EUROSTER 11WB USER MANUAL 7
up cycle – it turns the pump OFF in order to fire the new batch of fuel up as soon as possible.
Should the flame to extinct, the controller will automatically turn the fan OFF.
ATTENTION: The controller will not automatically turn the fan OFF if it was earlier
manually turned OFF by the user and not turned back ON.
11 FAN OPERATION
The controller attempts to maintain boiler temperature adjusting amount of air blown to the
furnace by the fan and turning the CH pump ON/OFF.
Cold boiler may sweat during the firing up period. Therefore the fan is operating at the highest
power level (preset Błąd: Nie znaleziono źródła odwołania) and the pump is OFF to shorten
that period as far as possible.
As soon as the boiler temperature has approached the preset (and is within the hysteresis
corridor), the controller starts to smoothly control air flow adjusting the fan power level. Fan
power range is limited by the minimum fan power (Błąd: Nie znaleziono źródła odwołania) and
the maximum fan power (Błąd: Nie znaleziono źródła odwołania) presets.
Should the boiler temperature to exceed the upper threshold, the controller will start the boiler
blowdown cycling. In that mode the fan is used only to remove combustion gases out of the
furnace. Blowdown cycle parameters should be set so that boiler temperature will drop down
to the level at which the controller will be able to resume linear control of the fan power.
Should the boiler temperature to exceed the alarm temperature, the fan will be turned OFF for
good. Overheating is signaled by pulsing of the controller display.
Should the boiler temperature to drop down below the put out preset (Błąd: Nie znaleziono
źródła odwołania), the fan will be turned OFF. The pumps will be operated normally.
12 PUMP OPERATION
CH pump is engaged as soon as boiler temperature Tboiler exceeds boiler preset temperature
Tpreset by more than half of hysteresis Hpump:
Tboiler > Tpreset +Hpump/2
The pump is disengaged as soon as the temperature drops down below the preset by more
than half of the hysteresis:
Tboiler < Tpreset – Hpump/2
Decision to turn UHW pump is made in two stages:
•The pump is turned ON if the tank temperature Ttank has dropped below the preset by
more than half of the pump hysteresis Hpump:
Ttank < Tpreset Hpump/2
If the UWH priority mode of operation is activated, the CH pump is then unconditionally
turned OFF. The pump is disengaged as soon as the tank temperature has exceeded the
threshold by more than half of the hysteresis:
Ttank > Tpreset + Hpump/2
•The pump may be disengaged without a risk of chilling out the tank provided that the
difference between the boiler temperature and the tank temperature is at least by 3 ºC
higher than the preset boiler tank temperature surplus Tboiler – Ttank > Tsurplus+3ºC. The
pump should run (to prevent chilling out the tank) until the difference decreases to the
surplus minus 3ºC, Tboiler – Ttank < Tsurplus 3ºC.
1 SUMMER SEASON OPERATION
Set CH system pump TURN ON temperature (11) higher then the UHW pump preset and the
fan preset (e.g. to 80°C) in order to disable CH system during the summer season. UHW tank
will heat up quickly and the boiler will be protected against excessive temperatures.
14 THE ANTY-STOP FUNCTION
The ANTY STOP function turns on the pump immediately after the controller is turned on, then
every 14 days. “AS” letters are blinking on the controller display while the function is active.