and maintenance manual

Trane JDAC Series Engineering Data Manual

Trane

Trane JDAC Series Engineering Data Manual

Acson international IOM-A5PADW-2101 Operation manual

Acson international

Acson international IOM-A5PADW-2101 Operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.