DX2010 Installation Instructions
P/N: 49533E Page 4
4.5 Tamper Point/Zone Inputs
This feature is not available for some control/communicators.
Consult your control/communicator’s Installation Instructions.
The DX2010 has the capacity for dual tamper point/zone inputs
utilizing two EOL resistors (using 1.5k or 2.2k Alarm Resistor). See
Figure 11.
5.0 DX2010 LED Operation
The DX2010 LED (Figure 12) flashes to indicate the status of the
device. The LED indications are:
• One flash per second indicates normal operation.
• LED steady ON can indicate any of the following:
- G wire is not connected or there is a communications problem
between the control panel and the DX2010.
- No locations/points are assigned to the DX2010 with this
address. See your control/communicator’s programming
guide for location/point assignment instructions.
- Address on the DX2010 is not set correctly.
• LED OFF indicates that there is no power to the module.
6.0 Setting the DX2010’s Address
Use Table 2 to configure the DX2010’s address. Refer to the control/
communicator’s installation manual to determine the appropriate
address for each DX2010 you connect. Figure 13 shows the DIP
switch configuration.
Each time you change the address DIP switches,
cycle the power to the DX2010 (turn the power off
and then on) for the address change to take effect.
L+COML+
2.2 k
EOL
Resistor
2.2 k
EOL
Resisto
1.5 k or 2.2 k
Alarm
Resistor
1.5 k or 2.2
Alarm
Resistor
Alarm
Contacts
Tamper
ontacts Tampe
Contac
Figure 11: Dual Point/Zone Input Wiring
ON
123456
tatus LED
Figure 12: DX2010 Status LED
ON
123456
OFF ON
Example:
Module Address 102
Figure 13: DIP Switch Configuration
DIP Switch Settings DIP Switch Settings
DIP
Switches S1 S2 S3 S4 S5 S6 DIP
Switches S1 S2 S3 S4 S5 S6
Module
Address 32 16 8 4 2 1 Module
Address 32 16 8 4 2 1
101 OFF OFF OFF OFF OFF OFF 117 OFF ON OFF OFF OFF OFF
102 OFF OFF OFF OFF OFF
ON 118 OFF
ON OFF OFF OFF ON
103 OFF OFF OFF OFF
ON OFF 119 OFF
ON OFF OFF ON OFF
104 OFF OFF OFF OFF
ON ON 120 OFF
ON OFF OFF ON ON
105 OFF OFF OFF
ON OFF OFF 121 OFF ON OFF ON OFF OFF
106 OFF OFF OFF
ON OFF ON 122 OFF
ON OFF ON OFF ON
107 OFF OFF OFF
ON ON
OFF 123 OFF
ON OFF ON ON
OFF
108 OFF OFF OFF
ON ON ON 124 OFF
ON OFF ON ON ON
109 OFF OFF
ON OFF OFF OFF 125 OFF ON ON
OFF OFF OFF
110 OFF OFF
ON OFF OFF ON 126 OFF
ON ON
OFF OFF ON
111 OFF OFF
ON OFF ON OFF 127 OFF
ON ON
OFF ON OFF
112 OFF OFF
ON OFF ON ON 128 OFF
ON ON
OFF ON ON
113 OFF OFF
ON ON
OFF OFF 129 OFF ON ON ON
OFF OFF
114 OFF OFF
ON ON
OFF ON 130 OFF
ON ON ON
OFF ON
115 OFF OFF
ON ON ON
OFF 131 OFF
ON ON ON ON
OFF
116 OFF OFF
ON ON ON ON 132 OFF
ON ON ON ON ON
ON indicates the DIP switch is in the ON position; OFF indicates the DIP switch is in the OFF position.
Table 2: Address Jumper Settings