AGD 641
PEDESTRIAN DETECTOR
AGD 641
PEDESTRIAN DETECTOR
POWER UP SEQUENCE
Aer applying power to the unit, the front red LED will permanently illuminate for approximately 30 secs while
the operating system loads. The LED will then start flashing and either extinguish if the detector has been
previously set-up and revert to normal operation (illuminated if zone is in detect, not illuminated if zone is
empty), or the LED will continue to flash until the unit has been set-up and commissioned.
OPTO-COUPLER RATINGS FOR ALL
VOLTAGE VERSIONS
• Max current 60mA
• Max Voltage 100V
• Max on-state impedance 25 Ohms
ELECTRICAL INSTALLATION
The detector is powered using a 12-24V ac/dc (±20%) or 230Vac supply. For the
non mains units the power is applied to the detector using the multi-pin mating
connector.
The AGD641 Pedestrian Detector is provided with a Buccaneer Series PX0728/S 9
pole connector to enable direct connection to the traic control system. The pin
outs of the connector and detector function are highlighted in the table below:
CONNECTIONS FOR 12V-24V ac/dc VERSIONS
CONNECTIONS FOR 230Vac VERSION
Installation and Commissioning
Pin
No.
Wire
Colour
Function Power
O
Power On-
No Detect
Power
On- Detect
1 RED 12-24V ac/dc - - - -
2 BLACK 0V ac/dc - - - -
3 GREEN Earth/Ground - - - -
4 WHITE Opto 1/2 Common - - - -
5 YELLOW Opto 1 N/O N/O N/C N/O -
6 BLUE Opto 1 N/C N/C N/O N/C Not for use on Puins/Toucans
7 - - - - - -
8 BROWN Not Connected - - - -
9 VIOLET Not Connected - - - -
Power supply
ratings
12Vac 24Vdc 24Vac 230Vac
Day time mode - - 170mA 17mA
Night time mode 300mA 140mA 200/255mA 24/30mA
Twin Cable 230Vac Supply Wiring (5m flying leads)
Cable Wire Colour Function Power O Power On - No Detect Power On –Detect
Power Brown 230Vac Live - - -
Blue 230Vac Neutral - - -
Signal Red Opto Common - - -
Blue Opto Contact N/C N/O N/C
Green Opto Contact N/O N/C N/O