Factory settings
Menu 6.1: HRG system Menu 6.4: Response values Menu 6.5: System settings
1. Usys (L-L) 400V 1. UNGR trip 60 % 1. Ground-fault relay Mode: Fail-safe
Relay test: on
2. CD-NGRM CD1000 2. INGR trip 60 % 2. NGR relay Mode: Fail-safe
Relay test: on
3. Frequency 50 Hz 3. > RNGR 150 % 3. Trip relay Mode: Fail-safe
4. INGR nom 5 A 4. < RNGR 50 % Relay test: on
5. RNGR nom 470 Ω 5. tNGR trip 0 s 4. Analogue Mode: 4-20 mA
Menu 6.2: CT 6. Ground fault trip on Function: R NGR
1. CT primary 600 7. tGF trip 5 s
5. Dig. in/out
System OUT: Fail-safe
2. CT secondary 1 8. Alarm stored on Pulser OUT: Non-fail-safe
3. CT connection 50 mA 9. trestart 5 s Pulser IN: Active high
Menu 6.3: NGR 10. Restart count 2 RESET IN: Active high
1. Method auto 11.Trip signal RMS TEST IN: Active high
2. PT primary 1 12. Upper limit harmonic 32 6. Buzzer Buzzer alarm: o
3. PT secondary 1 13. Lower limit harmonic 0 Buzzer test: on
Bender GmbH & Co. KG
Londorfer Straße 65 • 35305 Grünberg • Germany
USA, Mexico, Central America • Exton PA, USA
www.bender.org
Canada • Missisauga ON, Canada
www.bender-ca.com
South America • Santiago de Chile
www.bender-latinamerica.com
All rights reserved.
Reprinting and duplicating only with permission of the publisher
Technical data
Rated voltage......................................................................250 V
Overvoltage category............................................................... III
Nominal supply voltage US............................AC/DC, 48…240 V
for UL applications ......................................AC/DC, 48…240 V
for AS/NZS 2081 applications......................AC/DC, 48…230 V
Tolerance Us......................................................................±15 %
Tolerance Us(for UL applications).........................–50…+15 %
Tolerance Us(for AS/NZS 2081 applications).........–25…+20 %
Frequency range Us.............................................DC, 40…70 Hz
Power consumption (max.)................................... ≤ 7 W / 16 VA
Switching elements (Ground-fault, NGR, trip relay)
......... Changeover contacts, configurable fail-safe/non-fail-safe)
Contact data acc. to IEC 60947-5-1
Rated operational voltage ............................... AC 250 V/250 V
Utilisation category ............................................. AC-13/AC-14
Rated operational current AC....................................... 5 A/3 A
Rated operational current AC (for UL applications)....... 3 A/3 A
Rated operational voltage DC..............................220/110/24 V
Utilisation category...........................................................DC12
Rated operational current DC..................................0.1/0.2/1 A
Minimum current .....................................1 mA at AC/DC > 10 V
UL File Number
E173157