General Precautions Class 1 LED Product
Step 1 Read General Information
!
ATTENTION: Hazard of permanent eye damage exists when using optical transmission
equipment. This product emits intense light and invisible radiation. Do not look into module ports or
fiber optic cable connectors.
!
ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and assemblies.
Static control precautions are required when installing, testing, servicing or repairing this assembly.
Component damage may result if ESD control procedures are not followed. If you are not familiar
with static control procedures, reference Allen-Bradley publication 8000-4.5.2, “Guarding Against
Electrostatic Damage” or any other applicable ESD protection handbook.
!
ATTENTION: An incorrectly applied or installed drive can result in component damage or a
reduction in product life. Wiring or application errors such as under sizing the motor, incorrect or
inadequate AC supply, or excessive surrounding air temperatures may result in malfunction of the
system.
!
ATTENTION: Only qualified personnel familiar with the PowerFlex 700S Drive and associated
machinery should plan or implement the installation, start-up and subsequent maintenance of the
system. Failure to comply may result in personal injury and/or equipment damage.
!
ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus capacitors has
discharged before performing any work on the drive. Measure the DC bus voltage at the +DC & –
DC terminals of the Power Terminal Block (refer to Chapter 1 in the PowerFlex 700S User Manual,
publication 20D-UM001, for location). The voltage must be zero.
!
ATTENTION: Risk of injury or equipment damage exists. DPI or SCANport host products must
not be directly connected together via 1202 cables. Unpredictable behavior can result if two or more
devices are connected in this manner.
!
ATTENTION: Risk of injury or equipment damage exists. Parameters 365 [Encdr0 Loss Cnfg] -
394 [VoltFdbkLossCnfg] let you determine the action of the drive in response to operating
anomalies. Precautions should be taken to ensure that the settings of these parameters do not create
hazards of injury or equipment damage
!
ATTENTION: Risk of injury or equipment damage exists. Parameters 383 [SL CommLoss Data] -
392 [NetLoss DPI Cnfg] let you determine the action of the drive if communications are disrupted.
You can set these parameters so the drive continues to run. Precautions should be taken to ensure the
settings of these parameters do not create hazards of injury or equipment damage.