Assa Abloy Norton ADAEZ User manual

700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
1 of 17
®
ADAEZ (WIM)
Wireless Interface Module
Installation and
Operating Instructions
To obtain the latest manual and template revisions or to view installation and programming videos go to
www.nortondoorcontrols.com. For technical support call 800-438-1951 x6030, Option 4.
CAUTION
Changes or modifications not expressly approved by the party responsible for compliance could void the
user's authority to operate this device.
INSIDE
BUTTON
INSIDE BUTTON
PRESS & RELEASE
TO LEARN
HOLD TO ERASE
OUTSIDE
BUTTON
DOOR
OPERATOR
FIRE PANEL IN COM OUT
ACCESS CTR
OUTSIDE BUTTON
DISABLE
LOCK
POWER
NO COM NC
LOCK
OUTSIDE BUTTON
PRESS & RELEASE
TO LEARN
HOLD TO ERASE
OPERATOR
SIGNAL SIGNAL
DELAY
POWER IN
12 OR 24V
+CH S
Copyright © 2018, ASSA ABLOY Accessories and Door Controls Group, Inc. All rights
reserved. Reproduction in whole or in part without the express written permission of ASSA
ABLOY Accessories and Door Controls Group, Inc. is prohibited.

700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
2 of 17
Prerequisites
2
1. An ADAEZ swing door operator installed according to ADAEZ Pro Installation and Operating Instructions p/n
700002 with optional Hardwire Kit p/n 1015 or 24VDC (500ma minimum) power supply by others.
2. 12 or 24V AC or DC to power the WIM.
4. Protective barrier (caution/warning tape) has been set up to prevent unauthorized access to work area.
5. The door has been secured to prevent unexpected opening or closing during installation.
3. 24VDC is REQUIRED if the ADAEZ swing door operator will be powered thorough the WIM with the supplied
cable.
Applicability
Discussion
This manual provides system description, installation instructions, operating instructions, and
troubleshooting recommendations for the ADAEZ Wireless Interface Module (referred to as the WIM).
The ADAEZ WIM allows the ADAEZ swing door operator to interface with the ADAEZ wired or wireless
pushbuttons, wireless remote, an electric lock, fire panel, access control, and an outside pushbutton disable
contact.
This manual is applicable to the ADAEZ series Wireless Interface Module.
Purpose
1
Precautions
3
1. This product is intended for interior use only.
2. An operating door creates pinch hazards. Be careful making operating adjustments while the door is moving.
3. The transformer wiring must not be concealed behind walls or routed through doorways, window openings,
walls, ceilings, or floors. Also, this wiring must be secured to prevent it from becoming entrapped in the moving
parts of the operator or door.

700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
3 of 17
System Description
4
• ADAEZ wireless (RF) push buttons or
• Electric Lock
• Wired push buttons
• Fire Panel
• Access Control
• ADAEZ wireless (RF) hand held transmitter
• Switch to disable outside pushbutton
General
The ADAEZ WIM allows the ADAEZ swing door operator to interface with:
1. Pushbuttons: A wired and wireless input is provided for an INSIDE and an OUTSIDE pushbutton. An
optional handheld transmitter (p/n ADA1031) may be programmed to either the INSIDE or OUTSIDE
activation connection.
2. Operator Connection: A cable assembly (p/n ADA1015C) is provided to plug in the ADA EZ swing
door operator into the WIM module.
3. Access Control: Contacts are provided to interface the WIM with access control.
4. Lock Interface: Contacts are provided to control an electrical lock.
5. Lock Power: Contacts are provided to power an electric lock.
7. Power Input: A power input connector is provided to power the WIM by a 12 or 24V AC/DC* power
supply or using the optional hardwire kit (p/n ADA1015P).
*If the Door Operator will be powered using the supplied cable assembly (p/n ADA1015C) the WIM must
be powered by a 24VDC 750mA minimum power supply.
6. Outside Pushbutton Disable: A contact is provided to disable any input from an outside pushbutton.
8. Signal Delay: A switch is provided to enable a 1 second delay before sending an activate signal to the
door operator.
Inputs & Outpus
5

700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
4 of 17
6Mount and Apply Power to the WIM
The ADAEZ WIM may be powered by 12 or 24 Volts AC
or DC current. If the door operator will be powered
directly from the WIM, a 24VDC 750ma (minimum)
power supply is required.
NOTE:
2. Provide power to the WIM. (Refer to Figure 1)
a. If the Optional hardwire kit (p/n ADA1015P) is
used to power the WIM and door operator, plug
the provided GREEN connector into the power
port as shown.
1. Mount the WIM enclosure in a remote location
as desired.
b. If Power supply is by others, connect the power
supply using the provided GREEN connector. If
a DC power supply is used connect the ground
to the terminal marked “-“ and the positive to the
terminal marked “+”.
c. If the operator will be powered through the WIM,
power is properly applied to the ADAEZ
operator the LED on the bottom of the battery
pack will light steady GREEN.
ADA1015C) to power the Operator. When
d. When the WIM is properly wired with power
applied LED D8 near the power connector will
light GREEN.
use the supplied Operator Wire Harness (p/n
Figure 1
INSIDE
BUTTON
INSIDE BUTTON
PRESS & RELEASE
TO LEARN
HOLD TO ERASE
OUTSIDE
BUTTON
DOOR
OPERATOR
FIRE PANEL IN COM OUT
ACCESS CTR
OUTSIDE BUTTON
DISABLE
LOCK
POWER
NO COM NC
LOCK
OUTSIDE BUTTON
PRESS & RELEASE
TO LEARN
HOLD TO ERASE
OPERATOR
SIGNAL SIGNAL
DELAY
POWER IN
12 OR 24V
+CH S
+CH S
(INCLUDED)
ADA1015C OPERATOR CABLE
POWER SUPPLY BY OTHER
OR
(NOT INCLUDED)
ADA1015P
HARDWIRE KIT
12/24V
AC/DC

700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
5 of 17
3. LEDs DS8 through DS11 shall flash GREEN.
2. Refer to Figure 3. PRESS and HOLD the LEARN
button and PRESS and RELEASE the RESET
button on the setup board.
NOTE:
1. Refer to Figure 2 and Remove the bottom cover
from the door operator to access the Setup board.
The ADAEZ swing door operator is shipped with
wireless RF pushbuttons that are pre-programmed to
the operator. The RF codes MUST be erased from the
ADAEZ swing door operator for proper operation.
7Erase All RF Codes from the Door Operator
Figure 2 Figure 3
3. On the Setup board, LEDs DS8 through DS11
shall rapidly flash GREEN 3 times.
1. Refer to Figure 3 and PRESS and HOLD the
LEARN button until on the Operator Control
board until LEDs DS8-DS11 Flash Green.
2. Refer to Figure 4 and PRESS and RELEASE
the “OPERATOR SIGNAL” button on the WIM.
8Learn WIM Module to Door Operator
9/64” HEX WRENCH
OPTION
OFF
OFF
ON
TUNING
POTENTIOMETER
1-4
ADJUSTMENT
INDICATOR LEDS
CLOSE
POSITION
OPEN
POSITION
AUTO
SETUP
LEARN RESET
SELECT ENTER
OPEN & CLOSE TIME
OPEN & PWR CLOSE
FORCE
HOLD OPEN/
EXECUTIVE
OPTIONS
PG
PC LA
DB
4
32
1
OPTIONS:
POWER CLOSE
PUSH & GO
DYNAMIC BRAKING
LATCH ASSIST

700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
6 of 17
1. Refer to Figure 4. If the pushbuttons will be hard
wired, connect the INSIDE and OUTSIDE
pushbuttons to the WIM module contacts labeled
INSIDE BUTTON and OUTSIDE BUTTON.
a. Refer to Figure 4 and PRESS and RELEASE
the “INSIDE BUTTON” button.
b. The Audible will beep and the LED above the
button will flash RED if no RF signals have been
learned or GREEN if an RF button is already
stored in memory. If the audible sounds a
steady beep and the RED LED lights flashes 4
times rapidly the RF memory is full and must be
reset in order to learn a new RF activation
signal.
NOTE:
An INSIDE activation is considered to be an input from
the SECURE side of the door. An INSIDE activation will
switch the LOCK contact, the ACCESS CTR output
contact, and send an activation signal to the door
operator.
2. If the INSIDE pushbutton will be connected using
RF activation, it must be learned to the WIM.
The pushbuttons may be connected by wire or wireless
connection to either the INSIDE activation or OUTSIDE
activation. If an optional Handheld Transmitter (not
included) was purchased it may be connected to either
the INSIDE or OUTSIDE activation inputs.
An OUTSIDE activation is considered to be an input
from the NON-SECURE side of the door. An OUTSIDE
activation will switch the LOCK contact, the ACCESS
CTR output contact, and send an activation signal to the
door operator ONLY if the ACCESS CTR INPUT contact
is CLOSED.
d. The LED will flash and the audible will beep 4
times if the RF signal was successfully learned.
e. If the pushbutton is not learned the audible will
beep for two seconds and exit learn mode.
c. Press and release the INSIDE pushbutton (or
optional handheld transmitter or optional
pushbutton) 2 times.
3. If the OUTSIDE pushbutton will be connected using
RF activation, it must be learned to the WIM.
a. Refer to Figure 4 and PRESS and RELEASE
the “OUTSIDE BUTTON” pushbutton.
c. Press and release the OUTSIDE pushbutton (or
optional handheld transmitter or optional
pushbutton) 2 times.
b. The Audible will beep and the LED above the
button will flash RED if no RF signals have been
learned or GREEN if an RF button is already
stored in memory. If the audible sounds a steady
beep and the RED LED lights flashes 4 times
rapidly the RF memory is full and must be reset
in order to learn a new RF activation signal.
d. LED D4 will flash and the audible will beep 4
times if the RF signal was successufully learned.
e. If the pushbutton is not learned the audible will
beep for two seconds and exit learn mode.
9Connect Pushbuttons and/or Handheld Remote to WIM
1. Refer to Figure 4 and PRESS and HOLD the
INSIDE BUTTON pushbutton on the WIM for 5
seconds
4. LED D4 will flash RED 4 times and the audible
will beep for 4 seconds
5. All learned RF codes are now erased.
3. Refer to Figure 4 and PRESS and HOLD the
OUTSIDE BUTTON pushbutton for 5 seconds
2. LED D3 will flash RED 4 times and the audible will
beep for 4 seconds
10 Erasing RF Codes from WIM

700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
7 of 17
11 Erasing RF Codes from WIM
INSIDE
BUTTON
INSIDE BUTTON
PRESS & RELEASE
TO LEARN
HOLD TO ERASE
OUTSIDE
BUTTON
DOOR
OPERATOR
FIRE PANEL IN COM OUT
ACCESS CTR
OUTSIDE BUTTON
DISABLE
LOCK
POWER
NO COM NC
LOCK
OUTSIDE BUTTON
PRESS & RELEASE
TO LEARN
HOLD TO ERASE
OPERATOR
SIGNAL SIGNAL
DELAY
POWER IN
12 OR 24V
+CH S
LED D8
LED D2
LED D5
LED D3
LED D4
Figure 4

700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
8 of 17
NOTE:
The electric lock contact will switch state when the
INSIDE pushbutton is activated OR the Access Control
input contact is CLOSED.
1. An electric lock may be connected to the WIM as
shown in Figure 5.
2. A normally open or normally closed contact are
provided for fail safe or fail secure lock
installation. Connect the lock and power supply to
the WIM as shown in Figure 5.
3. An optional signal delay is provided to add a one
second time delay between receiving an activate
signal and sending an activate signal to the door
operator. This allows additional time for the lock to
unlock before the door starts to unlock before the
door starts to open. If the lock delay is required,
refer to Figure 4 and move the SIGNAL DELAY
12 Connect an Electric Lock to the WIM
Figure 5
INSIDE
BUTTON
INSIDE BUTTON
PRESS & RELEASE
TO LEARN
HOLD TO ERASE
OUTSIDE
BUTTON
DOOR
OPERATOR
FIRE PANEL IN COM OUT
ACCESS CTR
OUTSIDE BUTTON
DISABLE
LOCK
POWER
NO COM NC
LOCK
OUTSIDE BUTTON
PRESS & RELEASE
TO LEARN
HOLD TO ERASE
OPERATOR
SIGNAL SIGNAL
DELAY
POWER IN
12 OR 24V
+CH S
+CH S
LOCK
POWER
SUPPLY
ELECTRIC
LOCK
FAIL SECURE
FAIL SAFE
Optional Handheld Remote
(Not Included)
Wired or Wireless
Pushbutton Connection

700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
9 of 17
The ACCESS CTRL OUT contact will close when the
WIM module has received an authorized signal to
switch the LOCK contact.
Closing the FIRE PANEL contact will prevent the door
operator from accepting an activate signal or will close
the door operator if it is in the open position.
NOTE: 1. Refer to Figure 6 and connect the optional Access
Control Input contact, Alarm Panel Output contact,
or Fire Panel Input contact.
Closing the ACCESS CTRL IN contact will switch the
state of the LOCK contact and enable the OUTSIDE
pushbutton.
13 Connect the WIM to Access Control, Alarm Panel, or Fire Panel
INSIDE
BUTTON
INSIDE BUTTON
PRESS & RELEASE
TO LEARN
HOLD TO ERASE
OUTSIDE
BUTTON
DOOR
OPERATOR
FIRE PANEL IN COM OUT
ACCESS CTR
OUTSIDE BUTTON
DISABLE
LOCK
POWER
NO COM NC
LOCK
OUTSIDE BUTTON
PRESS & RELEASE
TO LEARN
HOLD TO ERASE
OPERATOR
SIGNAL SIGNAL
DELAY
POWER IN
12 OR 24V
+CH S
ALARM
PANEL
FIRE
PANEL
ACCESS
CONTROL
+CH S
Figure 6

700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
10 of 17
NOTE:
An optional Keyswitch or Access Control device may be
hard wired in series with the Outside Disable Button to
enable the Lock and Outside Pushbutton
2. Connect a Card Reader Access control OR Place a
Jumper across the ACCESS CTRL IN and COM.
NOTE:
Closing the OUTSIDE BUTTON DISABLE contact will
prevent the WIM from accepting an activation signal
from the OUTSIDE pushbutton. When the OUTSIDE
BUTTON DISABLE contact is closed the WIM will only
switch the lock state and activate the operator when an
INSIDE pushbutton signal is received.
1. Refer to Figure 6 and Connect the OUTSIDE
PUSHBUTTON DISABLE contact to the deadbolt
monitoring switch.
Placing a jumper across the ACCESS CTRL IN and
COM will maintain the lock in the UNLOCKED condition
unless the OUTSIDE BUTTON DISABLE contact is
CLOSED.
14 Connect the Outside Pushbutton Disable
LOCK
POWER
SUPPLY
FAIL SECURE
FAIL SAFE
Deadbolt
Status
Switch
Figure 8
Wired or Wireless
Pushbutton Connection
INSIDE
BUTTON
INSIDE BUTTON
PRESS & RELEASE
TO LEARN
HOLD TO ERASE
OUTSIDE
BUTTON
DOOR
OPERATOR
FIRE PANEL IN COM OUT
ACCESS CTR
OUTSIDE BUTTON
DISABLE
LOCK
POWER
NO COM NC
LOCK
OUTSIDE BUTTON
PRESS & RELEASE
TO LEARN
HOLD TO ERASE
OPERATOR
SIGNAL SIGNAL
DELAY
POWER IN
12 OR 24V
+CH S
+CH S
ACCESS
CONTROL
Connect to Access Control
OR
Jumper
Optional Keyswitch
Safety Override

700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
11 of 17
INSIDE
BUTTON
INSIDE BUTTON
PRESS & RELEASE
TO LEARN
HOLD TO ERASE
OUTSIDE
BUTTON
DOOR
OPERATOR
FIRE PANEL IN COM OUT
ACCESS CTR
OUTSIDE BUTTON
DISABLE
LOCK
POWER
NO COM NC
LOCK
OUTSIDE BUTTON
PRESS & RELEASE
TO LEARN
HOLD TO ERASE
OPERATOR
SIGNAL SIGNAL
DELAY
POWER IN
12 OR 24V
+CH S
LOCK
POWER
SUPPLY
FAIL SECURE
FAIL SAFE
ALARM
PANEL
CARD READER
(ACCESS
CONTROL)
+CH S
15 Electric Strike with RF or Wired Pushbuttons & Card Reader (or other access control)
Figure 7
Optional Handheld Remote
(Not Included)
Wired or Wireless
Pushbutton Connection

700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
12 of 17
INSIDE
BUTTON
INSIDE BUTTON
PRESS & RELEASE
TO LEARN
HOLD TO ERASE
OUTSIDE
BUTTON
DOOR
OPERATOR
FIRE PANEL IN COM OUT
ACCESS CTR
OUTSIDE BUTTON
DISABLE
LOCK
POWER
NO COM NC
LOCK
OUTSIDE BUTTON
PRESS & RELEASE
TO LEARN
HOLD TO ERASE
OPERATOR
SIGNAL SIGNAL
DELAY
POWER IN
12 OR 24V
+CH S
LOCK
POWER
SUPPLY
FAIL SECURE
FAIL SAFE
OUTSIDE PB
DISABLE
ALARM
PANEL
CARD READER
(ACCESS
CONTROL)
FIRE
PANEL
+CH S
16 All Connections used on WIM
Figure 9
Optional Handheld Remote
(Not Included)
Wired or Wireless
Pushbutton Connection

700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
13 of 17
17 Troubleshooting Recommendations
No Symptom Recommended Remedy
1 LED D8 does not light
Green when Operator
cable is plugged into WIM
and ADAEZ
· If using the ADA1015P hardwire kit verify the black wire with
white stripe is plugged into the “-“ terminal and the black wire is
plugged into the “+” terminal.
· If using Power supply by other, verify the wires from the power
supply are the correct polarity and plugged intot the “-“ and “+”
terminals.
· Verify the wires are fully seated and making a good connection.
· Using a multimeter, insert the probes into the holes below the “-
“ and “+” terminals and verify 12 or 24 Volts AC or DC voltage.
2 The LED on the ADAEZ
battery pack does not
light steady GREEN
when powered by the
provided operator cable
ADA1015C.
· Verify that 24VDC is being supplied to the POWER IN
connection on the WIM and LED D8 near the connector is
lighted steady GREEN.
· On the Operator Cable ADA1015C, Verify the black wire with
white stripe is plugged into the “-“ terminal and the black wire is
plugged into the “+” terminal on both ends of the cable.
· Verify the wires are fully seated into both green connectors on
both ends of the cable.
· Using a multimeter, insert the probes into the holes below the “-
“ and “+” terminals and verify 24 VDC on the Operator end of
the Operator Cable ADA1015C.
3 RF Pushbuttons or
Optional Handheld
Remote ADA1031 (Not
Included) will not Sync to
WIM
· Verify the voltage of the CR2032 battery is above 3.0V and
replace battery if necessary.
· Unwrap the antenna wire on the WIM and extend the wire
through a hole in the enclosure.
· If programming an INSIDE BUTTON Press and hold the
INSIDE BUTTON switch on the WIM for 5 seconds to erase all
existing learned transmitters. Re-learn using procedure above.
· If programming an OUTSIDE BUTTON Press and hold the
OUTSIDE BUTTON switch on the WIM for 5 seconds to erase
all existing learned transmitters. Re-learn using procedure
above.
4 Operator will not sync to
WIM
· Verify the jumper on the FIRE PANEL contact is in place.
· Verify the OUTSIDE BUTTON DISABLE contact is not closed.
· Erase all existing RF codes from Operator (on the Operator
setup board, PRESS and HOLD LEARN, PRESS and
RELEASE RESET).

700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
14 of 17
17 Troubleshooting Recommendations - con’t
No Symptom Recommended Remedy
5 Lock does not unlock
when an INSIDE activation
is sent.
· If RF buttons are used and LED D3 is NOT flashing perform
troubleshooting steps in section “RF transmitters will not
Sync to WIM”
· If hardwired buttons are used and D3 is NOT flashing:
o verify wires are connected to the Common (C) and
Normall Open (NO) switch contacts.
o Use a multimeter to verify a contact closure on
INSIDE BUTTON.
· If LED D3 is flashing
o Verify the jumper on the FIRE PANEL is in place.
· Measure the voltage across the LOCK POWER input and
verify the correct voltage for the lock.
6 Lock does not unlock
when an OUTSIDE
activation is sent.
· If RF buttons are used and LED D4 is NOT flashing perform
troubleshooting steps in section “RF transmitters will not
Sync to WIM”
· If hardwired buttons are used and D4 is NOT flashing:
o verify wires are connected to the Common (C) and
Normall Open (NO) switch contacts.
o Use a multimeter to verify a contact closure on
INSIDE BUTTON.
· If LED D4 is flashing
o Verify the ACCESS CTR IN contact is closed while
activation is being sent. The WIM will not accept an
OUTSIDE activation unless a valid access control
input is received.
o Verify OUTSIDE BUTTON DISABLE contact is not
closed.
o Verify the jumper on the FIRE PANEL is in place.
o Measure the voltage across the LOCK POWER
input and verify matching voltage with lock.
7 The OUTSIDE BUTTON
disable does not prevent
the lock from unlocking
o Verify the button is programmed/connected to the
OUTSIDE BUTTON contact.

700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
15 of 17
17Troubleshooting Recommendations - con’t
No Symptom Recommended Remedy
8 The ADAEZ operator
does not activate when
pushing the INSIDE
pushbutton
· If RF buttons are used and LED D3 is NOT flashing
perform troubleshooting steps in section “RF transmitters
will not Sync to WIM”
· If hardwired buttons are used and D3 is NOT flashing:
o verify wires are connected to the Common (C)
and Normall Open (NO) switch contacts.
o Use a multimeter to verify a contact closure on
INSIDE BUTTON.
· IF LED D3 IS flashing & LED D5 IS flashing
o Verify LEDs on setup board are lighting. If LEDs
on setup board do not light, Erase all learned
codes from the ADAEZ operator and re-sync the
WIM to the operator.
o Verify ADAEZ operator has been programmed using
the procedure in the Installation and Operating
Instructions.
· IF LED D3 IS flashing and LED D5 is NOT flashing
o Verify the jumper on the FIRE PANEL is in place.
· Turn the Signal Delay switch to the “ON” position.
9 The ADAEZ operator
does not activate when
pushing the OUTSIDE
pushbutton
· If RF buttons are used and LED D4 is NOT flashing
perform troubleshooting steps in section “RF transmitters
will not Sync to WIM”
· If hardwired buttons are used and D4 is NOT flashing:
o verify wires are connected to the Common (C)
and Normall Open (NO) switch contacts.
o Use a multimeter to verify a contact closure on
INSIDE BUTTON.
· IF LED D4 IS flashing & LED D5 IS flashing
o Verify LEDs on setup board are lighting. If LEDs
on setup board do not light, Erase all learned
codes from the ADAEZ operator and re-sync the
WIM to the operator.
o Verify ADAEZ operator has been programmed
using the procedure in the Installation and
Operating Instructions.
· IF LED D3 IS flashing and LED D5 is NOT flashing
o Verify the ACCESS CTR IN contact is closed
while activation is being sent. The WIM will not
accept an OUTSIDE activation unless a valid
access control input is received.
o Verify OUTSIDE BUTTON DISABLE contact is not
closed.
o Verify the jumper on the FIRE PANEL is in place.
o Turn the Signal Delay switch to the “ON” position.

700703 REV H 09/18
ADAEZ Wireless Interface Module
Installation and Operation Instructions
16 of 17
Note
This device complies with Industry Canada's licence-exempt RSSs. Operation is subject to
the following two conditions:
(1) This device may not cause interference; and
(2) This device must accept any interference, including interference that may cause
undesired operation of the device.
2) l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est
susceptible d'en compromettre le fonctionnement.
Changes or modifications not expressly approved by the party responsible for compliance
could void the user's authority to operate this device. This device complies with part 15 of
the FCC Rules. Operation is subject to the condition that this device does not cause
harmful interference.
1) l'appareil ne doit pas produire de brouillage;
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils
radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes :
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction manual,
may cause harmful interference to radio communications.
Norton Door Controls
3000 Highway 74 East
Monroe, NC 28112
Tel: (800)-438-1951 ext. 6030
www.nortondoorcontrols.com
support.aadcg@assaabloy.com
safety and convenience
leader in door opening solutions,
ASSA ABLOY is the global
dedicated to satisfying
end-user needs for security,
Table of contents
Other Assa Abloy Control Unit manuals

Assa Abloy
Assa Abloy LCU9101IV User manual

Assa Abloy
Assa Abloy HES iCLASS IC0020 Owner's manual

Assa Abloy
Assa Abloy OneSystem Service Module User manual

Assa Abloy
Assa Abloy TRAKA UD0011 User manual

Assa Abloy
Assa Abloy EffEff 1340-20 User manual

Assa Abloy
Assa Abloy effeff 720-40 Quick start guide

Assa Abloy
Assa Abloy EffEff 1338-14 User manual

Assa Abloy
Assa Abloy Medeco XT AIM Operation manual

Assa Abloy
Assa Abloy Securitron NL4 User manual

Assa Abloy
Assa Abloy LCU9101 User manual