GENERAL DESCRIPTION
The TW-DT-01/BL Taurus series detector samples the environmental temperature in the protected area; when the environmental temperature
level or variation rate exceeds a certain degree, a fire alarm message is sent to the control panel.
TW-DT-01/BL is battery powered and doesn’t need any system cabling installation.
LOCATION SELECTION
Select a location for the detector that conforms to your local applicable safety standards and that is in a good position for sending / receiving
wireless signals to / from the father TW-MTI-01, TW-MEC-01 or TW-ME-01 network device.
Mount the detector as far as possible from metal objects, metal doors, metal window openings, etc. as well as cable conductors, cables
(especially from computers), otherwise the operating distance may greatly drop.
The TW-DT-01/BL must NOT be installed near electronic devices and computer equipment that can interfere with its wireless communication
quality.
TW-DT-01/BL
Wireless Heat Detector Black
DEPLOYMENT PROCEDURE
1) Select a location for the detector. See LOCATION SELECTION.
2) Unbox the detector from its packaging.
3) Detach the detector from its base. See INSTALLING / REMOVING THE DETECTOR.
4) Detach the battery cover from the detector. See BATTERY COVER.
5.1) a) Link the detector to the system (insulating tab extraction).
See LINKING - WAKE-UP - WITH INSULATING TAB.
See LINKING - ONE-BY-ONE - WITH INSULATING TAB.
-- or --
5.2) a) Power up the detector.
See POWERING UP - FIRST TIME USE - WITHOUT INSULATING TAB.
See POWERING UP - RECOVERY.
b) Link the detector to the system (moving the link program switch).
See LINKING - WAKE-UP - WITHOUT INSULATING TAB.
See LINKING - ONE-BY-ONE - WITHOUT INSULATING TAB.
6) Reinstall the battery cover on the detector. See BATTERY COVER.
7) Detach the identification tag from the base adapter. See IDENTIFYING THE DETECTOR.
8) Install the base adapter. See FIXING THE ADAPTOR BASE.
9) Install the detector on the base adapter. See INSTALLING / REMOVING THE DETECTOR.
10) Install the identification tag to the base adapter, with all relevant information written / labelled on it. See IDENTIFYING THE DETECTOR.
11) Secure the detector to its base with its safety anti-tamper screw. See INSTALLING THE SAFETY SCREW.
12) Test the detector. See TESTING.
It is advisable to use the TW-SK-01 survey kit to
locate a good wireless installation location.
ARGUS SECURITY S.R.L. - Via del Canneto, 14 - 34015 - Muggia (TS) - Italy www.argussecurity.it
1) LED indicators
2) Battery A
3) Battery B
4) Link program switch
5) Tamper spring (internal)
6) Tamper switch (external)
7) Battery cover
8) Battery cover latch
9) Insulating tab
10) Wall fixing openings
11) Identification tag
12) Identification tag lodgement
13) Magnet test area
14) Base / detector reference marks
15) Safety screw
11234
5
Picture 1
1
6
7
8
9
10 10
11
13
14
15
12
All pictures are for product in black variant. Shown white for illustrative purpose only
BATTERY COVER
Detach the battery cover by pulling and lifting the closing latch.
To reinstall the battery cover, insert its two hooks into their corresponding
detector’s recesses; then block it by pressing down the opposite side, until you
hear the click of the closing latch.
INSTALLING / REMOVING THE DETECTOR
Rotate the detector clockwise on its adaptor base to install it.
Rotate the detector anti-clockwise from its adaptor base to remove it.
IDENTIFYING THE DETECTOR
The detector can be visually identified by the detachable tag imprinted with the adaptor base.
1) Detach the tag from the base.
2) Write / label the relevant identification information on the tag.
3) Insert the tag into its lodgement on the side of the adaptor base.
FIXING THE ADAPTOR BASE
Fix the base to the wall with suitable screws.
INSTALLING THE SAFETY SCREW
Always install the safety blocking screw.
LED INDICATORS STATUS MESSAGES
The two LED indicators communicate to the final user the status of the TW-DT-01/BL.
POWERING UP AND LINKING - PRELIMINARY NOTES
TW-DT-01/BL needs to be powered up with the supplied batteries.
Linking is the operation through which TW-DT-01/BL is “wirelessly connected” to a TW-MTI-01, TW-MEC-01 or TW-ME-01 Taurus network
device.
LINKING - WAKE-UP - WITH INSULATING TAB
“Wake-up” linking consists in associating one or more child devices to the Taurus system altogether in a single operation.
Wake-up is performed either through the TauREX software or the TW-MTI-01 / TW-MEC-01 keyboard-screen interface; it CANNOT be done
through TW-ME-01 devices.
1) Create the “virtual model” of the TW-DT-01/BL either on TauREX or on the TW-MTI-01 / TW-MEC-01.
2) Pull out the insulating tab.
3) Trigger the wake-up procedure either from TauREX or from the TW-MTI-01 / TW-MEC-01.
4) Wait the end of the “wake-up” linking procedure.
5) Check on TauREX or from TW-MTI-01 / TW-MEC-01 for linking success. Consult their user manual.
LINKING - ONE-BY-ONE - WITH INSULATING TAB
“One-by-one” linking consists in associating one child device at a time to the Taurus system.
This operation is performed either through the TauREX software or the TW-MTI-01 / TW-MEC-01 keyboard-screen interface; it CANNOT be
done through TW-ME-01 devices.
1) Create the “virtual model” of the TW-DT-01/BL either on TauREX or on the TW-MTI-01 / TW-MEC-01.
2) Trigger the linking procedure either from TauREX or from the TW-MTI-01 / TW-MEC-01.
3) Pull out the insulating tab.
4) Wait the end of the “one-by-one” linking procedure.
5) Check on TauREX or from TW-MTI-01 / TW-MEC-01 for linking success.
Consult their user manual.
Always install the battery cover, since it is a vital
part of the tamper detection feature. Make sure
the battery cover is safely fixed, blocked and
closed. Make sure that the internal tamper spring fits
completely into its battery cover’s lodgement. Check,
more than once, that the cover’s external tamper switch
clicks when pressed.
When extracting the insulating tab, keep both
batteries into their lodgements with your thumb,
since they can be accidentally pulled out too.
[email protected] L20-TWDT1B-0001 (vA.2)
2
Check the alignment of the raised reference
marks on the detector and on the base.
Always install the safety blocking screw.
Table 1
Please mind that LED signalling burns out battery
power, therefore reducing batteries lifespan.
Device status LEDs indication
Power up (DIP on “ON”) Blinks red 4 times
Power up (DIP opposite “ON”) Blinks green 4 times
Entering wake-up mode Blinks alternatively green / red 4 times
Link success (one-by-one) Blinks green 4 times, then the same pattern again
Link failure (one-by-one) Enters wake-up mode and signals “Entering wake-up mode” following this failure
Link success (wake-up) Blinks green 4 times, then same pattern again
Link failure (wake-up) Blinks green 4 times, then blinks red on once, then blinks alternatively green / red 4 times
Normal condition LED off (can be programmed so as to blink green every wireless communication)
Alarm activation Blinks red every 2 seconds
Battery fault LED off (can be programmed so as to blink amber every 5 seconds)
Tamper fault LED off
Replaced Blinks amber 2 times
Test mode active Blinks green
POWERING UP - FIRST TIME USE - WITHOUT INSULATING TAB
Use this procedure the first time you power up a TW-DT-01/BL; the detector has not been supplied with the insulating tab.
1) Make sure the Link / program switch is set on “ON”.
2) Insert the two supplied batteries into their device’s lodgments.
POWERING UP - DEVICE LINKED TO THE SYSTEM
Use this procedure when a TW-DT-01/BL is successfully linked to its Taurus system and you have to extract one or both batteries (e.g. batter-
ies substitution).
1) Reinsert the battery or both batteries into their lodgments.
If performing a batteries substitution, use two brand new batteries and substitute both of them.
Do not touch the Link / program switch.
POWERING UP - RECOVERY
Use this procedure when you fail to link successfully a TW-DT-01/BL or you want to link it again.
1) Move alternatively the Link / program switch 5 times.
2) Set the Link / program switch on “ON”.
3) Insert the two supplied batteries into their device’s lodgments.
LINKING - WAKE-UP - WITHOUT INSULATING TAB
“Wake-up” linking consists in associating one or more child devices to the Taurus system altogether in a single operation.
Wake-up is performed either through the TauREX software or the TW-MTI-01 / TW-MEC-01 keyboard-screen interface; it CANNOT be done
through TW-ME-01 devices.
1) Create the “virtual model” of the TW-DT-01/BL either on TauREX or on the TW-MTI-01 / TW-MEC-01.
2) Power-up the detector (either “first time use” or “recovery”).
3) Set the Link / program switch OPPOSITE to “ON”.
4) Trigger the wake-up procedure either from TauREX or from the TW-MTI-01 / TW-MEC-01.
5) Wait the end of the “wake-up” linking procedure.
6) Check on TauREX or from TW-MTI-01 / TW-MEC-01 for linking success. Consult their user manual.
LINKING - ONE-BY-ONE - WITHOUT INSULATING TAB
“One-by-one” linking consists in associating one child device at a time to the Taurus system.
This operation is performed either through the TauREX software or the TW-MTI-01 / TW-MEC-01 keyboard-screen interface; it CANNOT be
done through TW-ME-01 devices.
1) Create the “virtual model” of the child device either on TauREX or on the TW-MTI-01 / TW-MEC-01.
2) Trigger the linking procedure either from TauREX or from the TW-MTI-01 / TW-MEC-01.
3) Power-up the child device (either “first time use” or “recovery”).
4) Set the child device’s Link / program switch OPPOSITE to “ON”.
5) Wait the end of the “one-by-one” linking procedure.
6) Check on TauREX or from TW-MTI-01 / TW-MEC-01 for linking success. Consult their user manual.
TESTING
Magnet test
1) Activate test mode.
2) Apply again the magnet in correspondence of the “magnet test activation area”.
3) LED indicators signal “Alarm activation”.
Heat test
1) Activate test mode.
2) Apply the heat test device to the detector.
3) Wait a few seconds.
4) LED indicators signal “Alarm activation”.
BATTERY FAULTS AND BATTERY SUBSTITUTION PROCEDURE
When one or both batteries are low in charge, a specific fault message is routed to the
control panel. If such event occurs:
1) Remove the safety screw.
2) Remove the detector from its base.
3) Remove the batteries cover.
4) Extract both batteries.
5) Insert both new batteries into their holders, oriented as per polarity marks.
See POWERING UP - DEVICE LINKED TO THE SYSTEM.
6) Reinstall the batteries cover.
7) Reinstall the detector.
8) Reinstall the safety screw.
Local safety standards may require you
to test these devices on a regular basis.
Use only suitable heat test devices supplied by
approved manufacturers. Follow their specific
use instructions.
Before testing every TW-DT-01/BL,
always activate test mode. This is done
by holding a suitable magnet in the
“magnet test activation area”. When activated,
LED indicators signal “Test mode active”.
When a low battery condition is indicat-
ed, both batteries must be changed
altogether.
Batteries must be brand new.
Do not touch the Link / program switch.
Ensure that the batteries are installed properly,
with their polarities matching the indications on
the device.
Always ensure that the batteries are
installed properly, with their polarities
matching the indications on the device.
ARGUS SECURITY S.R.L. - Via del Canneto, 14 - 34015 - Muggia (TS) - Italy www.argussecurity.it
3
MAINTENANCE - CLEANING
1) Remove the safety screw.
2) Remove the detector from its base.
3) Thermistor area: use a small, soft bristle brush to dislodge any obvious contaminants such as insects, spider webs, hairs, etc.
4) Thermistor area: use a small vacuum tube or dry, clean, compressed air to suck up or blow any remaining small particles away.
5) Wipe the exterior housing of the detector with a clean, damp, lint-free cloth to remove any surface film that can later attract airborne
contaminants.
6) Install the detector onto its base again.
7) Test the detector.
8) Reinstall the safety screw.
TECHNICAL SPECIFICATIONS *
*See TDS-TWDTX technical specification document for further technical data.
** Detector’s rate of rise (A1R) / high temperature (BS) modes can be set through TauREX.
BATTERIES SPECIFICATIONS
*Batteries lifespan depends by environmental conditions, default monitor settings and link quality.
Specification Value
Communication range with TW-MTI-01, TW-MEC-01 or TW-ME-01
network devices 200 m (in open space)
Wireless frequency band 868 MHz
Number of wireless channels 66
Radiated power 14 dBm (25 mW)
Temperature alarm threshold (A1R rate of rise setting) ** 58 °C
Temperature alarm threshold (BS high temperature setting) ** 78 °C
Operating temperature range -10 °C to 55 °C
Maximum humidity (non condensing) 95% RH
IP rating 40
Specification Value
Batteries type CR123A (3 V, 1.25 Ah)
Batteries lifespan * 10 years
Low battery threshold value (nominal) 2.850 V
Table 2
Table 3
WARNINGS AND LIMITATIONS
Our devices use high quality electronic components and plastic materials that are highly resistant to
environmental deterioration. However, after 10 years of continuous operation, it is advisable to replace
the devices in order to minimize the risk of reduced performance caused by external factors. Ensure
that this device is only used with compatible control panels. Detection systems must be checked,
serviced and maintained on a regular basis to confirm correct operation. Smoke detectors may respond
differently to various kinds of smoke particles, thus application advice should be sought for special
risks. Detectors cannot respond correctly if barriers exist between them and the fire location and may
be affected by special environmental conditions. Refer to and follow national codes of practice and
other internationally recognized fire engineering standards. Appropriate risk assessment should be
carried out initially to determine correct design criteria and updated periodically.
Use only in Taurus fire detection and alarm systems.
WARRANTY
All devices are supplied with the benefit of a limited 5 years warranty relating to faulty materials or
manufacturing defects, effective from the production date indicated on each product. This warranty is
invalidated by mechanical or electrical damage caused in the field by incorrect handling or usage.
Product must be returned via your authorized supplier for repair or replacement together with full
information on any problem identified. Full details on our warranty and product’s returns policy can be
obtained upon request.
ARGUS SECURITY S.R.L.
Via del Canneto, 14
34015 Muggia (TS)
Italy
TW-DT-01/BL
EN 54-25:2008
EN 54-5:2017 + A1:2018
Category P (A1R / BS)
[email protected] L20-TWDT1B-0001 (vA.2)
4
0051
22
TU0310CPR
8504
22
TU0310UK

Other Argus Security Security Sensor manuals

Argus Security Taurus TW-MO-SB-01/916 User manual

Argus Security

Argus Security Taurus TW-MO-SB-01/916 User manual

Argus Security V100 User manual

Argus Security

Argus Security V100 User manual

Argus Security LW-DMCO-01 User manual

Argus Security

Argus Security LW-DMCO-01 User manual

Argus Security S2000 User manual

Argus Security

Argus Security S2000 User manual

Argus Security Taurus TW-SK-01 User manual

Argus Security

Argus Security Taurus TW-SK-01 User manual

Argus Security L-MC-SG/865 User manual

Argus Security

Argus Security L-MC-SG/865 User manual

Argus Security SG200 User manual

Argus Security

Argus Security SG200 User manual

Argus Security ALTAIR Series User manual

Argus Security

Argus Security ALTAIR Series User manual

Argus Security A2000L User manual

Argus Security

Argus Security A2000L User manual

Argus Security SG200-IS User manual

Argus Security

Argus Security SG200-IS User manual

Argus Security Taurus TW-DO-01/916 User manual

Argus Security

Argus Security Taurus TW-DO-01/916 User manual

Argus Security TW-DM-01/916 User manual

Argus Security

Argus Security TW-DM-01/916 User manual

Argus Security ALTAIR LITE Series User manual

Argus Security

Argus Security ALTAIR LITE Series User manual

Argus Security TAURUS TW-MI-S-01/916 User manual

Argus Security

Argus Security TAURUS TW-MI-S-01/916 User manual

Argus Security V200 User manual

Argus Security

Argus Security V200 User manual

Argus Security A3500 User manual

Argus Security

Argus Security A3500 User manual

Argus Security ALTAIR Series User manual

Argus Security

Argus Security ALTAIR Series User manual

Argus Security VCP100 User manual

Argus Security

Argus Security VCP100 User manual

Argus Security ALTAIR A1000 User manual

Argus Security

Argus Security ALTAIR A1000 User manual

Argus Security Taurus TW-DT-01/916 User manual

Argus Security

Argus Security Taurus TW-DT-01/916 User manual

Argus Security L-HT-SG User manual

Argus Security

Argus Security L-HT-SG User manual

Argus Security L-MC-SG User manual

Argus Security

Argus Security L-MC-SG User manual

Argus Security Taurus TW-DM-01 User manual

Argus Security

Argus Security Taurus TW-DM-01 User manual

Argus Security SG350-IS User manual

Argus Security

Argus Security SG350-IS User manual

Popular Security Sensor manuals by other brands

Tongdy PMD-18 Series manual

Tongdy

Tongdy PMD-18 Series manual

GasTech F-GUARD IR3-HD user manual

GasTech

GasTech F-GUARD IR3-HD user manual

Baumer URDK 10P8914/KS35A quick start guide

Baumer

Baumer URDK 10P8914/KS35A quick start guide

2M Technology 2MTHFR-2M user manual

2M Technology

2M Technology 2MTHFR-2M user manual

Recco R9 quick guide

Recco

Recco R9 quick guide

SKYLOTEC LORY Series Instructions for use

SKYLOTEC

SKYLOTEC LORY Series Instructions for use

Comunello Automation DART Installation and user manual

Comunello Automation

Comunello Automation DART Installation and user manual

GASTRON GTL-200 instruction manual

GASTRON

GASTRON GTL-200 instruction manual

Eaton MAB50R Installation and operation manual

Eaton

Eaton MAB50R Installation and operation manual

WatchGas NEO user manual

WatchGas

WatchGas NEO user manual

Optex URX-P01WH Installation instructions and operators manual

Optex

Optex URX-P01WH Installation instructions and operators manual

Inficon IRwin quick start guide

Inficon

Inficon IRwin quick start guide

PCB Piezotronics Tourmaline ICP 138A02 Installation and operating manual

PCB Piezotronics

PCB Piezotronics Tourmaline ICP 138A02 Installation and operating manual

Powerfix Profi PMDL 5 A1 operating instructions

Powerfix Profi

Powerfix Profi PMDL 5 A1 operating instructions

Satel ASD-100 manual

Satel

Satel ASD-100 manual

Chauvin Arnoux 760N user manual

Chauvin Arnoux

Chauvin Arnoux 760N user manual

THORLABS PDA50B2 user guide

THORLABS

THORLABS PDA50B2 user guide

Siemens FDOOT241-A3 manual

Siemens

Siemens FDOOT241-A3 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.