MAINTENANCE
Before starting any maintenance work, isolate and disable the system in order to avoid accidental and unwanted alarm or fault condi-
tions.
Remove the detector from its mounting base to allow inspection in good light at ground level.
Inspect the thermistor area and use a small, soft bristle brush to dislodge any evident contaminants such as insects, spider webs,
hairs, etc. Use a small vacuum tube or clean, dry and compressed air to suck up or blow away any remaining small particles from the
thermistor area. Wipe the exterior housing of the detector with a clean, damp, lint free cloth to remove any surface film that can later
attract airborne contaminants.
After all detectors have been inspected, repositioned on their mounting bases and power has been re-applied, check correct opera-
tion by testing the device.
TECHNICAL SPECIFICATIONS **
* Product operates down to 15 V, but without LED indication.
** Further technical data: see document TDS-A350L held by the manufacturer.
WARNINGS AND LIMITATIONS
Our devices use high quality electronic components and plastic materials that are highly re-
sistant to environmental deterioration. However, after 10 years of continuous operation, it is
advisable to replace the devices in order to minimize the risk of reduced performance caused by
external factors. Ensure that this device is only used with compatible control panels. Detection
systems must be checked, serviced and maintained on a regular basis to confirm correct opera-
tion.
Smoke detectors may respond differently to various kinds of smoke particles, thus application
advice should be sought for special risks. Detectors cannot respond correctly if barriers exist
between them and the fire location and may be affected by special environmental conditions.
Refer to and follow national codes of practice and other internationally recognized fire engineer-
ing standards. Appropriate risk assessment should be carried out initially to determine correct
design criteria and updated periodically.
WARRANTY
All devices are supplied with the benefit of a limited 5 years warranty relating to faulty materials
or manufacturing defects, effective from the production date indicated on each product.
This warranty is invalidated by mechanical or electrical damage caused in the field by incorrect
handling or usage. Product must be returned via your authorized supplier for repair or replace-
ment together with full information on any problem identified.
Full details on our warranty and product’s returns policy can be obtained upon request.
ARGUS SECURITY S.R.L.
Via del Canneto, 14
34015 Muggia (TS)
Italy
EN 54-5:2017+ A1:2018
A3500L
For use in compatible fire detection and
alarm system.
Category A1R and BS (category P)
Power supply *from 18 V (min) to 40 V (max)
Average standby current consumption 45 uA @ 24 V
Remote output max current consumption (externally limited) 20 mA
Compatible adaptor bases LAB1000 - “Low Profile Adaptor Base”
Thermal alarm threshold (ROR A1R category) 58 °C
Thermal alarm threshold (BS category) 78 °C
Operating temperature range -30 °C / +70 °C (no icing)
Humidity 95% RH (no condensation)
ANTI -TAMPER DETECTOR LOCK
The detector can be locked to its base as a deterrent to intentional removal performed by non authorized personnel.
Using a cutter, remove the anti-tamper plastic detail, as illustrated in figure 6.
To unlock the detector, insert the tip of a screwdriver into the side slot of the base by exerting only a light pressure (figure 7), and
release the detector by turning it anticlockwise.
.
LED INDICATORS
This detector is equipped with two red LEDs; their flash pattern indicate the present condition of the
detector itself:
Blinking: indicates the normal operative status of the detector; the performance of this pattern
depends upon the control panel’s model and its settings.
Continuous: indicates an alarmed condition of the detector.
Fault conditions are not indicated by LEDs, but only on the control panel.
Positioning of these LEDs is illustrated in figure 8.
IDENTIFICATION TAB
The adaptor base is equipped with a plastic tab where identification data can be visibly displayed.
Detach the tab from the base; write or label it with the required information, then insert it into its adaptor base’s slot.
TESTING THE DETECTORS - PRELIMINARY NOTE
Detectors should be tested after installation and during periodic maintenance visits; it is recommended each device should be tested
at least once per year.
After each test reset the system and allow at least one minute for power stabilisation.
HEAT TEST
Use a hair dryer of 1000-1500 W or an heat tool from an approved manufacturer. Direct the heat towards the detector from its side.
Hold the heat source at about 15 cm away from the detector in order to prevent damage to its cover during testing.
The detector should trigger an alarm message to the control panel, and, successively, the detector’s red LED should be activated by
the control panel itself.