AUMA SQEx 05.2 User manual

Control
Parallel
Profibus DP
Profinet
Modbus RTU
→Modbus TCP/IP
Foundation Fieldbus
HART
Part-turn actuators
SQEx 05.2 –SQEx 14.2
SQREx 05.2 –SQREx 14.2
Control unit: electronic (MWG)
with actuator controls
ACExC 01.2 Non-Intrusive
Assembly, operation, commissioningOperation instructions

Read operation instructions first.
●Observe safety instructions.
●These operation instructions are part of the product.
●Retain operation instructions during product life.
●Pass on instructions to any subsequent user or owner of the product.
Purpose of the document:
This document contains information for installation, commissioning, operation and maintenance staff.It is intended
to support device installation and commissioning.
Reference documents:
●Manual (Operation and setting ) of actuator controls ACExC 01.2 Modbus TCP/IP
●Manual (Fieldbus device integration) of actuator controls ACExC 01.2 Modbus TCP/IP
Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA
(refer to <Addresses>).
Table of contents Page
51. Safety instructions................................................................................................................. 51.1. Basic information on safety 61.2. Range of application 61.3. Warnings and notes 71.4. References and symbols
82. Identification........................................................................................................................... 82.1. Name plate 122.2. Short description
133. Transport, storage and packaging........................................................................................ 133.1. Transport 143.2. Storage 153.3. Packaging
164. Assembly................................................................................................................................ 164.1. Mounting position 164.2. Handwheel fitting 164.3. Part-turn actuator to valve: mount 174.3.1. Output drive for coupling 174.3.1.1. Part-turn actuator (with coupling): mount to valve 204.4. Mounting positions of local controls 204.4.1. Mounting positions: modify
215. Electrical connection............................................................................................................. 215.1. Basic information 235.2. KES electrical connection 245.2.1. Terminal compartment: open 255.2.2. Cable connection 265.2.3. Industrial Ethernet cable:connect 275.2.4. Terminal compartment: close 275.3. External earth connection 285.4. Accessories for electrical connection 285.4.1. Actuator controls on wall bracket
2
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
Table of contents ACExC 01.2 Non-Intrusive ModbusTCP/IP

295.4.2. Parking frame
306. Operation................................................................................................................................ 306.1. Manual operation 306.1.1. Manual operation: engage 306.1.2. Manual operation: disengage 306.2. Motor operation 306.2.1. Local actuator operation 316.2.2. Actuator operation from remote 326.3. Menu navigation via push buttons (for settings and indications) 336.3.1. Menu layout and navigation 346.4. User level, password 346.4.1. Password entry 356.4.2. Password change 356.5. Language in the display 356.5.1. Language change
377. Indications.............................................................................................................................. 377.1. Indications during commissioning 377.2. Indications in the display 387.2.1. Feedback indications from actuator and valve 407.2.2. Status indications according to AUMA classification 417.2.3. Status indications according to NAMUR recommendation 437.3. Indication lights of local controls 437.4. Mechanical position indication (self-adjusting) 447.5. Mechanical position indication via indicator mark
458. Signals (output signals)......................................................................................................... 458.1. Status signals via output contacts (digital outputs) 458.1.1. Assignment of outputs 458.1.2. Coding the outputs 458.2. Analogue signals (analogue outputs)
469. Commissioning (basic settings)........................................................................................... 469.1. End stops in part-turn actuator 479.1.1. End stop CLOSED: set 479.1.2. End stop OPEN: set 489.2. Type of seating: set 499.3. Torque switching: set 519.4. Limit switching: set 529.5. Fieldbus address (slave address), baud rate, parity and monitoring time: set 539.5.1. Modbus TCP/IP gateway: set 539.6. Test run 539.6.1. Direction of rotation at mechanical position indicator: check 549.6.2. Limit switching: check
5510. Commissioning (settings in the actuator)........................................................................... 5610.1. Switch compartment: open/close 5610.2. Mechanical position indicator (self-adjusting) 5710.2.1. Mechanical position indicator: set 5710.2.2. Gear stage of the reduction gearing: test/set 5810.3. Mechanical position indication via indicator mark (not self-adjusting) 5910.3.1. Mechanical position indicator: set
3
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive ModbusTCP/IP Table of contents

5910.3.2. Gear stage of the reduction gearing: test/set
6111. Corrective action.................................................................................................................... 6111.1. Faults during commissioning 6111.2. Fault indications and warning indications 6511.3. Fuses 6511.3.1. Fuses within the actuator controls 6511.3.2. Fuse replacement 6511.3.2.1. Replace fuses F1/F2 6611.3.2.2. Test/replace fuses F3/F4 6611.3.3. Motor protection (thermal monitoring)
6812. Servicing and maintenance................................................................................................... 6812.1. Preventive measures for servicing and safe operation 6812.2. Disconnection from the mains 6812.2.1. Disconnection from the mains with KP/KPH and KES electrical connection 6912.3. Maintenance 7012.4. Disposal and recycling
7113. Technical data......................................................................................................................... 7113.1. Technical data Part-turn actuator 7313.2. Technical data Actuator controls
7914. Spare parts............................................................................................................................. 7914.1. Part-turn actuators SQEx 05.2 –SQEx 14.2/SQREx 05.2 –SQREx 14.2 KES 8114.2. Actuator controls ACExC 01.2 KES Modbus TCP/IP
8315. Certificates.............................................................................................................................. 8315.1. Declaration of Incorporation and EU Declaration of Conformity
86Index........................................................................................................................................
89Addresses...............................................................................................................................
4
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
Table of contents ACExC 01.2 Non-Intrusive ModbusTCP/IP

1. Safety instructions
1.1. Basic information on safety
Standards/directives Our products are designed and manufactured in compliance with recognised
standards and directives.This is certified in a Declaration of Incorporation and an
EU Declaration of Conformity.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
They include among others:
●Standards and directives such as IEC 60079 “Explosive atmospheres".
- Part 14: Electrical installations design, selection and erection.
- Part 17: Electrical installations inspection and maintenance.
●Applicable configuration guidelines for network applications.
Safetyinstructions/warn-
ings All personnel working with this device must be familiar with the safety and warning
instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to avoid personal injury or property
damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out by suitably qualified personnel authorised by the end user or contractor
of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Work performed in potentially explosive atmospheres is subject to special regulations
which have to be observed.The end user or contractor of the plant are responsible
for respect and control of these regulations, standards, and laws.
Commissioning Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation.The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Operation Prerequisites for safe and smooth operation:
●Correct transport, proper storage, mounting and installation, as well as careful
commissioning.
●Only operate the device if it is in perfect condition while observing these instruc-
tions.
●Immediately report any faults and damage and allow for corrective measures.
●Observe recognised rules for occupational health and safety.
●Observe national regulations.
●During operation,thehousingwarms upandsurface temperatures>60°Cmay
occur.To prevent possible burns, we recommend checking the surface temper-
ature using an appropriate thermometer and wearing protective gloves, if re-
quired, prior to working on the device.
Protective measures The end user or the contractor are responsible for implementing required protective
measures on site, such as enclosures, barriers, or personal protective equipment
for the staff.
Maintenance To ensure safe device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior written consent of the manufacturer.
5
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive ModbusTCP/IP Safety instructions

1.2. Range of application
AUMA part-turn actuators are designed for the operation of industrial valves, e.g.
butterfly valves and ball valves.
The devices described below are approved for use in the potentially explosive
atmospheres of zones 1, 2, 21, and 22.
If temperatures >40 °C are to be expected at the valve mounting flange or the valve
stem (e.g.due to hot media), please consult AUMA.Temperatures > 40 °C are not
considered with regards to the non-electrical explosion protection.
Other applications require explicit (written) confirmation by the manufacturer.
The following applications are not permitted, e.g.:
●Industrial trucks according to EN ISO 3691
●Lifting appliances according to EN 14502
●Passenger lifts according to DIN 15306 and 15309
●Service lifts according to EN 81-1/A1
●Escalators
●Continuous duty
●Buried service
●Continuous submersion (observe enclosure protection)
●Potentially explosive areas of zones 0 and 20
●Potentially explosive areas of group I (mining)
●Radiation exposed areas in nuclear power plants
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device's
designated use.
Information These operation instructions are only valid for the "clockwise closing" standard
version, i.e. driven shaft turns clockwise to close the valve.
1.3. Warnings and notes
The following warnings draw special attention to safety-relevant procedures in these
operation instructions, each marked by the appropriate signal word (DANGER,
WARNING, CAUTION, NOTICE).
Indicates an imminently hazardous situation with a high level of risk. Failure
to observe this warning results in death or serious injury.
Indicates a potentially hazardous situation with a medium level of risk.Failure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a low level of risk. Failure to
observe this warning could result in minor or moderate injury. May also be
used with property damage.
Potentially hazardous situation. Failure to observe this warning could result
in property damage. Is not used for personal injury.
6
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
Safety instructions ACExC 01.2 Non-Intrusive Modbus TCP/IP

Arrangement and typographic structure of the warnings
Type of hazard and respective source!
Potential consequence(s) in case of non-observance (option)
→Measures to avoid the danger
→Further measure(s)
Safety alert symbol warns of a potential personal injury hazard.
The signal word (here: DANGER) indicates the level of hazard.
1.4. References and symbols
The following references and symbols are used in these instructions:
Information The term Information preceding the text indicates important notes and information.
Symbol for CLOSED (valve closed)
Symbol for OPEN (valve open)
Important information before the next step.This symbol indicates what is required
for the next step or what has to be prepared or observed.
Via the menu to parameter
Describes the path within the menu to the parameter. By using the push buttons of
the local controls you may quickly find the desired parameter in the display.
< > Reference to other sections
Terms in brackets shown above refer to other sections of the document which provide
further information on this topic.These terms are either listed in the index, a heading
or in the table of contents and may easily be located.
7
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive ModbusTCP/IP Safety instructions

2. Identification
2.1. Name plate
Figure 1: Arrangement of name plates
[1] Actuator name plate
[2] Actuator controls name plate
[3] Motor name plate
[4] Explosion protection approval plate
[5] Additional plate, e.g. KKS plate (Power Plant Classification System)
Actuator name plate
Figure 2: Actuator name plate (example)
(= manufacturer logo); (= CE mark)
[1] Name of manufacturer
[2] Address of manufacturer
[3] Type designation
[4] Order number
[5] Serial number
[6] Operating time in [s] for a part-turn movement of 90°
[7] Torque range in direction CLOSE
[8] Torque range in direction OPEN
[9] Type of lubricant
[10] Permissible ambient temperature
[11] Can be assigned as an option upon customer request
[12] Enclosure protection
[13] Data Matrix code
8
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
Identification ACExC 01.2 Non-Intrusive ModbusTCP/IP

Actuator controls name plate
Figure 3: Actuator controls name plate
(= manufacturer logo)
[1] Type designation
[2] Order number
[3] Serial number
[4] Actuator terminal plan
[5] Actuator controls terminal plan
[6] Mains voltage
[7] AUMA power class for switchgear
[8] Permissible ambient temperature
[9] Enclosure protection
[10] Control
[11] Data Matrix code
Motor name plate
Figure 4: Motor name plate (example)
(= manufacturer logo); (= CE mark)
[1] Motor type
[2] Motor article number
[3] Serial number
[4] Current type, mains voltage
[5] Rated power
[6] Rated current
[7] Type of duty
[8] Enclosure protection
[9] Motor protection (temperature protection)
[10] Insulation class
[11] Speed
[12] Power factor cos phi
[13] Mains frequency
[14] Data Matrix code
9
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive ModbusTCP/IP Identification

Approval plate in explosion-proof version
Figure 5: Approval plates in explosion-proof version (examples)
[1] Ex symbol, CE mark, number of test authority
[2] Ex certificate (number)
Classification:
[3] Electrical gas explosion protection
[4] Electrical dust explosion protection
[5] Non-electrical explosion protection
[6] Threads for line bushings at electrical connection
[7] Not used
Descriptions referring to name plate indications
Type designation Figure 6:Type designation (example)
1. Type and size of actuator
2. Flange size
3. Ex marking
Type and sizee
These instructions apply to the following devices types and sizes:
●Type SQEx = Part-turn actuators for open-close duty
Sizes: 05.2, 07.2, 10.2, 12.2, 14.2
●Type SQREx = Part-turn actuators for modulating duty
Sizes: 05.2, 07.2, 10.2, 12.2, 14.2
●Type ACExC = AUMATIC actuator controls
Size: 01.2
10
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
Identification ACExC 01.2 Non-Intrusive ModbusTCP/IP

Ex marking
Table 1:
Marking for explosion protection (example of /-a3b1)
1b3a–
Not used–
Motor type
a = VDX or SDX: 3-phase AC motor
= VWX or SWX: 1-phase AC motor
a
Protection type of electrical connection
3 = Terminal compartment Ex eincreased safety
4 = Terminal compartment Ex dflameproof enclosure
3
Protection type of position transmitter
a = Without intrinsically safe electric circuit
b = Electric circuit Ex iIntrinsic safety (RWG 5020.2Ex)
b
Protection type of fieldbus
1 = Without Ex fieldbus connection
2 = Ex nL non-incendive fieldbus connection
3= Ex ic intrinsically safe fieldbus connection
1
Order number The product can be identified using this number and the technical data as well as
order-related data pertaining to the device can be requested.
Please always state this number for any product inquiries.
On the Internet at http://www.auma.com > Service & Support > myAUMA, we offer
a service allowing authorised users to download order-related documents such as
wiring diagramsandtechnical data (both in GermanandEnglish),inspection certificate
and the operation instructions when entering the order number.
Actuator serial number Table 2:
Description of the serial number (with example of 0516NS12345)
NS123451605
Positions 1+2: Assembly in week = week 0505
Positions 3+4:Year of manufacture = 201616
Internal number for unambiguous product identificationNS12345
Actuator terminal plan Position 9 after TPA: Position transmitter version
I, Q = MWG (Magnetic limit and torque transmitter)
AUMA power class for
switchgear The switchgear used in the actuator controls (reversing contactors/thyristors) are
classified according to AUMA power classes (e.g.A1, B1, ....).The power class
defines the max. permissible rated power (of the motor) the switchgear has been
designed for.The rated power (nominal power) of the actuator motor is indicated in
kW on the motor name plate.For the assignment of the AUMA power classes to the
nominal power of the motor types, refer to the separate electrical data sheets.
For switchgear without assignment to any power classes, the actuator controls name
plate does not indicate the power class but the max. rated power in kW.
Control Table 3:
Control examples (indications on actuator controls name plate)
DescriptionInput signal
Control via ModbusTCP/IP interfaceModbusTCP/IP
Control via ModbusTCP/IP interface and control voltage for OPEN-CLOSE
control via digital inputs (OPEN, STOP, CLOSE)
ModbusTCP/IP/24V DC
Data Matrix code Whenregistered as authoriseduser, youmayuse our AUMA Assistant App to scan
the Data Matrix code and directly access the order-related product documents without
having to enter order number or serial number.
11
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive ModbusTCP/IP Identification

Figure 7: Link to AUMA Assistant App:
For further Service & Support, software/apps/...refer to www.auma.com.
2.2. Short description
Part-turn actuator Definition in compliance with EN 15714-2/EN ISO 5211:
A part-turn actuator is an actuator which transmits a torque to the valve for less than
one full revolution.It need not be capable of withstanding thrust.
AUMA part-turn actuators SQEx 05.2 –SQEx 14.2/SQREx 05.2 –SQREx 14.2 are
driven by an electric motor.For manual operation, a handwheel is provided.Switching
off in end positions may be either by limit or torque seating.Actuator controls are
required to operate or process the actuator signals.
Actuator controls ACExC 01.2 actuator controls are used to operate AUMA actuators and are supplied
ready for use.The actuator controls may be mounted directly to the actuator or
separately on a wall bracket.
The functions of the ACExC 01.2 actuator controls include standard valve control in
OPEN-CLOSE duty, positioning, process control, logging of operating data, diagnostic
functions right through control via various interfaces (e.g. Fieldbus, Ethernet and
HART).
Local controls/
AUMA software Operation, setting, and display can be either performed directly at actuator controls
or alternatively from Remote via binary input signals, or using another interface.
The following options are available at the actuator controls in local operation:
●The actuator can be operated via the push buttons of the local controls or set-
tingscanbemadeintheactuator controls menu.Thedisplayshows information
on the actuator as well as menu settings (contents of these instructions).
●Using the AUMA CDT software for Windows-based notebooks or the AUMA
Assistant App for Android-based devices, data can be uploaded and read
whereassettings can be modified and stored.Theconnectionbetweencomputer
and actuator controls is wireless via Bluetooth interface (not included in these
instructions). AUMA CDT software can be downloaded free of charge from our
website www.auma.com.
Intrusive - Non-Intrusive ●Intrusive version (control unit: electromechanical):
Limit and torque setting is performed via switches in the actuator.
●Non-Intrusive version (control unit: electronic):
Limit and torque setting is performed via the controls, without removal of actu-
ator or actuator controls covers.For this purpose, the actuator is equipped with
anMWG (magnetic limit and torque transmitter), also capabletosupplyanalogue
torque feedback signals/torque indication and analogue position feedback sig-
nals/position indication at the actuator controls output.
12
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
Identification ACExC 01.2 Non-Intrusive ModbusTCP/IP

3. Transport, storage and packaging
3.1. Transport
For transport to place of installation, use sturdy packaging.
Hovering load!
Risk of death or serious injury.
→Do NOT stand below hovering load.
→Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
→Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
→Actuatorsmountedtogearboxes:Attachropesorhooksforthepurposeoflifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.
→Actuators mounted to controls: Attach ropes or hooks for the purpose of lifting
by hoist only to the actuator and NOT to the controls.
→Respect total weight of combination (actuator, actuator controls, gearbox, valve)
→Secure load against falling down, sliding or tilting.
→Perform lift trial at low height to eliminate any potential danger e.g.by tilting.
Figure 8: Example: Lifting the actuator
Table 4:
Weight for ACExC 01.2 actuator controls
Weight approx. [kg]with electrical connection type:
14AUMA Ex plug/socket connector with screw-type terminals (KT)1)
12AUMA Ex plug/socket connector with screw-type terminals (KP)
14AUMAEx plug/socketconnector withterminal blocks(KES),increased
safety Ex e
16.5AUMAEx plug/socketconnector withterminal blocks(KES),increased
safety Ex d
Standard1)
13
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive ModbusTCP/IP Transport, storage and packaging

Table 5:
Weights for part-turn actuators SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2
with 3-phase AC motors
Weight with base and lever2)
Weight 1)
Type designation
Actuator approx. [kg]approx. [kg]
3429SQEx 05.2/
SQREx 05.2
3429SQEx 07.2/
SQREx 07.2
3834SQEx 10.2/
SQREx 10.2
5042SQEx 12.2/
SQREx 12.2
6251SQEx 14.2/
SQREx 14.2
Indicated weight includes AUMA NORM part-turn actuator with 3-phase AC motor, electrical con-
nection in standard version, unbored coupling and handwheel.For other output drive types, heed
additional weights.
1)
lndicated weight includes AUMA NORM part-turn actuator with 3-phase AC motor, electrical connec-
tion in standard version, and handwheel, including base and lever. For other output drive types,
heed additional weights.
2)
Table 6:
Weights for part-turn actuators SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2
with 1-phase AC motors
Weight with base and lever2)
Weight 1)
Type designation
Actuator approx. [kg]approx. [kg]
3933SQEx 05.2/
SQREx 05.2
3933SQEx 07.2/
SQREx 07.2
4339SQEx 10.2/
SQREx 10.2
5547SQEx 12.2/
SQREx 12.2
6756SQEx 14.2/
SQREx 14.2
Indicated weight includes AUMA NORM part-turn actuator with 1-phase AC motor, electrical con-
nection in standard version, unbored coupling and handwheel.For other output drive types, heed
additional weights.
1)
Indicated weight includes AUMA NORM part-turn actuator with 1-phase AC motor, electrical con-
nection in standard version, and handwheel, including base and lever.For other output drive types,
heed additional weights.
2)
3.2. Storage
Danger of corrosion due to inappropriate storage!
→Store in a well-ventilated, dry room.
→Protect against floor dampness by storage on a shelf or on a wooden pallet.
→Cover to protect against dust and dirt.
→Apply suitable corrosion protection agent to uncoated surfaces.
Damage on display caused by temperatures below permissible level!
→AC actuator controls MUST NOT be stored below –30 °C.
Long-term storage For long-term storage (more than 6 months), observe the following points:
14
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
Transport, storage and packaging ACExC 01.2 Non-Intrusive Modbus TCP/IP

1. Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:
Check for corrosion.If first signs of corrosion show, apply new corrosion protec-
tion.
3.3. Packaging
Our products are protected by special packaging for transport when leaving the
factory.The packaging consists of environmentally friendly materials which can easily
be separated and recycled.We use the following packaging materials: wood,
cardboard, paper, and PE foil.For the disposal of the packaging material, we
recommend recycling and collection centres.
15
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive ModbusTCP/IP Transport, storage and packaging

4. Assembly
4.1. Mounting position
The product described in this document can be operated in any mounting position.
Restriction:When using oil instead of grease within the actuator gear housing, the
hollow shaft mounting position must be perpendicular, with the flange pointing
downward.The type of lubricant used is indicated on the actuator name plate (short
designation F...= grease; O...= oil).
4.2. Handwheel fitting
Figure 9: Handwheel
[1] Spacer
[2] Input shaft
[3] Handwheel
[4] Retaining ring
1. If required, fit spacer [1] onto input shaft [2].
2. Slip handwheel [3] onto input shaft.
3. Secure handwheel [3] using the retaining ring [4] supplied.
Information The retaining ring [4] (together with these operation instructions) is stored in a
weatherproof bag, which is attached to the device prior to delivery.
4.3. Part-turn actuator to valve: mount
Danger of corrosion due to damage to paint finish and condensation!
→Touch up damage to paint finish after work on the device.
→After mounting, connect the device immediately to electrical mains to ensure
that heater minimises condensation.
The part-turn actuator is mounted to the valve using a coupling (standard) or via
lever. Separate instructions are available for actuator mounting to the valve when
equipped with base and lever.
16
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
Assembly ACExC 01.2 Non-Intrusive ModbusTCP/IP

4.3.1. Output drive for coupling
Design Figure 10:Valve attachment via coupling
[1] Actuator worm wheel with internal splines
[2] Splined plug-in coupling
[3] Valve shaft (example with key)
Application ●For valve attachments according to EN ISO 5211
●For rotating, non-rising valve stem
4.3.1.1. Part-turn actuator (with coupling): mount to valve
Unbored couplings or couplings with pilot bore must be machined to match the valve
shaft prior to mounting the part-turn actuator to the valve (e.g.with bore and keyway,
two-flat or square bore).
Information Assemble valve and part-turn actuator in the same end position. As standard, the
part-turn actuator is supplied in end position CLOSED.
●Recommended mounting position for butterfly valves:End position CLOSED.
●Recommended mounting position for ball valves: End position OPEN.
Assembly steps 1. If required, move part-turn actuator in same end position as valve using the
handwheel.
2. Clean mounting faces, thoroughly degrease uncoated mounting surfaces.
3. Apply a small quantity of grease to the valve shaft [2].
17
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive ModbusTCP/IP Assembly

4. Place coupling [1] onto valve shaft [2] and secure against axial slipping by using
a grub screw [3] or a clamping washer and a screw with curved spring lock
washer [4].Thereby, ensure that dimensions X,Y or L are observed (refer to
figure and table <Mounting positions for coupling>).
Figure 11: Examples: Fit coupling
[1] Coupling
[2] Valve shaft
[3] Grub screw
[4] Clamping washer and screw with curved spring lock washer
Figure 12: Mounting positions for coupling
Table 7:
Mounting position of the coupling within fitting dimensions according to AUMA definition
SQEx 14.2SQEx 12.2SQEx 10.2SQEx 07.2SQEx 05.2Dimensions [mm]
F6F14F14F12F12F10F10F07F05F07F05EN ISO 5211
88554433333X max.
101010105522222Y max.
125751016182506640404040L max.
5. Apply non-acidic grease at splines of coupling (e.g.Gleitmo by Fuchs).
18
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
Assembly ACExC 01.2 Non-Intrusive ModbusTCP/IP

6. Fit part-turn actuator.If required, slightly turn part-turn actuator until splines of
coupling engage.
Figure 13:
Information Ensure that the spigot (if provided) fits uniformly in the recess and that the flanges
are in complete contact.
7. If flange bores do not match thread:
7.1 Slightly rotate handwheel until bores line up.
7.2 If required, shift part-turn actuator by one tooth on the coupling.
8. Fasten part-turn actuator with screws.
Information: We recommend applying liquid thread sealing material to the
screws to avoid contact corrosion.
9. Fasten screws crosswise to a torque according to table.
Table 8:
Tightening torques for screws
Tightening torque [Nm]Threads
Strength class A2-80/A4–80
10M6
24M8
48M10
82M12
200M16
392M20
19
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive ModbusTCP/IP Assembly

4.4. Mounting positions of local controls
Figure 14: Mounting positions
The mounting position of the local controls is implemented according to the order.
If, after mounting the actuator to the valve or the gearbox on site, the local controls
are in an unfavourable position, the mounting position can be changed at a later
date.Four mounting positions shifted by respectively 90° are possible (by maximum
180° into one direction).
4.4.1. Mounting positions: modify
Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
→Before opening, ensure that there is no explosive gas and no voltage.
→Handle cover and housing parts with care.
→Joint surfaces must not be damaged or soiled in any way.
→Do not jam cover during fitting.
Electrostatic discharge ESD!
Risk of damage to electronic components.
→Earth both operators and devices.
1. Loosen screws and remove the local controls.
2. Check whether O-ring is in good condition, correctly insert O-ring.
3. Turn local controls into new position and re-place.
Cable damage due to twisting or pinching!
Risk of functional failures.
→Turn local controls by a maximum of 180°.
→Carefully assemble local controls to avoid pinching the cables.
4. Fasten screws evenly crosswise.
20
SQEx 05.2 –SQEx 14.2 / SQREx 05.2 –SQREx 14.2 Control unit: electronic (MWG)
Assembly ACExC 01.2 Non-Intrusive ModbusTCP/IP
Other manuals for SQEx 05.2
5
This manual suits for next models
9
Table of contents
Other AUMA Controllers manuals

AUMA
AUMA SAEx 07.2 User manual

AUMA
AUMA SA Series User manual

AUMA
AUMA SA Series User manual

AUMA
AUMA SAI 07.2 User manual

AUMA
AUMA Profibus PBD 100 User manual

AUMA
AUMA SAEx 07.2 User manual

AUMA
AUMA SAVEx 07.2 User manual

AUMA
AUMA SA 07.1 Administrator Guide

AUMA
AUMA SAEx 25.1 User manual

AUMA
AUMA PROFOX PF-M25 User manual

AUMA
AUMA SA 25.1 User manual

AUMA
AUMA SG 05.1 User manual

AUMA
AUMA PROFOX PF-M25X User manual

AUMA
AUMA SA3-SA100 User manual

AUMA
AUMA AM 01.1 User manual

AUMA
AUMA SAI 6 User manual

AUMA
AUMA SAM Ex 07.1 User manual

AUMA
AUMA SAVEx 07.2 User manual

AUMA
AUMA SGExC 05.1 User manual

AUMA
AUMA Aumatic AC 01.1 User manual