
DECS-100 General Information 1-3
Figure 1-2. Typical V/Hz Curves
Contact Input Circuits–continued
Terminal Assignments for Optional Functions
Var/PF Enable: 52J, 52K
Voltage Matching: VM, VMC
Common Alarm Output
Type: Form A
Rated Load: 7 Aac/Adc continuous
Make: 30 Aac/Adc, carry for 0.2 sec
Break: 7 Aac/0.1 Adc
Operating Voltage: 240 Vac/250 Vdc maximum
Terminals: AL1, AL2
Field Output
Field Resistance: 5 Sminimum
Terminals: F+, F–
Continuous Rating: 63 Vdc, 7 Adc
10 Second Forcing Rating
200 Vac Power Input: 135 Vdc, 15 Adc
110 Vac Power Input: 90 Vdc, 10 Adc (9 Sfield)
75 Vdc, 15 Adc (5 Sfield)
AVR Operating Mode
Adjustment Range: See Generator Voltage Sensing
Voltage Regulation: ±0.25% over load range at
rated power factor and
constant generator frequency.
±0.5% with 3-phase sensing
and shunt power at 40% THD
of the voltage waveform (due to
a 6 SCR load).
Temperature Drift: ±0.5% for a 40EC change
V/Hz Characteristic: Slope from 0 to 3PU is adjust-
able in 0.01PU increments.
Transition (Corner) frequency
is adjustable from 40 to 65 Hz.
See Fig. 1-2 for V/Hz curves.
Response Time: Within 1 cycle
FCR (Manual) Operating Mode
Adjustment Range: 0 to 7 Adc
Increment: 0.1 A
Var Operating Mode (Optional)
Adjustment Range: 100% to –100%
Increment: 0.1%
PF Operating Mode (Optional)
Adjustment Range: 0.6 lead to 0.6 lag
Increment: 0.001
Parallel Compensation
Modes: Reactive Droop and Reactive
Differential (cross-current)t
Droop Adjust Range: 0 to 10%
Increment: 1%
tBurden can exceed 1 VA if external resistors are
added to the CT circuit.
Field Overvoltage Protection
Pickup Range: 0 to 250 Vdc
Time Delay: 10 seconds (fixed)
Field Overcurrent Protection
Pickup
Range: 0 Adc to 15 Adc
Increment: 0.001 Adc
Time Delay
Range: 0 to 10 seconds
Increment: 1 second
Generator Overvoltage Protection
Pickup 100% to 120% of system
voltage setting
Increment: 1.0%
Time Delay: 0.75 seconds (fixed)
Soft-Start Function (AVR Mode Only)
Time Adjust Range: 1 to 7,200 seconds
Increment: 1 second
Voltage Matching
Accuracy: Generator rms voltage is
matched with the bus rms
voltage to within ±0.5% of the
generator voltage.
Time Adjustment
Range: 0 to 300 seconds
Increment: 0.01 seconds
Metering (BESTCOMS)
Generator Voltage
Range: 10 V to 79 kV
Accuracy: ±0.5% (at 25EC)
Generator Current
Range: 0.04 to 1,000 A (1 A CTs)
0.1 to 5,000 A (5 A CTs)
Accuracy: ±0.5% (at 25EC)