Operating and mounting Instruction for B.E.G. -Occupancy detector as wallswitch Indoor 180/R-2W UK
B.E.G.
LUXOMAT®Indoor 180/R-2W UK
GB
CAUTION: Have all work involving the 230 VAC mains supply
carried out by a qualied electrician!
Before starting disconnect the mains !
Article detection angle Part.-Nr.
Indoor 180R 2W UK 180° 92615
1. Product description
The LUXOMAT®Indoor 180-R/2W UK is a occupancy detec-
tor designed for ush-mounting in indoor lighting applications.
The Indoor 180 utilizes infrared- and accoustic- sensing
technology to detect the presence and movement of persons
(as well the infrared-radiation of larger animals and objects).
The sensor contains 2 red LEDs:
LED 1 for indication of
movements (in normal operation)
lux-level (in TEST mode)
LOW BATTERY/2hr charging status
LED 2 for sound indication
LED-2
Sound
LED-1
Movement/Lux-level
Low Battery
Furthermore it contains a twilight (Lux) sensor, a microphone
and a timer.
Lux-level , microphone and timer can be set here:
remove top cover as shown, this will give access to the controls.
Please follow the markings on the at top of the lens for
adjustment.
Function:
(Assuming the unit is switched OFF, 230VAC is present and
battery is charged).
Once the set twilight level is reached (=dark), the Indoor 180
will react only to detected movements and turn ON the relay,
thus illuminating the room, until no further movements or sounds
are detected and the internal timer elapses.
Once switched ON, each detected movement and/or sound will
restart the timer interval thus prolonging the ON-period.
Once the relay is switched OFF, the accoustic sensor remains
active for another 8-10 sec, to allow the relay to be re-triggered
by sounds or noises into ON state within this period.
2-wire installation:
The Indoor 180-R/2W-UK model has been specically designed
to replace manually operated light-switches in so called 2-wire
installation.
2-wire installations pose the problem, that once the relay turns
ON the connected luminaires, the powersupply for the sensor
is cut-off.
The solution to this problem is the use of a rechargeable battery,
which will be charged while the luminaires are OFF and which
will supply the sensor while the luminaires are switched ON.
In ON state the sensor will draw power from the battery and
constantly monitor the battery voltage.
Once the battery voltage drops to a dened LOW-BATTERY
value, the sensor will switch OFF the relay and enforce a
2hrs long charging period.
The LED-1 will quickly ash!
(Please note: during this 2hrs-period , the unit remains OFF and
will not react to any movement or sound)
If no mains supply is present, the battery will discharge further
and at some point in time the deep-discharge protection will kick
in and shut down the sensor entirely.
2. Prior to Installation
Before installation the following has to be considered:
• The LUXOMAT®Indoor 180 is designed for the
installation in standard switch ushmount boxes.
• The recommended xing height is 1.10 - 2.2m
• No parallel installation of units is allowed/
recommended.
• The connect luminaire load must not exceed
Ohmic load 3000W, 10 A, cosϕ= 1
Inductive load 1500 VA, 5 A, cosϕ= 0.5
Electronic ballast 35x 50W 140 uF max.
• There must be no obstacles in the view of the sensor, since
infrared rays cannot penetrate solid materials.
• The LUXOMAT® Indoor 180 is an automatic light
switch which cannot be used in intrusion applications.
The minimum load must exceed 50 W. If not, please
install the capacitor.
3. Installation
The 230VAC mains to be switched OFF
The LUXOMAT® Indoor 180 ts into a standard ushmounting
box. The location height on the wall should be between
1.10 - 2.20 m.
LUX
TIME
MIC-SOUND
RESET
L
N
Connect wiring as shown:
Note:
There is a pre-inserted shunt (thick wire) .
In normal operation this shunt must be installed!
Do not remove!
Setting into operation:
Note:
The battery is in most cases discharged due to prolonged period
of storage and requires charging!
Once connections are in place and the unit is securely fastened,
turn on mains supply.
Scenario A:
Battery is discharged! - Lights remain OFF!
LED-1 shall light up and ash quickly to indicate
LOW BATTERY and sensor will remain for 2hrs in charging
mode = relay OFF.
Scenario B:
Battery is sufciently charged! - Lights turn ON
LED-1 shall light up and ash slowly for start-up period of
60secs. After start-up period unit is operational.
Scenario C:
Battery is discharged! - BUT light turn ON!!
LED-1/LED-2 do not ash , relay does not switch!
In this unlikely case the unit cannot recover without removing the
SHUNT:
Turn OFF 230 VAC mains supply and remove shunt, than
reconnect 230VAC.
Without shunt installed , the load is disconnected from the relay
and regardless of relay state , charging should resume and LED-
1 should ash quickly (perhaps with some delay) .
Actions in scenarios A + C:
Let the unit charge for approx. 10mins.
The battery shall have recharged sufciently to allow a few
minutes of sensor operation.
Than for Scenario C , disconnect 230VAC and install shunt ,
and connect 230VAC again.
For A + C now press the RESET button (near MIC control). Since
the battery is charged to nominal voltage, the unit will reset and
enter the start-up period (LED-1 slow ashing).
After 60 secs the unit is operational and settings can be
performed as described below.
Fig.2
Fig.1Fig.3
230VAC ± 10% , 50-60Hz
2300W/10A/cos=1
1150VA/5A/cos=0.5
LUXOMAT®
INDOOR 180-R/2W-UK
IP20
LAB1807
LL'
contains RECHARGEABLE BATTERIES:
6 xNiMH/30AAAAH
1.2V/300mAh
LAB1809
Shunt
ON OFF
ON OFF
SAttention:
Before installation switch S is
to be put in position „ON“
(left)!
Fig.4
4. Adjustments of twilightswitch / timer and
acoustic-sensor
Twilightswitch (LUX)
The twilight-level can be set between approx.
40 to 2000 Lux.
Symbol : Night operation (dark only)
Symbol Day and night operation
Timer (R1)
• The delay timer can be adjusted from
15 sec to 16 min
• TEST:
Use this mode for setting up operation.
Every movement will cause relay to switch
ON for 1sec and than OFF again: walktest
LED-1 shows the current lux-level:
LED-1 = ON = bright
LED-1 = OFF = dark
• Symbol Pulse/chime function.
Every motion will turn ON relay for 1 sec
followed by a pause.
(the next pulse can only occur after pause!)
In pulse mode , there is no need for MIC/
acoustic detection. The MIC-control has
therefor an alternative function, it determines
the duration of pause following a pulse:
MIC-control = min = 9 sec
MIC-control = 50% = 30sec
MIC-control = max = 60sec
5. Wiring diagrams:
6. Technical data
• Supply voltage 230 VAC ±10%
• Accu 6 x NiMH/ 30 AAAAH
1,2 V/300mAh
• Detection angle 180° horizontally
approx. 60° vertically
• Range max. in m across 10.00 m
• Switching power
Ohmic load 3000W, cosϕ= 1
Inductive load 1500VA, cosϕ= 0.5
Electronic ballast 35x 36W
• Time settings 15 sec to 16 min
or Impuls
• Twiglight switch 5 - 2000 Lux
• Dimensions LxW 87 mm x 87 mm
Depth 61mm
• Ambient temperature: +5°C to +45°C
• Protection / class IP 20 / II / CE
• Enclosure material Housing of high grade UV- and
shock-resistant Polycarbonate
• Minimum Load 50 W
7. Electromagnetic Compliance (EMV)
When positioned within direct vicinity of high powered radio
transmitting equipment (e.g. portable phones , H.A.M., taxi,
police,  re, ambulance radio operators etc.) false activation
switching may be experienced. However, this in uence will not
damage the sensor electronics.
The automatic switching of the sensor will sease as soon as the
source of radio interference stops transmitting.
MAN 6940 – 100214-2
40
200
600
1200
2000
Tes
15
30
1
2
5
10
16
Mic
8. Trouble shooting - Practical hints
1. Lamp does not light up
Cause:
Action:
Tungsten halogen lamp defective
- Replace tungsten halogen lamp
No mains connection
- Check connection by qualified electrician
Incorrect setting of lux level
- Correct setting of lux level
Unit mounted too high
- Mount at recommended height
PIR detector lens obstructed by dirt or other objects
- Clean lens or remove objects
Main fuse defective
- Check or replace by qualified electrician
2. Delayed lamp activation
Mounted too high
- Mount at height stated in specification
(1.2 to 2.2m)
Direct line of approach
- Re-direct walking so that the approach is not frontally
3. Lamp stays on continuously
Continual thermal activity detected ie. extractor fan, central
heating ducts
- Check for any activity which could cause unit detection to be
maintained
Delay time set too high
- Reduce time delay
- Check ambient noiselevel, if necessary switch off noisesources
4. Limitation of range (not up to the minimum speci cation)
Mounted too high
- Correct mounting height
Temperature difference between ambient temperature and
source of heat too small
No improvement possible
Direction of movement aimed directly at lens of motion detector
Move laterally to detector
Fig.5
B.E.G.
12 m
3 m
10 m
180°
1.10 - 2.20 m

This manual suits for next models

1

Other B.E.G. Security Sensor manuals

B.E.G. LUXOMAT PD4-S-GH Firmware update

B.E.G.

B.E.G. LUXOMAT PD4-S-GH Firmware update

B.E.G. LUXOMAT PD4-M-DIM-Corridor User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-DIM-Corridor User guide

B.E.G. LUXOMAT PD2-M-2C User manual

B.E.G.

B.E.G. LUXOMAT PD2-M-2C User manual

B.E.G. LUXOMAT PD3-1C User guide

B.E.G.

B.E.G. LUXOMAT PD3-1C User guide

B.E.G. LUXOMAT BL2 User manual

B.E.G.

B.E.G. LUXOMAT BL2 User manual

B.E.G. LUXOMAT PD9-M-2C User guide

B.E.G.

B.E.G. LUXOMAT PD9-M-2C User guide

B.E.G. LUXOMAT net PD11-KNX-FLAT-BA User manual

B.E.G.

B.E.G. LUXOMAT net PD11-KNX-FLAT-BA User manual

B.E.G. LUXOMAT RC-plus next N-230 KNX-DX User manual

B.E.G.

B.E.G. LUXOMAT RC-plus next N-230 KNX-DX User manual

B.E.G. LUXOMAT Indoor 180-M-2C User guide

B.E.G.

B.E.G. LUXOMAT Indoor 180-M-2C User guide

B.E.G. LUXOMAT PD4-BMS User manual

B.E.G.

B.E.G. LUXOMAT PD4-BMS User manual

B.E.G. LUXOMAT LC-Click 140 Owner's manual

B.E.G.

B.E.G. LUXOMAT LC-Click 140 Owner's manual

B.E.G. LUXOMAT PD4N-KNX-K-DX How to use

B.E.G.

B.E.G. LUXOMAT PD4N-KNX-K-DX How to use

B.E.G. LUXMAT PD4-S User guide

B.E.G.

B.E.G. LUXMAT PD4-S User guide

B.E.G. Luxomat PICO-M-1C-FC User guide

B.E.G.

B.E.G. Luxomat PICO-M-1C-FC User guide

B.E.G. Luxomat PD2-DIM Series User manual

B.E.G.

B.E.G. Luxomat PD2-DIM Series User manual

B.E.G. LUXOMAT PD4-M-1C Series User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-1C Series User guide

B.E.G. Luxomat PD2-S User manual

B.E.G.

B.E.G. Luxomat PD2-S User manual

B.E.G. LUXOMAT PD4-M-TRIO-2DALI DSI-1C Wiring diagram

B.E.G.

B.E.G. LUXOMAT PD4-M-TRIO-2DALI DSI-1C Wiring diagram

B.E.G. LUXOMAT PD4-M-DIM-SM User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-DIM-SM User guide

B.E.G. LUXOMAT PD4-M-2C-C Series User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-2C-C Series User guide

B.E.G. LUXOMAT PD4-M-DIM-Corridor Series User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-DIM-Corridor Series User guide

B.E.G. LUXOMAT PD5-M-1C-Clip User guide

B.E.G.

B.E.G. LUXOMAT PD5-M-1C-Clip User guide

B.E.G. RC-plus next 130 Service manual

B.E.G.

B.E.G. RC-plus next 130 Service manual

B.E.G. LUXOMAT PD4-S-DAA4G User guide

B.E.G.

B.E.G. LUXOMAT PD4-S-DAA4G User guide

Popular Security Sensor manuals by other brands

Whelen Engineering Company 2022 Series installation guide

Whelen Engineering Company

Whelen Engineering Company 2022 Series installation guide

Apollo 55000-268 quick start guide

Apollo

Apollo 55000-268 quick start guide

Elko iNELS RFSF-100 manual

Elko

Elko iNELS RFSF-100 manual

Velleman PIR40 user manual

Velleman

Velleman PIR40 user manual

STEINEL IS 2180-2 operating instructions

STEINEL

STEINEL IS 2180-2 operating instructions

EMX Industries ULT-MVP instruction manual

EMX Industries

EMX Industries ULT-MVP instruction manual

Visatron VN 115 / 93 operating instructions

Visatron

Visatron VN 115 / 93 operating instructions

Bircher Reglomat ProLoop operating instructions

Bircher Reglomat

Bircher Reglomat ProLoop operating instructions

Velleman HAM841K user manual

Velleman

Velleman HAM841K user manual

INIM Electronics EB0020 manual

INIM Electronics

INIM Electronics EB0020 manual

EMX Industries Ultra II DTEK operating instructions

EMX Industries

EMX Industries Ultra II DTEK operating instructions

ESYLUX MD-C360i/6 mini installation instructions

ESYLUX

ESYLUX MD-C360i/6 mini installation instructions

Watts 709 Series Installation, maintenance & repair

Watts

Watts 709 Series Installation, maintenance & repair

STEINEL Serie IS 180 operating instructions

STEINEL

STEINEL Serie IS 180 operating instructions

Abus PLBW10000 quick guide

Abus

Abus PLBW10000 quick guide

Tecsis P3298 operating instructions

Tecsis

Tecsis P3298 operating instructions

GVS Elipse Integra Instructions for use

GVS

GVS Elipse Integra Instructions for use

Gilson VERITY 1741 user guide

Gilson

Gilson VERITY 1741 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.