1. Product information
• Multisensor (presence, temperature, brightness detection)
for connection to proprietary bus systems
• Output of the current light and temperature value as
analog voltage
• Low noise Reed Relays
• Other functions via remote control adjustable
2. Operation
The presence detector has sensors for presence;
Temperature and brightness detection which are suitable for
connection to proprietary bus systems. The output of the signals
takes place by analog voltage values 0-10V (10LUX = 0.1 V,
0.5 ° C = 0.1 V) at the output terminals. For evaluating the
motion detection a floating reed relay is still available.
3. Safety information
Work on the mains supply may only be carried out by
qualified professionals or by instructed persons under the
direction and supervision of qualified skilled electrical
personnel in accordance with electrotechnical regulations.
Disconnect supply before installing!
This device is not suitable for disconnection.
4. Montage
A circular opening of diameter 68 mm must first of all be
produced in the ceiling.
1
4
68 mm
3
2
1) Using the sensor
2) Cover slat (if necessary)
3) Protective cover
4) Ceiling
(68 mm diameter hole, drilled)
Having connected up the cables in accordance with regulations,
the detector is inserted into the opening as shown in the
drawing opposite and fixed into position with the assistance
of the spring clip.
5. Hardware configuration FC
Position LED’s and potentiometer
LUX-0 LUX-I
TIME
15s
30s
1min.
1s
2
5
10
15
30
TEMP
+−
0
Potentiometer (A): Potentiometer Brightness adjustment LUX-0
Potentiometer (B): Potentiometer Follow-up time
Potentiometer (C): Potentiometer Temperature setting TEMP
Potentiometer (D): Potentiometer Brightness adjustment LUX-I
LED I: red
Sensor
(
LUX-0
)
: Brightness
Sensor
(
LUX-I
)
: Brightness
Sensor (1) : Temperature
6. Self test cycle/Startup behavior
The product enters an initial 60-second self-test cycle, when the
supply is first connected. During this time the device does not
respond to movement and stays on.
7. Putting into operation / Settings
Adjustment follow-up time “motion detection“
TIME
15s
30s
1min.
1s
2
5
10
15
30
The follow-up time can be set from 1 sec to 30 min.
Brightness adjustment LUX-0
LUX-0 The potentiometer LUX-0 can set fine adjustment of
the light output value
Brightness adjustment LUX-I
LUX- I The potentiometer LUX-I can set fine adjustment of the
light output value
Temperatur Offset
TEMP
+
0
With potentiometer TEMP, an offset can be set
(+4 ° C to -4 ° C)
8.1 Brightness adjustment
With the potentiometers LUX 0 and LUX-I, the output voltage of
the 0-10V output of + / - 10% change and the slope of the lux /
VDC curve can be adjusted. Losses caused by cable lengths can
be compensated.
5 V
10 V
500 lux 1000 lux LUX
VDC
Potentiometer 2
(LUX)
8.2 Brightness value output as a voltage value`the LUX-terminal
The brightness value output corresponds each 10LUX = 0.1 V
The brightness measurement includes the area between 0LUX =
0V to 10V = 1000 lux
An update of the measured values are approximately every
0.5 s
0
5
10
500 1000 LUX
VDC
8.3 Temperature adjustment
With the TEMP potentiometer output voltage can be offset bet-
ween -4ºC (-0.8V) to 4ºC (0.8V) regarding to the temperature
measured by the temperature sensor in order to compensate
the measurement of the sensor depending where the device
is placed. The neutral position of the potentiometer is marked
with an arrow where the 0 offset is.
5 V
10 V
25 50 C°
VDC
Potentiometer
8.4 Temperature value output as a voltage value
to the TEMP terminal
The temperature value output corresponds each 0.5 ° C = 0.1
V. The temperature range is the range between 0 ° C = 0 V
and goes to 50 ° C = 10V is done to update the readings
approximately every 10s
0
5
10
25 50 °C
VDC
9. Motion detection
The motion sensor turns on the relay with active motion and
turns off when the unit detects no movement and the follow-up
time has expired. After switching off the motion detection for
about 2s is deactivated to prevent an unwanted power up
again. An update of the measured values are approximately
every 20ms.
(D)
(A) (B) (C)
I
LUX-0
1
!
!
!
LUX-I
Sensor
4
PD4N-LTMS-RR
10. Exclude sources of interference
+=
If the detection zone is too large, or areas covered that should
not be monitored, use the blinds to reduced or limited those
areas.
11. Range of Coverage
24 m
8 m
6,40 m
24 m
360°
2,50 m
walking towards
walking across
seated
1
2
3
1
2
12. Technical data
Power supply: 16-48 VDC
Power consumption: < 1W
Ambient temperature: 0°C to +50°C
Degree of protection
/class: IP20 / II
Settings: Potentiometer and
Remote control
LUX-/TEMP-Output: 0-10 V ± 200 mV,
10 mA max.
Light values
Sensitivity: 0 - 1000 Lux, ± 20 Lux
Light measurement: ca.10 mV/Lux
Temperature values: 0°C - +50°C, ± 0,5°C
Sensitivity
Temperature values: ca.200 mV/°C
Area of coverage: circular 360°
Range of coverage
Ø H 2,50 m /
T = 18°C: seated 6,40
m
/
tangential 24m /
radial 8 m
Recommended height
for mounting: 2 - 3 m
Light measurement: mixed light
Motion detector: potential-free contact NO, µ
Contact load:
max. 48 VDC, 100mA, cos φ=1
Time setting (Channal 1): Potentiometer
1s. - 30 min.
Remote control
5s - 1h or Impuls function
Connection: single wire (not stranded)
0,34... 1,5 mm²
single conductor
Cable length: max. 100 m*
*Avoid paralell wiring to power cables. If a separatetd installa-
tion is not possible, the use of shielded cables is recommended
Dimensions H x Ø [mm] 34 x 93 mm
Visible portion
when built into ceiling: 20 x 83 mm
Sensor and power supply in one case
Declaration of Conformity:
This product respects the directives concerning
1. electromagnetic compatibility (2014/30/EU)
2. low voltage (2014/35/EU)
3. restriction of the use of certain hazardous substances in
electrical and electronic equipment (2011/65/EU)
13. Article / Part nr. / Accessory
Typ FC
PD4N-LTMS-RR 92709
LUXOMAT®Remote control:
IR-LTMS (incl. wall bracket) 92185
Accessory:
BSK Ball basket guard 92199
14. LED function displays
LED function indicators
Operating state LED function indicators
Initialization 60s initialization, red ashes 2x in
the second
Active red lights on when motion is
detected
Resetting the Temperature potentiometer on neutral, LED lights
up for 2 seconds.
15. Connections
X1, X2: Auswertungseinheiten/-geräte
+
-
+
X1
X2
-NO NO TEMP LUX
16-48 VDC
16-48V 0-10V 0-10V
16. Putting into operation of the remote control
IR-LTMS (optional)
IR-LTMS
B.E.G. LUXOMAT®
CDS
1CDS
0CDS
1+0 5
sec
10
sec 20
sec 30
sec 1
min 5
min
10
min 15
min 30
min 1h RESET
T++ T+ T-- T-
LED
on/off TEST
C
M
Y
CM
MY
CY
CMY
K
xxxx_IR-LTMS.pdf 1 06.06.2014 12:06:35
IR-LTMS
Wall bracket for remote
control IR-LTMS
17. Settings by remote control when open
Explanation of the remote control button
functions
CDS
1Factory setting: In this setting, the light measurement take
place over light sensor LUX-0
CDS
0In this setting, the light measurement takes place via light
sensor LUX-I
CDS
1+0 In this setting, the light measurement take place over an
average of the two light sensors.
Impuls function
5
sec
1h
Follow-up time
RESET
Reset in the open state: Deletes all values set with the
remote control, Potentiometer settings apply.
Resetting when closed: End all active follow-up Timer
T++ Increase the temperature offset to +1°C (0,2V)
T+ Increase the temperature offset to +0,5°C (0,1V)
T-- Reduce the temperature offset to -1°C (0,2V)
T- Reduce the temperature offset to -0,5°C (0,1V)
This function permanently blocks the reception of remote
control signals. This function can be activated within 5
sec. after closing the detector. To unlock see 18. Reset the
permanent sabotage protection
Normal sensitivity
High sensitivity
LED
on/off Activate or deactivate the LED display
TEST
Test mode, only dependent on movement. With every
movement switches the light for 2 seconds ON, then for 2
sec. OFF. After 3min. Test mode is automatically terminated
and returns to normal operating mode.
To turn the light on and off manually by pressing the button
briey. The light will remain on or off as people are detec-
ted plus the follow-up time.
18. Reset the permanent sabotage protection
If the permanent sabotage protection is activated, the detector can
be released again as follows:
• Switch off the power supply and switch it back on
• Switch the power supply off again after 31 seconds of the
initialization and before 59 seconds
• Apply power again and wait for for the self testing
• Press the unlock
19. Selection of the light sensors
The product PD4N-LTMS-RR used a a light sensor, to determine
the brightness value by default, which is located in the outer
cover ring. Through this arrangement, results a selective range,
where the light measurement takes place. For a enlargement of
the selective measurement range, a second light sensor (behind
the lens) can be switched on or get individually activated by the
optional remote control.
Sensor
(
LUX-0
)
Light sensor in the cover ring (Factory setting)
Sensor
(
LUX-1
)
Light sensor behind the lens
20. LED-functional indicators
LED function indicators
Operating state LED function indicators
Remote control signal LED ashes briey
Detector close LED shines 5 sec.
8355_Op_MAN_PD4N-LTMS-RR-DE_92709_en_V2 28.06.2019
Resetting
when open:
Deletes
all values set
with the remote
control, light OFF.
Potentiometer
and DIP switches
are enabled for
setting.
CDS
1CDS
0CDS
1+0
5
sec at 1h
T++ T+ T-- T-
or
LED
on/off
t < 5 s
max
50
Lux
1500
Lux
ON
OFF
X1, X2: Evaluation units/-devices

Other B.E.G. Security Sensor manuals

B.E.G. LUXOMAT PD4-S-DAA4G User guide

B.E.G.

B.E.G. LUXOMAT PD4-S-DAA4G User guide

B.E.G. LUXOMAT Indoor 180-R User manual

B.E.G.

B.E.G. LUXOMAT Indoor 180-R User manual

B.E.G. LUXOMAT PD9-M-DIM User guide

B.E.G.

B.E.G. LUXOMAT PD9-M-DIM User guide

B.E.G. LUXOMAT PD11-KNX-FLAT-DX How to use

B.E.G.

B.E.G. LUXOMAT PD11-KNX-FLAT-DX How to use

B.E.G. LUXOMAT PD2-M-DALI/DSI-SM/FC User guide

B.E.G.

B.E.G. LUXOMAT PD2-M-DALI/DSI-SM/FC User guide

B.E.G. MINI-S-PP-FC User guide

B.E.G.

B.E.G. MINI-S-PP-FC User guide

B.E.G. Luxomat PICO-M-1C-FC User guide

B.E.G.

B.E.G. Luxomat PICO-M-1C-FC User guide

B.E.G. LUXOMAT PD2N-KNX-ST-UP User manual

B.E.G.

B.E.G. LUXOMAT PD2N-KNX-ST-UP User manual

B.E.G. LUXOMAT PD4-DIM User guide

B.E.G.

B.E.G. LUXOMAT PD4-DIM User guide

B.E.G. LUXMAT PD4-S User guide

B.E.G.

B.E.G. LUXMAT PD4-S User guide

B.E.G. LUXOMAT PD4-M-1C-C-SM User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-1C-C-SM User guide

B.E.G. LUXOMAT PD4-M-1C-GH-AP User manual

B.E.G.

B.E.G. LUXOMAT PD4-M-1C-GH-AP User manual

B.E.G. LUXOMAT Indoor 180-SC Service manual

B.E.G.

B.E.G. LUXOMAT Indoor 180-SC Service manual

B.E.G. RC-plus next 130 Service manual

B.E.G.

B.E.G. RC-plus next 130 Service manual

B.E.G. LUXOMAT PD4-M-2C-DUO User manual

B.E.G.

B.E.G. LUXOMAT PD4-M-2C-DUO User manual

B.E.G. LUXOMAT RC-plus next N-230 KNX-DX User manual

B.E.G.

B.E.G. LUXOMAT RC-plus next N-230 KNX-DX User manual

B.E.G. LUXOMAT PD4-M-DIM-Corridor User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-DIM-Corridor User guide

B.E.G. LUXOMAT BL2 User manual

B.E.G.

B.E.G. LUXOMAT BL2 User manual

B.E.G. LUXOMAT PD4-M-1C-SM User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-1C-SM User guide

B.E.G. LUXOMAT PD4-BMS User manual

B.E.G.

B.E.G. LUXOMAT PD4-BMS User manual

B.E.G. KNX RC-plus next 230 KNX Service manual

B.E.G.

B.E.G. KNX RC-plus next 230 KNX Service manual

B.E.G. LUXOMAT PD4-M-1C-C-PS User manual

B.E.G.

B.E.G. LUXOMAT PD4-M-1C-C-PS User manual

B.E.G. LUXOMAT PD4-S-DAA4G User guide

B.E.G.

B.E.G. LUXOMAT PD4-S-DAA4G User guide

B.E.G. LUXOMAT PD4-M-DIM-Corridor Series User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-DIM-Corridor Series User guide

Popular Security Sensor manuals by other brands

Elmes Electronic PTX50 quick start guide

Elmes Electronic

Elmes Electronic PTX50 quick start guide

SEB RGDAT-A70 user manual

SEB

SEB RGDAT-A70 user manual

Major tech MT980 instruction manual

Major tech

Major tech MT980 instruction manual

INSTEON TriggerLinc 2843-2 quick start guide

INSTEON

INSTEON TriggerLinc 2843-2 quick start guide

EMS FireCell FCX-170-001 installation guide

EMS

EMS FireCell FCX-170-001 installation guide

Philips OccuSwitch LRM1771 installation guide

Philips

Philips OccuSwitch LRM1771 installation guide

KWB SAFETY FIXX 011620 Instructions for use

KWB

KWB SAFETY FIXX 011620 Instructions for use

Medclair NOD DU4000-M2 user manual

Medclair

Medclair NOD DU4000-M2 user manual

PCB Piezotronics 200C50 Installation and operating manual

PCB Piezotronics

PCB Piezotronics 200C50 Installation and operating manual

Crestron GLS-PLS-120 quick start guide

Crestron

Crestron GLS-PLS-120 quick start guide

AMT AMT-LX218 Service manual

AMT

AMT AMT-LX218 Service manual

System Sensor WFD20A Installation instruction

System Sensor

System Sensor WFD20A Installation instruction

Gira 2050 Series operating instructions

Gira

Gira 2050 Series operating instructions

AJAX ReX manual

AJAX

AJAX ReX manual

Siemens AS Series manual

Siemens

Siemens AS Series manual

ABB Orion1 Base Excerpts From the Instruction Manual

ABB

ABB Orion1 Base Excerpts From the Instruction Manual

OPTEX FA V Series instruction manual

OPTEX FA

OPTEX FA V Series instruction manual

Dectris PILATUS3 R Technical Specifications and Operating Procedure

Dectris

Dectris PILATUS3 R Technical Specifications and Operating Procedure

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.